HomeMy WebLinkAboutRVCWD CCR 20182018 Consumer Confidence Report
Water System Name: Millview, Calpella & Redwood Valley Report Date: 6/l/2019
County Water District
We test the drinking water quality for marry constituents as required by state and federal regulations. This report shows
the results of our monitoring for the period of Januar y I - December 31, 2018 and may include earlier monitoring data.
Este informe contiene informaci6n muy importante sobre su agua potable. Traduzealo 6 liable con alguien que to
entienda bien.
Type of water source(s) in use: Blend of surface water and well water
Name & general location of source(s): Russian River, Calpella Well 1 and Millview Well 6
Drinking Water Source Assessment information: Drinking water assessment report completed June 2011
Time and place of regularly scheduled board meetings for public participation:
Millview CWD: 3rd Tuesday of each month at District Office 151 Laws Ave. Ukiah 6pm
Calpella CWD: 3rd Wednesday of each month at District Office 151 Laws Ave. Ukiah 6pm
Redwood Valley CWD: 3rd Thursday of each month at District Office 151 Laws Ave. Ukiah 6pm
For more information, contact: District Office Phone: Millview (707) 462-7229
Calpella (707) 462-2666
Redwood Valley (707) 485-0679
I TERMS USED IN THIS REPORT I
Maximum Contaminant Level (MCL): The highest
level of a contaminant that is allowed in drinking
water. Primary MCLs are set as close to the PHGs (or
MCLGs) as is economically and technologically
feasible. Secondary MCLs are set to protect the odor,
taste, and appearance of drinking water.
Maximum Contaminant Level Goal (MCLG): The
level of a contaminant in drinking water below which
there is no known or expected risk to health. MCLGs
are set by the U.S. Environmental Protection Agency
(USEPA).
Public Health Goal (PHG): The level of a
contaminant in drinking water below which there is no
known or expected risk to health. PHGs are set by the
California Environmental Protection Agency.
Maximum Residual Disinfectant Level (MRDL):
The highest level of a disinfectant allowed in drinking
water. There is convincing evidence that addition of a
disinfectant is necessary for control of microbial
contaminants.
Primary Drinking Water Standards (PDWS): MCLs and
MRDLs for contaminants that affect health along with their
monitoring and reporting requirements, and water treatment
requirements.
Secondary Drinking Water Standards (SDWS): MCLs
for contaminants that affect taste, odor, or appearance of the
drinking water. Contaminants with SDWSs do not affect the
health at the MCL levels.
Treatment Technique (TT): A required process intended to
reduce the level of a contaminant in drinking water.
Regulatory Action Level (AL): The concentration of a
contaminant which, if exceeded, triggers treatment or other
requirements that a water system must follow.
Variances and Exemptions: State Board permission to
exceed an MCL or not comply with a treatment technique
under certain conditions.
ND: not detectable at testing limit
ppm: parts per million or milligrams per liter (mg/L)
Maximum Residual Disinfectant Level Goal ppb: parts per billion or micrograms per liter (µg/L)
(MRDLG): The level of a drinking water disinfectant ppt: parts per trillion or nanograms per liter (ng/L)
below which there is no known or expected risk to parts per quadrillion or ico ram per liter Q L
health. MRDLGs do not reflect the benefits of the use ppq' l p q p g p (p )
of disinfectants to control microbial contaminants. pCi/L: picocuries per liter (a measure of radiation)
20l a .4WlQ r'f R Fn)-m n,,..:. 4 1,,,.. In t c
Consumer Confidence Report Pave 2 o{b
The sources of drinking water (both tap water and bottled water) include rivers, lakes, streams, ponds, reservoirs,
springs, and wells. As water travels over the surface of the land or through the ground, it dissolves naturally -occurring
minerals and, in some cases, radioactive material, and can pick up substances resulting from the presence of animals or
from human activity.
Contaminants that may be present in source water include:
® Microbial contaminants, such as viruses and bacteria, which may come from sewage treatment plants, septic systems,
agricultural livestock operations, and wildlife.
