HomeMy WebLinkAboutWCWD CCR 2022Willow County Water District
2022 Consumer Confidence Report
We test the drinking water quality for many constituents as required by state and federal regulations. This report shows the
results of our monitoring for the period of January 1 - December 31, 2022.
The sources of drinking water (both tap and bottled waters) include rivers, lakes, streams, ponds, reservoirs, springs and
wells. As water travels over the surface of the land or through the ground, it dissolves naturally occurring minerals and,
in some cases, radioactive material. It can, also, pick up substances resulting from the presence of animals or from
human activity.
This report is designed to inform you about the quality of water we delivered to you from the districts two well sites
located on the south end of the Ukiah Valley.
You can learn more about the District by attending any of our regularly scheduled board meetings held on the second
Monday of each month at 6:30 PM online via zoom, link available at
https://willowcountywaterdistrict.org/board-meetings
If you have any questions about this report or concerning the Willow Water District, please contact Jared Walker at
707-462-2666.
Drinking Water Source Assessment Information: A (DWSA) was completed for the Districts wells in December,
2003. You can obtain a completed copy of this report by contacting the District Office.
Summary: There have been no contaminants detected from the wells, however the sources are considered vulnerable to
the following activities: Agricultural drainage, Sewer collection system, Wells – Agricultural / Irrigation, Automobile –
Gas Stations, Septic systems
TERMS USED IN THIS REPORT
Maximum Contaminant Level (MCL): The highest
level of a contaminant that is allowed in drinking water.
Primary MCLs are set as close to the PHGs (or MCLGs)
as is economically and technologically feasible.
Secondary MCLs are set to protect the odor, taste, and
appearance of drinking water.
Maximum Contaminant Level Goal (MCLG): The
level of a contaminant in drinking water below which
there is no known or expected risk to health. MCLGs are
set by the U.S. Environmental Protection Agency
(USEPA).
Public Health Goal (PHG): The level of a contaminant
in drinking water below which there is no known or
expected risk to health. PHGs are set by the California
Environmental Protection Agency.
Maximum Residual Disinfectant Level (MRDL): The
highest level of a disinfectant allowed in drinking water.
There is convincing evidence that addition of a
disinfectant is necessary for control of microbial
contaminants.
Maximum Residual Disinfectant Level Goal
(MRDLG): The level of a drinking water disinfectant
below which there is no known or expected risk to health.
MRDLGs do not reflect the benefits of the use of
disinfectants to control microbial contaminants.
Primary Drinking Water Standards (PDWS): MCLs and
MRDLs for contaminants that affect health along with their
monitoring and reporting requirements, and water treatment
requirements.
Secondary Drinking Water Standards (SDWS): MCLs for
contaminants that affect taste, odor, or appearance of the
drinking water. Contaminants with SDWSs do not affect the
health at the MCL levels.
Treatment Technique (TT): A required process intended to
reduce the level of a contaminant in drinking water.
Regulatory Action Level (AL): The concentration of a
contaminant which, if exceeded, triggers treatment or other
requirements that a water system must follow.
Variances and Exemptions: Department permission to
exceed an MCL or not comply with a treatment technique
under certain conditions.
ND: not detectable at testing limit
ppm: parts per million or milligrams per liter (mg/L)
ppb: parts per billion or micrograms per liter (ug/L)
ppt: parts per trillion or nanograms per liter (ng/L)
ppq: parts per quadrillion or pictogram per liter (pg/L)
pCi/L: picocuries per liter (a measure of radiation)
Contaminants that may be present in source water include:
• Microbial contaminants, such as viruses and bacteria that may come from sewage treatment plants, septic systems,
agricultural livestock operations, and wildlife.
• Inorganic contaminants, such as salts and metals, that can be naturally-occurring or result from urban storm water runoff,
industrial or domestic wastewater discharges, oil and gas production, mining, or farming.
• Pesticides and herbicides, that may come from a variety of sources such as agriculture, urban storm water runoff, and
residential uses.
• Organic chemical contaminants, including synthetic and volatile organic chemicals that are by-products of industrial
processes and petroleum production, and can also come from gas stations, urban storm water runoff, agricultural
application, and septic systems.
• Radioactive contaminants that can be naturally-occurring or be the result of oil and gas production and mining activities.
In order to ensure that tap water is safe to drink, the USEPA and the state Department of Public Health (Department)
prescribe regulations that limit the amount of certain contaminants in water provided by public water systems. Department
regulations also establish limits for contaminants in bottled water that provide the same protection for public health.
Tables 1, 2, 3, 4, 5, 7, and 8 list all of the drinking water contaminants that were detected during the most recent sampling
for the constituent. The presence of these contaminants in the water does not necessarily indicate that the water poses a health
risk. The Department allows us to monitor for certain contaminants less than once per year because the concentrations of these
contaminants do not change frequently. Some of the data, though representative of the water quality, are more than one year
old.
TABLE 1 – SAMPLING RESULTS SHOWING THE DETECTION OF COLIFORM BACTERIA
Microbiological
Contaminants
(complete if bacteria detected)
Highest No.
of Detections
No. of
months
in
violation
MCL MCLG Typical Source of Bacteria
Total Coliform Bacteria (In a mo.)
