Loading...
HomeMy WebLinkAboutManley's Boiler 2017-10-05SHORT FORM CONSTRUCTION CONTRACT ##1718127 This Agreement is made and entered on October 5, 2017, in Ukiah, California, by and between Manley's Boiler's Inc., a CA Corporation ("Contractor") and the City of Ukiah ("City"), a general law municipal corporation. RECITALS: 1. The plans and specifications for this work ("the Work") are contained in Exhibit A - Bid Specification, which is attached hereto and incorporated herein by this reference. 2. Contractor is properly licensed and qualified to perform the work. 3. Whenever this Agreement calls for City approval or notification, the approval or notification must be signed by the City Manager or his or her designee. AGREEMENT: Wherefore, in consideration of the foregoing facts and the terms and conditions as further stated herein, the parties hereby agree as follows. 1. PERFORMANCE OF THE WORK Contractor will perform the Work as further provided herein. 1.1 Time of Performance. Contractor shall commence the Work when receiving a formal Notice to Proceed, and shall complete the Work by no later than thirty (30) calendar days from receipt of Notice to Proceed. 1.1.1. X [check if applicable; It is agreed by the parties to the contract that time is of the essence and that, in case all the work is not completed before or upon the expiration of the time limit as set forth, damage, other than those cost items identified in section 1.1.2, will be sustained by the City and that it is and will be impracticable to determine the actual amount of damage by reason of such delay; and it is therefore agreed that, subject to Sections 1.13-1.14, below, the .J:r\a�rt.ms0o\s:��^rt form. construction contract cc -or Pt 201? 1 Contractor will pay to the City the sum of five hundred dollars ($500.00) per day for each and every calendar day's delay beyond the time prescribed. 1.1.2 [c`:eck if applicable] In case the work called for under this contract is not completed within the time limit stipulated herein, the City shall have the right as provided hereinabove, to extend the time of completion thereof. If the time limit be so extended, the City shall have the right to charge to the Contractor and to deduct from the final payment for the work the actual cost to the City of engineering, inspection, superintendence and other overhead expenses which are directly chargeable to the contract and which accrue during the period of such extension, except that the cost of final unavoidable delays shall not be included in such charges. 1.2 Construction of Contract Documents. Contractor will perform the Work in compliance with the plans and specifications set forth in the attached Exhibit A. If there is any inconsistency or conflict between the plans and the specifications, the specifications will prevail. If there is any inconsistency between the plans and the specifications and this agreement, the terms of this Agreement shall prevail, unless expressly stated otherwise in a particular specification. 1.3 Contractor furnished items. Contractor will furnish all necessary labor, materials, tools, equipment, and transportation necessary to perform the Work. 1.4 New SB 854 requirements 1.4.1 No contractor or subcontractor may be listed on a bid proposal for a public works project (submitted on or after March 1, 2015) unless registered with the Department of Industrial Relations pursuant to Labor Code section 1725.5 [with limited exceptions from this requirement for bid purposes only under Labor Code section 1771.1(a)]. 1.4.2 No contractor or subcontractor may be awarded a contract for public work on a public works project (awarded on or after April 1, 2015) unless registered with the Department of Industrial Relations pursuant to Labor Code section 1725.5. 1.4.3 This project is subject to compliance monitoring and enforcement by the Department of Industrial Relations. �::uAagrrms06Vshrr;_ form conscruct;cn cnncracl. i,-onPY 5, 2017 I/ 1.4.4 The Labor Commissioner through the Division of Labor Standards Enforcement (DLSE) may at any time require contractors and subcontractors to furnish electronic certified payroll records directly to DLSE. Commencing with contracts awarded or after April 1, 2015, all contractors and subcontractors must furnish electronic certified payroll records directly to the DLSE. 1.4.5 The Prime Contractor is required to post job notices at the job site as prescribed by regulations (currently, 8 CCR §16451 (d) . ) 1.5 Use of Employees. 1.5.1. Contractor and any subcontractors shall pay all mechanics and laborers employed by them to work upon the site of the work unconditionally and without subsequent deductions or rebate on any account the full amounts due at the time of payment at wage rates not less than those contained in the applicable prevailing wage determination, regardless of any contractual relationship which may be alleged to exist between the Contractor and subcontractors and such laborers and mechanics. 1.5.2. Contractor shall comply with the California Labor Code Section 1775. In accordance with said Section 1775, Contractor shall forfeit as a penalty to the City, $50.00 for each calendar day or portion thereof, for each workman paid less than the stipulated prevailing rates for such work or craft in which such workman is employed for any work done under the Contract by him or her or by any subcontractor under him or her in violation of the provisions of the Labor Code and in particular, Labor Code Sections 1770 to 1780, inclusive. In addition to said penalty and pursuant to Section 1775, the difference between such stipulated prevailing wage rates and the amount paid to each workman for each calendar day or portion thereof for which each workman was paid less than the stipulated prevailing wage rate shall be paid to each workman by the Contractor. 1.5.3. Pursuant to the provision of Section 1770 of the Labor Code of the State of California, City has ascertained the general prevailing rate of wages (which rate includes employer payments for health and welfare, vacation, pension and similar purposes) applicable to the work to be done, for straight time work. The holiday wage rate listed shall be applicable to all ag,'r7s06\short form oonstructior contract ',ctoher 2011 3 holidays recognized in the collective bargaining agreement of the particular craft, classification, or type of workers concerned. Copies of the General Prevailing Wage Determination are on file in the office of the City Engineer and are available to the Contractor on request. The Contractor shall post the wage determination at the site of work in a prominent place where the workers can easily see it. 1.5.4. City will not recognize any claim for additional compensation because the Contractor has paid any rate in excess of the prevailing wage rate obtained from the City Engineer. The possibility of wage increases is one of the elements to be considered by the Contractor in determining his or her bid and will not in any circumstances be considered as the basis for a claim against the City. 1.5.5. Travel and Subsistence Payments. Contractor shall make travel and subsistence payments to each worker needed to execute the work in accordance with the requirements in Section 1773.8 of the Labor Code (Chapter 880, Statutes of 1968). 1.5.6. Apprentices. Attention is directed to the provisions in Sections 1777.5 (Chapter 1411, Statutes of 1968) and 1777.6 of the California Labor Code concerning the employment of apprentices by the Contractor or any subcontractor under him. Contractor and any subcontractor under him or her shall comply with the requirements of said sections in the employment of apprentices. Information relative to apprenticeship standards, wage schedules and other requirements may be obtained from the Director of Industrial Relations, ex officio the Administrator of Apprenticeship, San Francisco, California, or from the Division of Apprenticeship Standards and its branch offices. Copies of Labor Code Sections 1771 (requiring prevailing wages), 1775 (imposing penalties, including a $50 per day, per worker forfeiture, for failure to pay prevailing wages), 1776 (requiring contractor to maintain available for inspection certified payroll records), 1777.5 (requiring certain apprenticeship programs), 1813 :u\agrtmsO6\chor:. form construction contract r, - r,ev `L 01"7 4 (imposing penalties for failure to make records available for inspection) and 1815 (requiring time and 1-2 for overtime) are available at the Department of Industrial Relations website at 1-,rIr : , w.d_ ca.gnv/ 1.6 CITY Inspector. CITY may designate an architect, engineer, other design professional or other inspector ("Inspector") to supervise and/or inspect Contractor's performance of the Work. The Inspector shall have no authority to change the Work, the compensation for performing the Work or the time for completing the Work without City's prior written approval. City shall notify the Contractor in writing, if it designates an Inspector. 