• Inorganic contaminants, such as salts and metals, that can be naturally -occurring or result from urban stormwater
runoff, industrial or domestic wastewater discharges, oil and gas production, mining, or farming.
® Pesticides and herbicides, which may come from a variety of sources such as agriculture, urban stormwater runoff,
and residential uses.
s Organic chemical C0171aminants, including synthetic and volatile organic chemicals, which are by-products of
industrial processes and petroleum production, and can also come from gas stations, urban stormwater runoff,
agricultural application, and septic systems.
® Radioactive contaminants, which can be naturally -occurring or be the result of oil and gas production and mining
activities.
In order to ensure that tap water is safe to drink, the USEPA and the State Water Resources Control Board (State
Board) prescribe regulations that limit the amount of certain contaminants in water provided by public water systems.
State Board regulations also establish limits for contaminants in bottled water that provide the same protection for public
health.
Tables 1, 2, 3, 4, 5, 7, and 8 list all of the drinking water contaminants that were detected during the most recent
sampling for the constituent. The presence of these contaminants in the water does not necessarily indicate that the
water poses a health risk. The State Board allows us to monitor for certain contaminants less than once per year because
the concentrations of these contaminants do not change frequently. Some of the data, though representative of the water
quality, are more than one year old.
TABLE l — SAMPLING RESULTS SHOWING THE DETECTION OF COLIFORM BACTERIA
Microbiological
Highest No.
No. of months in
Contaminants
f Detections
violation
MCL
MCLG
Typical Source of Bacteria
(complete if bacteria detected)
Total Coliform Bacteria
0
0
More than I sample in a
0
Naturally present in the
month with a detection
environment
Fecal Coliform or E. eoli
0
0
A routine sample and a
0
Human and animal fecal waste
repeat sample detect
total coliform and either
sample also detects fecal
coliform or E. coli
TABLE 2 — SAMPLING
RESULTS SHOWING THE DETECTION OF LEAD AND COPPER
90111No.
Lead and Copper
Sample
No. of
percentile
sites
(complete if lead or copper
Date
samples
level
exceeding
AL
PHG
Typical Source of Contaminant
detected in the last sample set)
collected
AL
detected
Lead (ppb)
Internal corrosion of household
Millview
2016
20
ND
0
15
0.2
water plumbing systems;
Calpella
2016
5
ND
0
15
0.2
discharges from industrial
Redwood Valley
2016
20
ND
0
15
0.2
manufacturers; erosion of natural
deposits
Copper (ppm)
Internal corrosion of household
Millview
2016
20
1.20
0
1.3
0.17
plumbing systems; erosion of
Calpella
2016
5
0.165
0
1.3
0.17
natural deposits; leaching from
Redwood Valley
2016
20 1
0.20
0
1.3
0.17
wood preservatives
TABLE 3 — SAMPLING
RESULTS FOR SODIUM AND HARDNESS
Chemical or Constituent
Sample
Level
Range of
PHG
(and reporting units)
Date
Detected
Detections
MCL
(MCLG)
Typical Source of Contaminant
Sodium (ppm)
201 S
6.45
6.4 — 6.5
none
F`�7generally
Salt present in the water and is
naturally occurring
90l.4 .ew.e rf-n ram,•», I_ 1)n r c
Consumer Confidence Report Page 3 of 6
Sum of polyvalent cations present
Hardness (ppm)
2018
104
85 - 140
none
none
in the water, generally magnesium
and calcium, and are usually
naturally occurring
"Anv vrotation o1 an A9CL or•AL is asterisked Adtlitinnal irrfnrntntinn ream rlina /he vinln/in» is ro•nvidnr/Inra,• fin rlolc ronn,•r
TABLE 4 — DETECTION OF CONTAMINANTS WITH A PRIMARY DRINKING WATER STANDARD
Chemical or Constituent
Sample
Level
Range of
MCL
PHG
(and reporting units)
Date
Detected
Detections
(MRDLI
(MCLG)
Typical Source of Contaminant
IMRDLGI
Erosion of natural deposits; residue
Aluminum (ppm)
2018
.110
0 - .330
1
0.6
from some surface water treatment
processes.