0 0 More than 1 sample in a month
with a detection 0 Naturally present in the environment
Fecal Coliform or E. coli (In the year)
0 0
A routine sample and a repeat
sample detect total coliform
and either sample also detects
fecal coliform or E. coli
0 Human and animal fecal waste
TABLE 2 – SAMPLING RESULTS SHOWING THE DETECTION OF LEAD AND COPPER
Lead and Copper
(complete if lead or copper
detected in the last sample set)
No. of
samples
collected
90th
percentile
level
detected
No. sites
exceeding
AL
AL PHG Typical Source of Contaminant
Lead (ppb)
2020 20 0 0 15 0.2
Internal corrosion of household water
plumbing systems; discharges from
industrial manufacturers; erosion of natural
deposits
Copper (ppm)
2020 20 0.92 0 1.3 0.17
Internal corrosion of household plumbing
systems; erosion of natural deposits;
leaching from wood preservatives
TABLE 3 – SAMPLING RESULTS FOR SODIUM AND HARDNESS
Chemical or Constituent
(and reporting units)
Sample
Date
Level
Detected
Range of
Detections MCL PHG
(MCLG) Typical Source of Contaminant
Sodium (ppm) 2022 13 13 none none Salt present in the water and is generally
naturally occurring
Hardness (ppm) 2022 114 114 none none
Sum of polyvalent cations present in the
water, generally magnesium and calcium,
and are usually naturally occurring
*Any violation of an MCL or AL is asterisked. Additional information regarding the violation is provided later in this report.
TABLE 4 – DETECTION OF CONTAMINANTS WITH A PRIMARY DRINKING WATER STANDARD
Chemical or Constituent
(and reporting units)
Sample
Date
Level
Detected
Range of
Detections
MCL
[MRDL]
PHG
(MCLG)
[MRDLG]
Typical Source of Contaminant
Fluoride (ppm) 2022 0 < .10 2.0 1
Erosion of natural deposits; water
additive which promotes strong teeth;
discharge from fertilizer and
aluminum factories
Nitrate (ppm) 2022 .28 0 - .56 10 10
Runoff and leaching from fertilizer
use; leaching from septic tanks and
sewage; erosion of natural deposits
Total Trihalomethanes
(ppb) 2022 11.21 11.21 80 N/A By-product of drinking water
chlorination
Haloacetic Acids (ppb) 2022 603. 6.3 60 N/A By-product of drinking water
chlorination
Chlorine (ppm) 2020 0.35 0.2 – 0.5 4 4 Drinking water disinfectant added for
treatment
Gross Alpha Particle
Activity (Pci/L) 2021 1.5 1.09 – 1.91 15 0 Erosion of natural deposits
TABLE 5 – DETECTION OF CONTAMINANTS WITH A SECONDARY DRINKING WATER STANDARD
Chemical or Constituent
(and reporting units)
Sample
Date
Level
Detected
Range of
Detections MCL Typical Source of Contaminant
Sulfate (ppm) 2022 13.05 9.1 - 17 500 Runoff/leaching natural deposits; industrial waste
Chloride (ppm) 2022 7.65 7.6 – 7.7 500 Runoff/leaching natural deposits; seawater influence
Specific Conductance
(umhos/cm) 2022 240 240 1000 Substances that form ions when in water
Total Dissolved solids
(ppm) 2022 150 150 1000 Runoff/leaching natural deposits
Turbidity (NTU) 2022 .445 .1 - .85 5 units Soil Runoff
TABLE 6 – DETECTION OF UNREGULATED CONTAMINANTS
Chemical or Constituent
(and reporting units)
Sample
Date
Level
Detected
Range of
Detections Notification Level Health Effects Language
Boron (ppb) 2003 170 160 - 180 1000 Erosion of natural deposits
*Any violation of an MCL, MRDL, or TT is asterisked. Additional information regarding the violation is provided later in this report.
Additional General Information on Drinking Water
Drinking water, including bottled water, may reasonably be expected to contain at least small amounts of some
contaminants. The presence of contaminants does not necessarily indicate that the water poses a health risk. More
information about contaminants and potential health effects can be obtained by calling the USEPA’s Safe Drinking
Water Hotline (1-800-426-4791).
Some people may be more vulnerable to contaminants in drinking water than the general population. Immuno-compromised
persons such as persons with cancer undergoing chemotherapy, persons who have undergone organ transplants, people with
HIV/AIDS or other immune system disorders, some elderly, and infants can be particularly at risk from infections. These people
should seek advice about drinking water from their health care providers. USEPA/Centers for Disease Control (CDC)
guidelines on appropriate means to lessen the risk of infection by Cryptosporidium and other microbial contaminants are
available from the Safe Drinking Water Hotline (1-800-426-4791).
Summary Information for Violation of a MCL, MRDL, AL, TT,
or Monitoring and Reporting Requirement
VIOLATION OF A MCL, MRDL, AL, TT, OR MONITORING AND REPORTING REQUIREMENT
Violation Explanation Duration Actions Taken to Correct
the Violation
Health Effects
Language
0
For Water Systems Providing Ground Water as a Source of Drinking Water
TABLE 7 – SAMPLING RESULTS SHOWING
FECAL INDICATOR-POSITIVE GROUND WATER SOURCE SAMPLES
Microbiological Contaminants
(complete if fecal-indicator
detected)
Total No. of
Detections
Sample
Dates
MCL
[MRDL]
PHG
(MCLG)
[MRDLG]
Typical Source of Contaminant
E. coli (In the year)
0 0 (0) Human and animal fecal waste
Enterococci (In the year)
0 TT N/A Human and animal fecal waste
Coliphage (In the year)
0 TT N/A Human and animal fecal waste
Summary Information for Fecal Indicator-Positive Ground Water Source Samples,
Uncorrected Significant Deficiencies, or Ground Water TT
SPECIAL NOTICE OF FECAL INDICATOR-POSITIVE GROUND WATER SOURCE SAMPLE
SPECIAL NOTICE FOR UNCORRECTED SIGNIFICANT DEFICIENCIES
VIOLATION OF GROUND WATER TT
TT Violation Explanation Duration Actions Taken to Correct
the Violation
Health Effects
Language
0