1.7 Site Conditions. Contractor acknowledges that it has inspected the work site and any improvements involving the Work and satisfied itself as to the conditions which can affect the Work or its cost. Contractor has not relied on any representation by CITY or its officers or employees as to the condition of the site or the houses or any condition that might affect the cost of performing this Agreement. 1.8 New Products Required. All equipment, materials or fixtures furnished by Contractor under this Agreement shall be new and of the most suitable grade for the intended purpose, unless otherwise specifically provided. 1.9 Compliance with Laws. The Contractor shall give all notices and comply with all applicable laws, ordinances, codes, rules and regulations. The Contractor shall secure and pay for all permits, fees, and licenses necessary for the proper execution and completion of the work. 1.10 Protection of Site and Improvements. The Contractor shall preserve and protect the site, grounds and any involved improvements and shall not alter or damage any portion thereof, except as is absolutely necessary in order to perform the Work. The Contractor shall repair or replace, as directed by CITY, any property that it damages, looses or destroys in violation of this paragraph. Contractor shall assume full responsibility for maintaining the safety of the worksite in compliance with all applicable state and federal worker safety and protection laws and shall maintain the worksite in compliance with all such laws. .,. �. ,' rtms05\rh^rt form constructicn -ontr act c*ores , 2017 5 1.11 Inspection of Work. The Contractor shall ensure that the Work is available for inspection by CITY or its Inspector at all reasonable times and that no work is covered up or rendered incapable of inspection without prior notice to CITY or its Inspector and a reasonable opportunity for inspection. The presence or absence of an CITY inspector or the conduct of an inspection by CITY or its Inspector shall not relieve the Contractor from any contract requirement or compliance with Exhibit A. 1.12 Title. The Contractor warrants that it conveys full and complete title, free of all liens and encumbrances, to all materials, supplies, fixtures and equipment furnished to CITY under this Agreement and agrees to fully defend and indemnify CITY, its officers and employees, and the houses and homebuyers included in the Work from and against any claim, lien, charge, debt, cost, expense or liability arising from a breach of said warranty. 1.13 Warranties. In addition to any other warranties in this contract, the Contractor warrants that the Work conforms to the contract requirements and is free of any defect in equipment, material or workmanship for a period of one year from the date of final acceptance of the Work by CITY. If CITY accepts any part of the Work before final acceptance of the entire Work, the warranty shall continue for the period of one year from the date of such partial acceptance. The Contractor shall remedy, at the Contractor's expense, any failure to conform, or any defect. [Initial if following sentence applies / / / /] CITY shall retain _% of the Contract Amount to secure the Contractor's warranty and shall remit the unused portion of that amount at the end of the warranty period. The time limit of this warranty shall not apply to any latent defects, or gross negligence or fraud on the part of the Contractor. 1.14. Extension of Time. Should any delays occur which the City may consider unavoidable, as herein defined, the Contractor shall, pursuant to his or her application, be allowed an extension of time proportional to said delay or delays, beyond the time herein set forth, in which to complete this contract; and liquidated damages for delay shall not be charged against the Contractor by the City during an extension of time granted because of unavoidable delay or delays. Any claim by Contractor for a time extension based on unavoidable .;:uAa3 r'. ❑s06\;h-r_ [onn constrcct ian ronLcart uctnber �, :'017 C delays shall be based on written notice delivered to the City within 15 days of the occurrence of the event giving rise to the claim. Failure to file said written notice within the time specified shall constitute a wa-ver of said claim. Notice of the full extent of the claim and all supporting data must be delivered to the City within 45 days of the occurrence unless the City specifies in writing a longer period. All claims for a time extension must be approved by the City and incorporated into a written change order. 1.15. Unfavorable Weather and Other Conditions. During unfavorable weather and other conditions, the Contractor shall pursue only such portions of the work as shall not be damaged thereby. No portions of the work whose satisfactory quality or efficiency will be affected by any unfavorable conditions shall be constructed while these conditions remain, unless, by special means or precautions approved by the City, the Contractor shall be able to overcome them. The Contractor shall be granted a time extension of one day for each unfavorable weather day that prevents him or her from placing concrete forms or placing and finishing concrete or asphalt concrete. Such unfavorable weather day is defined as a rain day where precipitation prevents the contractor from performing the work more than four (4) continuous hours within the authorized work period or a temperature day where the ambient temperature is below that specified for the placement of materials associated with the controlling work item for more than four (4) continuous work hours of the authorized work period. 1.16. Saturday, Sunday, Holiday and Night Work. No work shall be done between the hours of 6 p.m. and 7 a.m., nor on Saturdays, Sundays or legal holidays except such work as is necessary for the proper care and protection of work already performed, or except in cases of absolute necessity and in any case only with the permission of the City. It is understood, however, that night work may be established as a regular procedure by the Contractor if he or she first obtains the written permission of the City and that such permission may be revoked at any time by the City if the Contractor fails to maintain at night adequate force and equipment for reasonable prosecution and to justify inspection of the work. .,:c`•-artmsff,\sh-rr form _-on struc-._on _ont.ract 'u't-w­°, 2071 7 1.17. Hours of Labor. Eight (8) hours of labor shall constitute a legal day's work and the Contractor or any subcontractor shall not require or permit more than eight hours of labor in a day from any person employed by him or her in the performance of the work under this contract, unless paying compensation for all hours worked in excess of eight (8) hours per day at not less than 1 1-� times the basic rate of pay. The Contractor shall forfeit to the City, as a penalty, the sum of twenty-five dollars ($25.00) for each workman employed in the execution of the contract by him or her or by any subcontractor, for each calendar day during which such laborer, workman, or mechanic is required or permitted to labor more than eight hours in violation of the provisions of Section 1810 to 1816, inclusive, (Article 3, Chapter 1, Part 7, Division 2) of the Labor Code of the State of California and any acts amendatory thereof. 2. CONTRACT PRICE CITY shall pay the Contractor for performance of this Agreement time and materials with a total not to exceed amount of $77,777.00. 3. PAYMENT OF CONTRACT PRICE 3.1 City shall pay any invoice fo by the City, within thirty (30) days payments under this contract shall be certificates in writing from the City covered by the payments has been done due fn accordance with this contract. 