Gross Alpha Particle
Activity (Pci/L)
2016
0.37
0 - .973
15
0
Erosion of natural deposits
Erosion of natural deposits; water
Fluoride (ppm)
2018
.036
0 - .l 1
2
1
additive which promotes strong
teeth; discharge from fertilizer and
aluminum factories
Runoff and leaching from fertilizer
Nitrate (as N) (ppm)
2018
0.785
0 — 2.2
45
45
use; leaching from septic tanks and
sewage; erosion of natural deposits
Total Trihalomethanes
By-product of drinking water
(TTHM) (ppb)
2018
30.58
0 — 78.68
80
N/A
disinfection
I-Ialoacetic Acids (HAA5)
By-product of drinking water
(ppb)
2018
8.51
0 — 23.80
60
N/A
disinfection
TABLE 5 — DETECTION OF CONTAMINANTS WITH A SECONDARY
DRINKING WATER STANDARD
Chemical or Constituent
Sample
Level Detected
Range of
MCL
PHG
Typical Source of Contaminant
(and reporting units)
Date
Detections
(MCLG)
Erosion of natural deposits;
Aluminum (ppb)
2018
.110
0 - .330
200
N/A
residual from some surface water
treatment processes
Naturally -occurring organic
Color (Units)
2018
2.16
0 - 13
15
N/A
materials
Leaching from natural deposits;
Iron (ppb)
2018
236.66*
0 - 600
300
N/A
Industrial wastes
Manganese (ppb)
2018
53.33*
0- 160
50
N/A
Leaching from natural deposits
Naturally -occurring organic
Odor -threshold (Units)
2018
0
0
3
N/A
materials
Turbidity (Units)
2018
2.48
0 — 9.50
5
N/A
Soil runoff
Runoff/leaching from natural
Zinc(ppm)
2018
0
0
5
N/A
deposits; industrial wastes
Total dissolved solids
Runoff/leaching from natural
(TDS) (ppm)
2018
146.66
120 - 200
1000
N/A
deposits
Specific Conductance
Substances that form ions when in
(US/cm)
2018
250
200 - 340
1600
N/A
water; seawater influence
Runoff/leaching from natural
Chloride (ppm)
2018
5.06
3.1 - 8.7
500
N/A
deposits; seawater influence
2014 SIVS CCR For•rn n—.r.. 1 I— Wn 1;
Consznner Confidence Report Par7e -d of 6
Runoff/leaching from natural
Sulfate (ppm) 2018 9.5 8.6 - 10 500 N/A deposits; industrial wastes
TABLE 6 — DETECTION OF UNREGULATED CONTAMINANTS
Chemical or Constituent Sample Range of
(and reporting units) Date Level Detected Detections Notification Level Health Effects Language
'Any vtotauon or an A -L, MKOL, or I is asterisked. Additional information regarding Nre violation is provided later in this report.
Additional General Information on Drinking Water
Drinking water, including bottled water, may reasonably be expected to contain at least small amounts of some
contaminants. The presence of contaminants does not necessarily indicate that the water poses a health risk. More
information about contaminants and potential health effects can be obtained by calling the USEPA's Safe Drinking Water
Hotline (1-800-426-4791).
Some people may be more vulnerable to contaminants in drinking water than the general population. Immuno-
compromised persons such as persons with cancer undergoing chemotherapy, persons who have undergone organ
transplants, people with HIV/AIDS or other immune system disorders, some elderly, and infants can be particularly at
risk from infections. These people should seek advice about drinking water from their health care providers.
USEPA/Centers for Disease Control (CDC) guidelines on appropriate means to lessen the risk of infection by
Cryptosporidium and other microbial contaminants are available from the Safe Drinking Water Hotline (1-800-426-
4791).