4. INDEMNIFICATION AND INSURANCE. r completed work, and approved of its receipt by City. All made upon the presentation of and shall show that the work and the payments thereof are 4.1 Indemnification. The Contractor shall do all of the work and furnish all labor, materials, tools and appliances, except as otherwise herein expressly stipulated, necessary or proper for performing and completing the work herein required in the manner and within the time herein specified. The mention of any specific duty or liability imposed upon the Contractor shall not be construed as a limitation or restriction of any general liability or duty imposed upon the Contractor by this contract, said reference to any specific duty or liability being made herein merely for the purpose of explanation. S:u\agr;_ms06\snnr�_ farm construction contract ',stoner 5, 2017 E The right of general supervision by the City shall not make the Contractor an agent of the City and the liability of the Contractor for all damages to persons or to public or private property, arising from the Contractor's execution of the work, shall not be lessened because of such general supervision. Until the completion and final acceptance by the City of all the work under and implied by this contract, the work shall be under the Contractor's responsible care and charge. The Contractor shall rebuild, repair, restore and make good all injuries, damages, re - erections and repairs, occasioned or rendered necessary by causes of any nature whatsoever, excepting only acts of God and none other, to all or any portions of the work, except as otherwise stipulated. To the fullest extent permitted by law, Contractor shall indemnify and hold harmless the City and its officers, directors, agents, and employees from and against all claims, damages, losses and expenses including but not limited to attorneys' fees, costs of suit, expert witness fees and expenses and fees and costs of any necessary private investigators arising out of or resulting from the performance of the work, provided that any such claim, damage, loss or expense (1) is attributable to bodily injury, sickness, disease or death, or to injury to or destruction of tangible property, other than the work itself, including the loss of use resulting therefrom and (2) is caused in whole or in part by any act or omission of the Contractor, any subcontractor, or anyone directly or indirectly employed by any of them, or anyone for whose acts any of them may be liable, regardless of whether or not it is caused in part by a party indemnified hereunder, or by the negligence or omission of a party indemnified herein. In any and all claims against the City or any of its agents or employees by any employee of the Contractor, any subcontractor, anyone directly or indirectly employed by any of them, or anyone for whose acts any of them may be liable, the indemnification obligation shall not be limited in any way by any limitation on the amount or type of damages, compensation or benefits payable by or for the Contractor or any subcontractor under workers' or workmen's compensation acts, disability benefit acts, or other employee benefit acts. The obligation to indemnify shall extend to and include acts of the indemnified party which may be negligent or omissions which may cause negligence. S:u\agc t. rt's 06\n},nr t. form c-)nstrur-. `_a: ^infract .,,,t,net S, 2017 1 The City shall have the right to estimate the amount of such damage and to cause the City to pay the same and the amount so paid for such damage shall be deducted from the money due the Contractor under this contract; or the whole or so much of the money due or to become due the Contractor under this contract as may be considered necessary by the City, shall be retained by the City until such suits or claims for damages shall have been settled or otherwise disposed of and satisfactory evidence to that effect furnished to the City. 4.2 Insurance. Contractor shall procure and maintain for the duration of the contract insurance against claims for injuries to persons or damages to property which may arise from or in connection with the performance of the work hereunder by the Contractor, his or her agents, representatives, employees or subcontractors. 4.2.1. Minimum Scope of Insurance Coverage shall be at least as broad as: 1. Insurance Services Office Commercial Liability Coverage (occurrence form CG 0001). 2. Insurance Services Office form number CA 0001 (Ed. 1/87) covering Automobile Liability, code 1 (any auto). 3. Worker's Compensation insurance as required by the State of California and Employer's Liability Insurance. 4.2.2. Minimum Limits of Insurance Contractor shall maintain limits no less than: 1. General Liability: $2,000,000 per occurrence for bodily injury, personal injury, and property damage. If Commercial General Liability Insurance or other form with a general aggregate limit is used, either the general aggregate limit shall apply separately to this project/location or the general aggregate limit shall be twice the required occurrence limit. 2. Automobile Liability: $2,000,000 per accident for bodily injury and property damage. :u\ay-r-_m0 o\snort form cons ruction contract Ur t2ber �, 7017 10 3. Employer's Liability: $1,000,000 per accident for bodily injury and property damage. 4.2.3. Deductibles and Self-insured Retentions Any deductibles or self-insured retentions must be declared to and approved by the City. At the option of the City, either: the insurer shall reduce or eliminate such deductibles or self-insured retentions as respects the City, its officers, officials, employees and volunteers; or the Contractor shall provide a financial guarantee satisfactory to the City guaranteeing payment of losses and related investigations, claim administration and defense expenses. 4.2.4. Other Insurance Provisions The general liability and automobile liability policies are to contain, or be endorsed to contain, the following provisions: 1. The City, its officers, officials, employees, and volunteers are to be covered as insureds with respect to liability arising out of automobiles owned, leased, hired or borrowed by or on behalf of the contractor; and with respect to liability arising out of work or operations performed by or on behalf of the Contractor including materials, parts or equipment furnished in connection with such work or operations. General liability coverage can be provided in the form of an endorsement to the Contractor's insurance, or as a separate owner's policy. 2. For any claims related to this project, the Contractor's insurance coverage shall be primary insurance as respects the City, its officers, officials, employees, volunteers. Any insurance or self-insurance maintained by the City, its officers, officials, employees, or volunteers, shall be excess of the Contractor's insurance and shall not contribute with it. 3. Each insurance policy required by this clause shall be endorsed to state that coverage shall not be canceled by either party, except after thirty (30) days' prior written notice by certified mail, return receipt requested, has been given to the City. : u\acr tmsr)o\nhr rt form -ons ruction cant.rar.t. crop -F. _. ZOS, 11 4.2.5. Acceptability of Insurers Insurance is to be placed with admitted California insurers with an A.M. Best's rating of no less than A - for financial strength, as for long-term credit rating and AMB -1 for short-term credit rating. 4.2.6. Verification of Coverage Contractor shall furnish the City with original certificates and amendatory endorsements effecting coverage required by this clause. The endorsements shall be on forms provided by the City or on other than the City's forms, provided those endorsements or policies conform to the requirements. All certificates and endorsements are to be received within 15 days from written notice of contract award, and the work shall not commence until the certificates and endorsements have been approved by the City. The City reserves the right to require complete certified copies of all required insurance policies, including endorsements effecting the coverage required by these Special Provisions at any time. 4.2.7. Subcontractors Contractor shall include all subcontractors as insureds under its policies or shall furnish separate certificates and endorsements for each subcontractor. All coverages for subcontractors shall be subject to all of the requirements stated herein. 5. TERMINATION. This Agreement may only be terminated by City: 1) for breach of the agreement; 2) because funds are no longer available to pay Contractor for services provided under this Agreement; or 3) City has abandoned and does not wish to complete the project for which Contractor was retained. City shall notify Contractor of any alleged breach of the agreement and of the action required to cure the breach. If Contractor fails to cure the breach within the time specified in the notice, the contract shall be terminated as of that time. If terminated for lack of funds or abandonment of the project, the contract shall terminate on the date notice of termination is given to Contractor. City shall pay the Contractor only for services i. `,agrtms0n\st,nrL form roastructicn r_ontract ';store _, 2017 12 performed and expenses incurred as of the effective termination date, unless terminated because the Contractor has failed to satisfactorily cure a breach after notice in which event City shall: a. retain any amounts earned under the Contract but not yet paid by City; b. take possession of all material and fixtures on the job site; C. have the right to complete the Work and recover from Contractor any increased cost to complete the Work above the amounts that would have been paid to Contractor hereunder, together with any other damages suffered by City as a result of said breach. 6. MODIFICATION OF AGREEMENT. City may, from time to time, request changes in the Work, the time to complete the work or the compensation to be paid for the Work. Such changes must be incorporated in written amendments to this Agreement. To be effective, all such changes as referred to in this section must be agreed upon in writing by both parties to this agreement. 7. ASSIGNMENT. The Contractor shall not assign any interest in this Agreement, and shall not transfer any interest in the same (whether by assignment or novation), without the prior written consent of City. 8. APPLICATION OF LAWS. The parties hereby agree that all applicable Federal, State and local rules, regulations and guidelines not written into this Agreement shall hereby prevail during the period of this Agreement. 9. INDEPENDENT CONTRACTOR. It is the express intention of the parties hereto that Con- tractor is an independent contractor and not an employee, joint venturer, or partner of City for any purpose whatsoever. City shall have no right to, and shall not control the manner or prescribe the .l: t_\aar t`r�n05\r,?,,r'_ form const-ructi^n c�n-ract , 2017 13 method of accomplishing those services contracted to and performed by Contractor under this Agreement, and the general public and all governmental agencies regulating such activity shall be so informed. Those provisions of this Agreement that reserve ultimate authority in City have been inserted solely to achieve compliance with federal and state laws, rules, regulations, and interpretations thereof. No such provisions and no other provisions of this Agreement shall be interpreted or construed as creating or establishing the relationship of employer and employee between Contractor and City. Contractor shall pay all estimated and actual federal and state income and self-employment taxes that are due the state and federal government and shall furnish and pay worker's compensation insurance, unemployment insurance and any other benefits required by law for himself and his employees, if any. Contractor agrees to indemnify and hold City and its officers, agents and employees harmless from and against any claims or demands by federal, state or local government agencies for any such taxes or benefits due but not paid by Contractor, including the legal costs associated with defending against any audit, claim, demand or law suit. Contractor warrants and represents that it is a properly licensed for the work performed under this Agreement with a sub- stantial investment in its business and that it maintains its own offices and staff which it will use in performing under this Agreement. 10. GOVERNING LAW. This Agreement shall be governed by and construed in accordance with the laws of the State of California and any legal action concerning the agreement must be filed and litigated in the proper court in Mendocino County, each party consenting to jurisdiction and venue of California state courts in Mendocino County. 11. SEVERABILITY. If any provision of the Agreement is held by a court of com- petent jurisdiction to be invalid, void, or unenforceable, the remaining provisions shall nevertheless continue in full force and effect without being impaired or invalidated in any way. .S:i'a,rims06\smart form conetnic Y_i on contract 2017 14 12. INTEGRATION. This Agreement, including the exhibits attached hereto, contains the entire agreement among the parties and supersedes all prior and contemporaneous oral and written agreements, understandings, and representations among the parties. No amendments to this Agreement shall be binding unless executed in writing by all of the parties. 13. WAIVER. No waiver of any of the provisions of this Agreement shall be deemed, or shall constitute a waiver of any other provision, nor shall any waiver constitute a continuing waiver. No waiver shall be binding unless executed in writing by the party making the waiver. 14. NOTICES. Whenever notice, payment or other communication is required or permitted under this Agreement, it shall be deemed to have been given when personally delivered, emailed, telefaxed or deposited in the United States mail with proper first class postage affixed thereto and addressed as follows: CONTRACTOR CITY Manley's Boiler, Inc. City of Ukiah 7931 Whitaker Street 300 Seminary Ave. Buena Park, CA 90621 Ukiah, CA. 95482 Email: steve@manleysboiler.com Email: mhorger@cityofukiah.com Service by telefax shall bear a notation of the date and place of transmission and the facsimile telephone number to which transmitted. Either party may change the address to which notices must be sent by providing notice of that change as provided in this paragraph. .::c�a�rtrs05\s?,art form rcnstructi^n contract -nhPr zn1'+ 15 15. PARAGRAPH HEADINGS. -e paragraph headings contained herein are for convenience and reference only and are not intended to define or limit the scope of this agreement. 16. EXECUTION OF AGREEMENT. This Agreement may be executed in duplicate originals, each bearing the original signature of the parties. Alternatively, this Agreement may be executed and delivered by facsimile or other electronic transmission, and in more than one counterpart, each of which shall be deemed an original, and all of which together shall constitute one and the same instrument. When executed using either alternative, the executed agreement shall be deemed an original admissible as evidence in any administrative or judicial proceeding to prove the terms and content of this Agreement. WHEREFORE, the parties have entered this Agreement on the date first written above. lAANL BOILER C. CITY OF UKIAH i 1 I I Ellen J. Manle President / Sagengiac" o City Manager California Contractor's License Number 573413 [Number or N/A] 5:'a\agrtms06\short form construction contract October S, 2017 16 EXHIBIT A City of Ukiah Bids muni he emuilecl, hived or hand ikliverei:4 to the cnntuct infin-matiun lister/ herein, cunt hr rile .V)I! rliecl deadline. or the hid it -ill he reh'cted Submitted by: 'ylanley's Boiler, Inc. (( ompan� lame & Address) 7931 Whitaker Street Buena Park, CA. 90621 REQUEST FOR BID QUO SEMINARY A% I l L 1 KIAH, CALIFOR\I:A 1)5482 P: (707) 463-6233. F: (707) 3 13-362 1 D:VUE: 9/12/2017 RE:Q. N0. E36354 BIDS NILI. RE: 1111'E IVE:D I N711. 1:30 p.m., September 27. 2017 \1 NII UFI 1('F OF rill PRO C t R1 1.11 \l \f.\\ \Gt R 1,1 \n\ \R) \\ 1 i t ry ,.rt KI \11 Iii': Man liorreer E.nlai l: nlhorgerii eiq ofukiah.conl 131 D5 ARE: RIaOt ISI FD Ft)R Ili E: 1`01.1 01,% I I E.%IS: 1LL, BIDS SHALL BE H.O.B. t KIAH, CA. Ot k. rrrl DESCRIPTION t Ntr PRICE LVIE\DE) PRICE I I LIMP Sunt AH equipment. labor and materials to rrmo\e arid replucc mo (? I e\istinL, Rile Boilers 577,i'77.00 $77,777.00 \\ith ('it\ supplicd tiro t_') nc\\ Ritc Boiler, at the Ch\', W wtc\\atcr Trcauncni Plant. as Per attache l specification. NLA\DA"TOR) PRE-BID NIEETI\G 9 a.m.. G1 ednesda}. September 20.'