Lead -Specific Language for Community Water Systems: If present, elevated levels of lead can cause serious health
problems, especially for pregnant women and young children. Lead in drinking water is primarily from materials and
components associated with service lines and home plumbing. Millview, Calpella and Redwood Valley County Water
Districts are responsible for providing high quality drinking water, but cannot control the variety of materials used in
plumbing components. When your water has been sitting for several hours, you can minimize the potential for lead
exposure by flushing your tap for 30 seconds to 2 minutes before using water for drinking or cooking. If you are
concerned about lead in your water, you may wish to have your water tested. Information on lead in drinking water,
testing methods, and steps you can take to minimize exposure is available from the Safe Drinking Water Hotline or at
http://www.epa.gov/safewater/lead.
Summary Information for Violation of a MCL, MRDL, AL, TT,
or Monitoring and Reporting Requirement
VIOLATION OF A MCL, MRDL, AL, TT, OR MONITORING AND REPORTING REQUIREMENT
Violation
Explanation
Duration
Actions Taken to Correct
Health Effects
the violation
Language
*Iron,
Levels well below
ongoing
Filtration
Manganese,
mcl after
Turbidity
filtration
*Iron and Manganese exceeded the MCL, these numbers are reflected in raw water prior to filtration and
treatment. State Water Resource Control Board has not required sampling post filtration and treatment.
For Water Systems Providing Ground Water as a Source of Drinking Water
2014 SWS CCR Form n ,.; .r r,..,, ')n I s
Conszuner Confidence Report
Pate oi6
TABLE 7 — SAMPLING RESULTS SHOWING
FECAL INDICATOR -POSITIVE GROUND WATER SOURCE SAMPLES
Microbiological Contaminants
(complete if fecal -indicator detected)
Total No. of
Detections
Sample MCL
Dates (MRDLJ
PHG
(MCLG)
[MRDLG]
Typical Source of Contaminant
E. coli
(In the year)
0
(0)
Human and animal fecal waste
Enterococci
(In the year)
TT
n/a
Human and animal fecal waste
Coliphage
(In the year)
TT
n/a
Human and animal fecal waste
Summary Information for Fecal Indicator -Positive Ground Water Source Samples,
Uncorrected Significant Deficiencies, or Ground Water TT
SPECIAL NOTICE OF FECAL INDICATOR -POSITIVE GROUND WATER SOURCE SAMPLE
SPECIAL NOTICE FOR UNCORRECTED SIGNIFICANT DEFICIENCIES
VIOLATION OF GROUND WATER TT
TT Violation Explanation Duration Actions Taken to Correct Health Effects
the Violation Language
For Systems Providing Surface Water as a Source of Drinking Water
TABLE 8 - SAMPLING RESULTS SHOWING TREATMENT OF SURFACE WATER SOURCES
Treatment Technique (a)
(Type of approved filtration technology used)
Turbidity of the filtered water must:
Turbidity Performance Standards (b)
I — Be less than or equal to _.3_ NTU in 95% of measurements in a month.
(that must be met through the water treatment process)
2 — Not exceed 1.0 NTU for more than eight consecutive hours.
3 — Not exceed 5.0 NTU at any time.
Lowest monthly percentage of samples that met Turbidity
98.1
Performance Standard No. 1.
Highest single turbidity measurement during the year
.405 ntu
Number of violations of any surface water treatment
0
2014 SWS CCR Form Ro„i—d 1— M I ;
Conszrnzer Confidence Report Pa e�6n6
requirements
(a) A required process intended to reduce the level of a contaminant in drinking water.
(b) Turbidity (measured in NTU) is a measurement of the cloudiness of water and is a good indicator of water quality and filtration performance.
Turbidity results which meet performance standards are considered to be in compliance with filtration requirements.
* Anv violation of a TT is marked irid7 an asterisk. Additional information regarding the violation is provided below.
Summary Information for Violation of a Surface Water TT
VIOLATION OF A SURFACE WATER TT
TT Violation
Explanation
Duration
Actions Taken to Correct
the Violation
Health Effects
Language
Summary Information for Operating Under a Variance or Exemption
2014 SWS CCR Form n .,: 1-11 In r ;