_01 7 Cit\ of L Liah aste\\ater Treanlent Plant 300 Plant Road. Ukiah. Cry 9,3482 Pai ment Te SIGNA 1-1 RF.: DAME: 09/27/2017 LEAD TIME: ARO: 1/A PRI\ I' \AME:: Ellen Iflanlev, Pres ent IPIIONF, 562-427-314-1 L\IAII.: Steve@man evs of er.arn TERMS: I WEAL NREFERENCL Local Vendors shall be given an allowance of five percent (5`yo) up to a maximum allowance of $2.5UU. on any bid for supplies. equipment and/or materials per Ukiah City Code Section 1522 U 4 A i_ocal Vendor is detined as one which 1) conducts business in an Office or other business premises with a physical location in Mendocino County 2) holds a valid business license Issued by Mendocino County or one of the cites in Mendocino County for that business location. and 3) has conducted business In complaince with 1) and 2) for not less than six (b) months prior to requesting the prelerence I he City shall receive satisfactory proof that a business qualities as a local Vendor before it may receive the local preference In the event that there Is a tie bid where one bidder is local the other is not and the bid is equal in price and quality, the award shall go to the Local Vendor 2 Right is reserved to refect any and all bids 3 Right Is reserved to accept separate items unless specifically denied by bidder 4 Rights reserved to refect a bid from any bidder who has previously tailed to perform adequately for the City of Ukiah 5 In CASE OF UEFAUL I the City of Ukiah may procure the items quoted on from other sources and hold the original bidder liable for any increased costs b I he price. terms, delivery point. and delivery date may Individually or collectively be the basis of the awarding of the bid 7 In submitting the bid. bidder agrees that the bid Shall remain open and may not be revoked or withdrawn for bU days from the Did due date unless a different time period Is specified In RF8. 8. Bidder agrees to perform according to Its bid if the City's acceptances communicated to the bidder within the time specified in number 7 above REQUEST FOR BID City of Ukiah SPECIFICATION E36354 BOILER REMOVAL AND INSTALLATION AT THE WASTEWATER TREATMENT PLANT September 12, 2017 Mandatory Pre -Bid Meeting 9 a.m., Wednesday, September 20, 2017 at the Wastewater Treatment Plant 300 Plant Road Ukiah, California 95482 Bids are Due: 1:30 p.m., September 27, 2017 Purpose/Background The City of Ukiah is seeking a qualified contractor to provide bids for all equipment, labor and materials to remove and replace two (2) existing Rite Boilers with City supplied two (2) new Rite Boilers at the City's Wastewater Treatment Plant. Contact Person The City has designated Mary Horger, Procurement Manager as the contact person for questions related to this Request for Bid. Questions are to be submitted in writing, and can be done so by fax at (707) 313-3621, or by e-mail at mhorger'u cityofukiah.com. Mandatory Pre -Bid Meeting A mandatory pre-bid meeting will be held 9 a.m., Wednesday, Septermber 20, 2017 at the project site located at the Wastewater Treatment Plant, 300 Plant Road, Ukiah, California to fully acquaint interested Contractors with local conditions, construction and labor required so that he or she may fully understand the facilities, difficulties and restrictions attending the execution oft lie work under the Contract. Failure to attend this meeting will be just cause for the bid to be rejected as non-responsive. Contractors shall thoroughly examine and be familiar with the specification. The failure of any contractor to receive or examine any form, instrument, addendum. or other document, or to visit the site and acquaint himself with conditions there existing, shall in no way relieve the contractor from any obligation with respect to his or her bid or to the contract. The drawings for the work show conditions as they are supposed or believed by the Engineer to exist; but, it is neither intended nor shall it be inferred that the conditions as shown thereon constitute a representation by the Engineer, the City or its officers that such conditions are actually existent, nor shall the City, the Engineer or any of their officers or representatives be liable for any loss sustained by the Contractor as a result of a variance between the conditions shown on the drawings and the conditions actually revealed during the progress of the work or otherwise. Oral statements or instructions made during this mandatory pre-bid meeting will not constitute an amendment to this solicitation. The City will determine the appropriate action necessary, if any, and may issue a written amendment to the bid request. The contractor shall investigate to his or her satisfaction the conditions to be encountered, the character, quality and quantities of work to be performed and materials to be furnished and the requirements of the Plans, Special Provisions, Standard Specifications, Standard Plans, and Contract Documents. The submission of a bid shall be considered conclusive evidence that the contractor has made such examination and has accepted the project workplace as a safe workplace to perform the work of the Contract. Scope of Work The scope of work consists of all labor, equipment, materials, and incidentals of any kind (with the exception of City supplied materials) to remove the two existing boilers, and install, and start-up two new boilers located at the City of Ukiah Wastewater Treatment Plant, located at 300 Plant Road, Ukiah, California. The boilers to be replaced were manufactured by Rite Boiler, Part Number A180WGG, serial numbers 24793 and 24794, and were installed at the Plant in 1995. The boilers are used to provide heat for the two digesters. It will be the responsibility of the contractor to remove and dispose of the existing boilers, burners, and any other items being replaced during the course of the work. The two (2) new replacement boilers have already been purchased and received by the City, and are awaiting installation at the Wastewater Treatment Plant. The new boilers purchased are supplied with dual fuel burners, with sel)(wate digester- and nano al gas gas !h•ains, and have the following description: Rite Indoor Model A 180WGG, 43 HP, 125 PSI Hot Water Boiler with two (2) probe low water cut-offs and relief valve set at 125 psi. With Powerflame CR2-GG-15 6-14•' water column supply natural gas pressure and 8.5" mininium digester gas pressure. With Y horse power blower motor, 460/60/3 motor with stepdown transformer for controls, CSD -1, Cal Code, full modulation tiring. The probe low water cut-off will be at the back of the boiler so they will not interfere with the supply water pipe. With ceramic fiber combustion chamber with firebox access door, hinged head plates, draft gauge and 18" barometric damper shipped loose. Digester gas train is standard aluminum body and brass valves, the pipe nipples and fittings are Schedule 40, 150 PSI Rated, 316 Stainless Steel. The boilers include manual push-pull soot scrapers installed to help keep the heat exchanger fire side tree of siloxaine and other deposits. includes manufacturer installed inches of water column gas pressure gauges before and after the natural gas main pressure regulator on each boiler, as well as the same make gauges on the digester train. The gauges include test valves so you can turn off the pressure to the gauges when not testing. Boilers have the same vent and water connection sizes and locations as the original 1995 boilers. The boilers have ceramic fiber combustion chambers in lieu of refractory combustion chambers. One boiler is supplied with standard right hand gas train and controls, the other with lett had gas train and controls. Firebox access doors have been placed on the side opposite the gas train and controls so they are not blocked off by the fuel piping. The installation of' the Rite Boilers is to be in accordance with the Rite Boilers instruction Manual for Indoor & Outdoor Rite Power Burner Fired Boilers, provided for as Attachment A. The start-up of the Powerflame burners is to be performed in accordance with the Power Flame Installation & Operation C Manual, provided for as Attachment B. The following documents have been provided for as reference to assist in the preparation of your bid: Attachment C - WWTP Facility Drawings — 3 Drawings Attachment D — Approved Rite Boiler Drawings — 3 Pages The work site wil I be kept clean and tidy during the course of the work. Contractor shall be solely responsible for any and all damages extending from the work described herein. Contractor shall restore all damaged property to its original condition at his/her own expense. All work will be provided for in accordance with the City's standard short form construction contract, provided for as Attachment E. Price The bid price for this work will be submitted per the bid sheet provided, and shall be lump sum, and consist of all labor. materials, equipment, applicable fees, including tax and freight necessary to perform the work as described in this bid specification. Terms Payment will be made 30 calendar days after final date of acceptance of work. The City reserves the right to award to the lowest, responsible bidder. The City also reserves the right to waive any irregularities and technicalities and request rebids should it be deemed in its best interests to do so. The price and terms may individually or collectively be the basis of awarding of the bid. The City also reserves the right to reject any and all bids. Warranty Unless otherwise indicated, the Contractor must provide a l -year workmanship warranty from the date of final acceptance. The Contractor shall replace promptly and at his own expense any materials and/or workmanship which fail during this warranty period. Indemnify and Hold Harmless Contractor agrees to accept all responsibility for loss or damage to ani person or entity, and to defend, indemnity, hold harmless and release the City, its officers, agents and employees, from and against any and all actions, claims, damages, disabilities, or costs of litigation that may be asserted by any person or entity, arising out of or in connection with the negl igent or will ful misconduct in the performance by contractor hereunder, whether or not there is concurrent, passive or active negligence on the part of the City, but excluding liability due to the sole active negligence or willful misconduct of the City. This indemnification obligation is not limited in any way by any limitation on the amount or type of damages or compensation payable to or for Contractor or its agents under Workmen's Compensation acts, disability benefits acts or other employee's benefits acts. Contractor shall be liable to the City for any loss or damage to City property arising from or in connection with Contractor performance hereunder. Time of Comnletion The Contractor �N ill complete the work within 30 calendar days from receipt of formal Notice to Proceed. Other Requirements The selected contractor will need to comply with the following requirements: 1. Insurance - Contractor's attention is directed to the insurance requirements — see Attachment F. Contractors shall finish to the City, upon award of contract, certificates of insurance covering full liability under Worker's Compensation laws of the State of California, Comprehensive General Liability and Business Auto Insurance with policy limits of not less than $1,000,000 naming the City as an additional insured party. It is highly recommended that contractors confer with their respective insurance carriers or brokers to determine in advance of bid submission the availability of insurance certificates and endorsements as prescribed and provided herein. If an apparent awarded contractor fails to comply with the insurance requirements, that contractor may be disqualified from award of the contract. If you have questions regarding the City's requirements, please contact the City's Risk Manager at 707-463-6287. 2. Compliance with State of California and OSHA - All materials, parts and equipment furnished pursuant to these specifications shall be in compliance with the laws and regulations of the State of California and OSHA. The contractor shall, if requested by the City, supply certification and evidence of such compliance. 3. Legal Requirements and Permits: The contractor agrees to fully comply with all local, City, State and Federal laws, regulations and ordinances governing performance of contractual services required, and it will be the responsibility of the contractor to obtain any and all necessary licenses, permits or clearances, including the actual cost of licenses. 4. License Requirements - Contractor must possess a current State of California Contractor's license and a City of Ukiah business license. (For information business license, please contact Kathy Norris. City of Ukiah Finance Department at 707-463-6202.) a. The Contractor shall possess a valid State of California Class C-4 Boiler. Hot Water Heating and Steam Fitting- Contractor license. Contractor shall provide proof of possession ofthe proper licenses and certificates of registration necessary to perform the work. Employees actually performing the tasks shall provide proof of proper certificates of registration for same. b. The Contractor shall keep in force a City of Ukiah business license for the extent of the project. c. Where subcontractors/jobbers are used, Contractor shall provide the City with proof of proper licenses, certificates and proof of insurance for work performed. Notice to Contractors - Contractor Registration and Prevailing Wages -No contractor orsubcontractor Inco, be listed on a bid.for a public works project (submitted on or after March 1, 2015) unless registered irith the Dc/R11-1111071 of7ndustrial Relationslrursuant to Labor Code section 1725.5 [with limited exceptions from this reyttireurcut Jor bid proposes only ttrulerLcrhor Codc .section 1771.1(a)J. No c-otttrctctor• orsttbcorttr actor• micro• be an,arded a contract for public work on a public works project (cnrarded on or after April 1, 2014) unless registered with the Delmi-tment of Industrial Relations pursuant to Labor Code section 1725.5. The prints contructor.shall be resporrsible,for•postingjob site notices as prescribed by regulation. This project is subject to congViancc monitoring and enforcement h}- the Deperrttncnt of Industrial Relations. Each laborer or mechanic of Contractor or any subcontractor engaged in work on the project under this contract shall be paid, pursuant to provisions of Section 1770, including amendments thereof, of the Labor Code of tile State of California, the Director of the Department of Industrial Relations. State of California, has ascertained the general prevailing rate of wages for straight time, overtime Saturdays, Sundays and Holidays including employer payment for health and welfare, vacation, pension and similar purposes, copies of the General Prevailing Wage Determination (applicable to the work), for the locality in which the work is to be done can be reviewed at Website: %% ww .dir.ca.�-,ov/dlsr/pis d/northern.html . The Labor Commissioner through the Division ofLabor Standards Enfirrcentent (DLSE) mcrt• at am time require contractor and subcontractors to fiu•rrish electronic certified pa }roll records directlt, to DLSE. Conimcw-ing rn,ith contracts awarded on or after April 1, 2015, all contractors and subcontractors must fttrni.sh electronic certified l?aYroll records directly to the DLSE. Bidder Qualifications They City will satisfy itself that the potential contractors are reputable firms with a proven track record. Contractors are requested to provide the information requested under Work Performance History Capability. References shall include the contact name and phone number. Bid Submission Deadline Bids can be submitted in hardcopy, fax, or by email. Bids are due on or before 1:30 p.m, Wednesday, September 27, 2017 to: City of Ukiah Purchasing Department Attn: Mary Horger 411 West Clay Street Phone: (707) 463-6233, Fax: (707) 313-3621 Email: mhor,-,er u,citvofukiah.com It �Nill be the sole responsibility of the contractors to have their bids delivered to the City before the closing hour and date. Late bids will not be considered and will be returned unopened to the sender. The City will not be responsible for any cost incurred by the Contractor in preparation of their bid. INDEMNIFY ANI) HOLD H.�IZ11LIa� :�GItEE�1F:\T t ontractol- ililrce:� Its idl lit', IU:" Ill» Ot dillllai?: It, -illA hcI'>U11 UI- and to klelQ11d. mclemnity. hold harnllC,. and rcicase the ( itv, its off-Icets. a_Cnt,'and enlplovice,. fionl and against iim and all i coons. claims. dama_es, disabilities. or Costs of, liti_ation that Fila\ he assCrted h\ all person or entity. ari inL_ out of ur in Connection \\lilt the ncsli rnt ur \\ ilit'ul nlisCondttct in the pertirrmancc b\ contractor. herCLIlider. \\hetheror not there k Concurrent, pa>si\C or acti\ C ne_IigCIlCe on the part ot'thc Cit\, but c\Cludin_ hahilit\ dltc to the sole aCti\C negli_cnCC or \\illt'ul n1i,C011dtlCt ot'the ('it,. I his indenlrlification ohli_2ation is not limited in an\ \\a\ h\ am limitation on the 011101.1111 til- 1\ pC of dWlla_'c, ill' Colnlpetl alion Ila\ able to of- flitContra(101' ill- ita iil-Icnts lil)llct' Workmen's (onipcii atiUtl act>, disuhillt\ hellefits acts or other Cmplo\ce s acts. ConUaCtol ,hall he liable to the Cit\ t -or an\ loss or diuuage to Cit\ property arising from or ill Connection \\ ith Contractot pCri0n n1.u1CC hCreundcr. I-hC undcrs11_111Cd tckrlo\%lcd_es that this doCwrlerlt, to_,ethcr\\ ith OIL: rc;ultillL htlrrha"'C order issued h\ the: Cit\, the CXcrutCd Short F01111 Con u'uction Contract. the in,tuanCe rclluircmcnt. for Contractors. and the Contractor Statement Rccardin_ iruurancc co\crage Comprise a \\rittcn agreement hCMecn the Contractor and the Uit\ hilidin_ on hoth pitrtic, File undersi_ned declarCs thc\ are litnliliar with the item: specified and ha\c carefulk read the RIB ,h,�CiliCation rC�luil'CIII Crlts, cIIQAcd illi of -the ti__tu-cs stated on the spccification, and aceCpts full responsihiIit\ I'm an\ Crror or omission in the preparation of -this hid. Ffils hid is submitted h\. )check one► hldi\ Kival ( )\\flet' - — Partnership l Corporation Other I cLml \anm oh Bidder .Manley's boiler, Inc. AddrC'ss oh Bidder `a I Whitaker Street, buena Park, CA. 90(,21 ,l -ay IU:- 33-02O3801 Phone Nunlhcr D02-427-3[44 E=ar \unlhcr -502-.124-8626 California State Contractor's License #: , 111' !:.\piration Date: 07'31/2010 Department of Industrial Relation Public Works Reoistration #: 1000002417 By : --� - ' ' '�v - -- — --- -- I),tte 09/2712017 signature Print or T\ pe Name: 1-Ilen I Manley President . _— 1-itlC WORK PERFORMANCE HISTORY AND CAPABILITY: Contractor is requested to provide the name, locations and a narrative statement on the work performed. WORK PERFORMED 1. COMPANY NAME: Nissin Foods Boiler pipe welding and valve CONTACT: Jorge Andrade ADDRESS: 2001 W. Rosecrans Ave. Gardena, CA. 90249 PHONE 310-327-8478 2. COMPANY NAME: County of San Bernardino CONTACT Marty Marshall ADDRESS 385 N. Arrowhead _ San Bernardino, CA. 92415 PHONE: 909-208-8490 3. COMPANY NAME: Ventura Youth Correctional Facility CONTACT: Roy Calzada ADDRESS -31 00 Wright Road Camarillo, CA. 93010 PHONE: 805-485-8071 Ext. 3218 4. COMPANY NAME: Raytheon -El Segundo CONTACT: John Pena ADDRESS: 2000 E. El Segundo Blvd. El Segundo, CA. 90245 PHONE: 310-261-8434 6 replacements. On-going boiler maintenance, service, testing, and repair of 64 various boilers throughout the County of San Bernardino On-going boiler maintenance, service, testing, and repair of on-site boilers. Replaced two 530 gallon water storage heaters in 2014. On-going boiler maintenance, service, testing, and repair of all on-site boilers. MANLEY'S BOILER, INC. VARIOUS PROJECT EXPERIENCE VARIOUS PROJECTS IN PROGRESS: Description Dollar Value Owners Name Rep Name/Email Owner Address Boiler maintenance, service, inspection, On-going 916-255-6187 9838 Old Placerville Road calibration, and repair for 21 prisons in California Department of Maria Crews Ste B-2 California $ 3,286,000.00 Corrections and Rehab. maria.crews@cdcr.ca.gov Sacramento, CA. 95827 On-going maintenance, service and repair of all On-going John Pena 2000 E. EI Segundo Blvd. on-site boilers. as per contract Raytheon -EI Segundo john.o.pena@raytheon.com EI Segundo, CA. 90245 On-going maintenance, service and repair of 64 UTC Aerospace Larry Vega 8200 Arlington Avenue various boilers throughout the County of San - - - Marty Marshall 385 N. Arrowhead Bernardino. $_237,360.00 County of San Bernardino mmarshall@fm.sbcounty.gov San Bernardino, CA. 92415 Service, maintenance, repair, replace parts for $165,000.00 3/1/2017 200193752 Fulton Vantage, Kawanee, and Peerless boilers Eric Oates 707 West Acequia Avenue as needed. $ 45,600.00 City of Visalia ericoates@ci.visalia.ca.us Visalia, CA. 93291 Service, maintenance, repair, replace parts for $ 50,170.52 Nissin Foods Mike Ponce 3291 Loma Vista Rd. Ajax and Raypak boilers as needed. $ 70,348.00 Ventura County Medical mike. ponce@ventura.org Ventura, CA. 93003 VARIOUS CLOSED PROJECTS FROM THE PREVIOUS SEVEN YEARS: 2016/2017 Scheduled Completion Date Contract # 01/01/2017 12/31/2018 C5606805 01/01/2017 12/31/2019 170591 14-15-88 6/30/2017 131414 Contract Date of Description Percent Phone Complete 916-255-5704 On-going 916-255-6187 contract Remove existing Ajax steam boiler. Supply and On-going 310-261-8434 contract $ 64,000.00 On-going 909-208-8490 contract install new Hi -Delta Raypak boiler. On-going 559-713-4469 contract 213-487-4444 On-going 805-204-8005 contract Scheduled Completion Date Contract # 01/01/2017 12/31/2018 C5606805 01/01/2017 12/31/2019 170591 14-15-88 6/30/2017 131414 Contract Date of Description Dollar Value Owner's Name Rep Name Owner Address Phone Amount Completion Contract # Remove existing Ajax steam boiler. Supply and david.sheil@ash.dsh.ca.gov Washington Moranzonl 3250 Wilshire Blvd. $ 64,000.00 9/1/2016 15-10111 install new Hi -Delta Raypak boiler. $ 45,423.00 One Park Plaza washington@reaItechla.com Los Angeles, CA. 90010 213-487-4444 _$_45,423.00 4/28/2017 17-0123C-1 Supply and install two (2) two -million btu UTC Aerospace Larry Vega 8200 Arlington Avenue - - - - Charles Chaffee Raypak boilers. $ 165,000.00 Systems/ILL larry.vega@am.jll.com Riverside, CA. 92503 951-232-1439 $165,000.00 3/1/2017 200193752 Jorge Andrade 2001 W. Rosecrans Avenue Burbank, CA. 91505 818-331-5834 $ 10,000.00 Boiler pipe welding and valve replacements. $ 50,170.52 Nissin Foods ajorge@nissinfoods.com Gardena, CA. 90249 310-327-8478 $ 50,170.52 12/31/2016 VARIOUS Weld repair on Boiler #4 for boiler feed piping David Shell 10333 EI Camino Real modifications. $ 64,000.00 Atascadero State Hospital david.sheil@ash.dsh.ca.gov Atascadero, CA. 93423 805-468-2249 $ 64,000.00 9/1/2016 15-10111 David Sheil 10333 EI Camino Real Completely rebuild the refractory for boiler #3. $ 90,532.87 Atascadero State Hospital david.sheil@ash.dsh.ca.gov Atascadero, CA. 93423 805-468-2249 $ 90,532.87 8/1/2016 15-10128-000 - - - - Charles Chaffee Remove old tubes and purchase and install new cchaffee@burbankmarriott.co 2500 N. Hollywood Way tube bundle for Raypak boiler. $ 10,000.00— Marriott Burbank Burbank, CA. 91505 818-331-5834 $ 10,000.00 6/1/2016 31688960492 - — — _m Jackeline Bonilla Remove old tubes and purchase and install new jackeline.bonilla@pihhealth.or 11500 Brookshire Avenue tube bundle for Patterson Kelly Boiler. $ 20,000.00 Downey Regional Hospital g Downey, CA. 90241 562-904-5000 $ 17,777.68 2/19/2016 D11929 Replace existing underground double containment steam and condensate lines at California State Prison - Mac Mimaki 44750 60th Street W. 661-729-2000 06/2016 - California State Prison, Los Angeles County $_ 207,000.00_ Lancaster mac.mimaki@c_dcr.ca.g_ov CA. 93536 Ext. 7307 $207,000.00 10/2016 C5606377 US Dept. o the _Lancaster, PO Box 10046 Demo existing boiler and purchase and install Army/Infinite Energy Jim Howie TR11109 South Loop Rd. 07/2016 - three (3) two -million btu boilers. $ 275,159.34 Construction - Daggett jhowie@iec8a.com Fort Irwin, CA. 92310 760-386-0400 $275,159.34 09/2016 W91248 -11-D-0001 Replace two Lochinvar boilers on roof -top at The Kimberly McDowel 5000 Clark Ave., Lakewood, CA. Centre at Sycamore Plaza. $ 169,995.00 City of Lakewood kmcdowel@lakewoodcity.org 90712 562-866-9771 $169,995.00 6/13/2016 2015-5 Replace one heat exchanger and 1000 gallon Danny Miller 590 S. Burlingame Ave., Los 310-451-8011 storage tank. $ 56,287.98 Brentwood Country Club facilitymgr@brentwoodcc.net Angeles, CA. 90049 Ext. 249 $ 56,287.98 6/1/2016 San Diego Convention Debbie Noble 111 W. Harbor Dr., San Diego, Rebuild two roof -top K300 boilers w/ re -tubes. $ 110,705.00 Center debbie.noble@visitsandiego.com CA. 92101 619-525-5383 $110,705.90 1/27/2016 E:\CeanneDocs\manleys work in progress prev yrs rev 2015 Description Dollar Value Owner's Name Rep Name Owner Address Phone Contract Amount Date of Completion Contract # Demo four existing boilers and install customer Santa Ana Unified School Sonny Carrillo 1401 S. Grand Ave., Santa Ana, Owner Address Phone Amount supplied boilers. $ 32,624.00 District isagani.carrillo@sausd.us CA. 92705 714-936-0570 $ 32,624.00 12/1/2015 Provide all labor & materials as necessary to Replace two 530 gallon water storage heaters. $ 165,991.00 Ventura Youth Correctional roy.calzada@cdcr.ca.gov 93010 remove & demo old boiler; purchase & install $165,991.00 Pasadena Community Sandra Collins 1570 E. Colorado Blvd., Pasadena Community Sandra Collins new boiler at building C. $ 139,900.00 College sdcollins@pasadena.edu Pasadena, CA. 91106 626-585-7367 $139,900.00 12/29/2015 sdcollins@pasadena.edu Pasadena, CA. 91106 Los Angeles County Nick Wiehardt 24501 S. Figueroa, Carson, CA. 310-830-2400 Labor and materials to replace the underground Retrofit three 500 hp burners $ 399,998.00 Sanitation District nwiehardt@lacsd.org 90745 Ext. 5254 $399,998.00 2/1/2015 Install heat exchanger and rental boiler with California Institute for California Institute for John Dickson 16756 Chino -corona Rd., Corona, 909-606-4957 two storage tanks. $ 135,400.00 Women john.dickson@cdcr.ca.gov CA. 92878 Ext. 7343 $135,400.00 1/31/2015 2014 E:\CeanneDocs\manleys work in progress prev yrs rev Contract Date of Description Dollar Value Owner's Name Rep Name Owner Address Phone Amount Completion Contract # Roy Calzada 3100 Wright Road, Camarillo, CA. 805-485-8071 Replace two 530 gallon water storage heaters. $ 165,991.00 Ventura Youth Correctional roy.calzada@cdcr.ca.gov 93010 Ext. 3218 $165,991.00 4/11/2014 Pasadena Community Sandra Collins 1570 E. Colorado Blvd., Replace boiler in building D $ 32,559.00 College sdcollins@pasadena.edu Pasadena, CA. 91106 626-585-7367 $ 32,559.00 2/18/2014 Labor and materials to replace the underground steam & condensate lines; and install heat California Institute for John Dickson 16756 Chino -corona Rd., Corona, 909-606-4957 exchanger and rental boiler with two tanks. $ 112,002.00 Women john.dickson@cdcr.ca.gov CA. 92878 Ext. 7343 $112,002.00 8/29/2014 Gary King 8039 Beach Blvd., Buena Park, Remove and install new Rite boiler. $ 109,896.00 Knott's Berry Farm gary.king@knotts.com CA. 90620 714-220-5295 $109,896.00 4/25/2014 2013 Contract Date of Description Dollar Value Owner's Name Rep Name Owner Address Phone Amount Completion Contract # Los Angeles Unified School Barrett Elementary School District of Los Angeles Dave Perez 419 W. 98th Street Replace and install hot water and steam boilers. $ 60,123.18 County david.perez@lausd.net Los Angeles, CA. 90045 714-328-7997 $ 60,123.18 6/28/2013 Retube D -style Cleaver -Brooks, install Coen Rob Swenson 2025 E. Harbor Dr. burner, overhaul economizer. $ 957,400.00 CP Kelco rob.swenson@cpkelco.com San Diego, CA. 92113 619-595-5038 $957,400.00 8/13/2013 2012 Contract Date of Description Dollar Value Owner's Name Rep Name Owner Address Phone Amount Completion Contract # Jorge Andrade 2001 W. Rosecrans Ave. Install six boilers and all equipment. $ 112,800.00 Nissin Foods ajorge@nissinfoods.com Gardena, CA. 90249 310-327-8478 $112,800.00 8/1/2012 2011 Contract Date of Description Dollar Value Owner's Name Rep Name Owner Address Phone Amount Completion Contract # Mark Stephenson mark.stephenson@ 9655 Granite Ridge Drive #100 Burner & boiler install $ 193,861.00 Bumble Bee bumblebee.com San Diego, CA. 92123 562-204-4915 $193,861.00 9/1/2011 2010 Contract Date of Description Dollar Value Owner's Name Rep Name Owner Address Phone Amount Completion Contract # Ray Carpenter rcarpenter@ 35435 Pala Del Norte Rd. Boiler repairs $ 335,458.00 Orange Grove Energy orangegroveenergy.com Pala, CA. 92059 760-615-2010 $335,458.00 12/27/2010 E:\CeanneDocs\manleys work in progress prev yrs rev 04, of Ukiah Boiler Removal & Installation at the N'WTP - RFB SUBCONTRACTORS: The bidder must submit a list of subcontractors whom he proposes to employ on the work with proper firm name and business address of each. Subcontractor's Name None Work to be performed Address City/State/Zip Phone Number Fax Number License Number/Type/Expiration Date DIR PW Registration # Subcontractors Name Work to be performed Address City/State/Zip Phone Number Fax Number License Number/Type/Expiration Date DIR PW Registration # Subcontractors Name Work to be performed Address City/State/Zip Phone Number Fax Number License Number/Type/Expiration Date 7 DIR PW Registration # Cit l• of I 'Airrh Boiler Removal & Installation at the !{'JVTP - RFB RIDI)FR(()\IR\(-I-OR SI \[1-.111:\I RFG \RUIVi I\tit R \\('I ('(A I It Vel Clo he submitted %%ith Kid) li DDI-RIIFRFRI(FRTIFIESthmhe,liM,wiccccd,mduWamanddicinsuranceeu�cra,ercyuirement.specitiecl ut the Rcyuest tiff Fiid lor. IIOTI-'R MAI(A \l A\I) I\S I \I I \ IlU\ \ I I IIF \\ \S I I \\ \ I I t( I lu \ l \IF\ I IT \\ I Should m I ht ;+warded the contract. sic I cutin that "e I can nuet the spec hied requirement; for in,urunce. inelu3in, ntNurancc ",\era�c of the subcontractors. and agree to name; the ( its of t kiah as kdtlitional Insured for the %%ork specified. \nd cce I cc ill eompl� Stith the pt -c,\ i;ion> of Sect I,nj ;?tln of the I emploser to he inavol against hahilitt Or ttorkc•r', onnpensmion or W undertake sclt-tnsit rance in accordance \t ith the Pro\ iIiuttS ul that LOdC. hCfLne 1:0111ntcncin, the performance of the \\cork �peiihed. Manlcy'� 1;mlcr, Inc. Plc.uc Print i Pcrurn. I irm- or ('orp,mationl Signature of ko�t nivcd Itrhresentatite Ellen J :\tanlr�, Pl-eSidCllt Plea,c I'rint (\anrr N. l itis Irl ,luthorved Rchrr,cntati�ci 09i29/201 362-427-31.1.4 Date Phone A'umhci 8 PURCHASING DEPARTMENT 411 West Clay Street, Ukiah CA 95482 lip �� f Ukiah (707)463-6233 J mhorger(a,cityofukiah.com SPEC. E36354 — BOILER REMOVAL AND INSTALLATION AT THE WASTEWATER TREATMENT PLANT Addendum No. 1 September 26, 2017 The following is Addendum No. 1 to SPEC. NO. E36354 Boiler Removal and Installation at the Wastewater Treatment Plant. IF YOU SUBMIT A PROPOSAL, ACKNOWLEDGMENT OF THIS ADDENDUM MUST BE SHOWN ON THIS ADDENDUM. IN ADDITION, THIS SIGNED ACKNOWLEDGMENT MUST BE SUBMITTED WITH YOUR PROPOSAL, OR IT MAY BE DEEMED AS NON-RESPONSIVE, This Addendum is hereby made part of the Contract Documents to the same extent as though it were originally included therein. I. BID DEADLINE HAS CHANGED: The new deadline to submit bids is 1:30 p.m., Friday, September 29, 2017. II Attachment B — Power Flame Installation & Operation C Manual. The incorrect document was issued with original bid request. It is replaced with the manual attached. III The following is added to the Scope of Work: A Existing Gas Supply Lines: 1. Contractor to re -pipe the existing gas supply lines to remove from location between the boilers, to keep clear and open for future boiler maintenance, and to accommodate the new location of the replacement boiler valve trains. Please see Exhibit 1 for proposed relocation of the lines. 2. All valve, gauges and piping are to be replaced with new. 3. Add additional ball valve to inches -in -water gauge, shown in Exhibit 2. 4. Repaint the gas supply lines to "Industrial Yellow" to follow ANSI guidelines. B. Existing Water Supply Lines: 1. Outlet: Add Emergency Connection Outlet as shown on Exhibit 1, 3 and 4. Replace existing tee with cross fitting. This will need to be done prior to the replacement of the boilers, to minimize down time of digester operations during the remainder of the project, and to also enable future maintenance work on boilers as needed once project is complete. Add additional temperature gauge. 2. Inlet: Add Emergency Connection Inlet as shown on Exhibit 1 and S. Replace existing 90 degree elbow on inlet water with a tee, to accommodate the additional emergency connection inlet as shown on Exhibit 1. This will need to be done prior to the replacement of the boilers, to minimize down time of digester operations during the remainder of the project, and to also enable future maintenance work on boilers as needed once project is complete. 3. Exhaust Drain Plumbing: Current location shown in Exhibit 6. To be relocated from the middle of the boilers, to the outside of the boilers, to open up space between the boilers for maintenance. Page 1 of 2 4 Replace all existing butterfly valves with new, and add as needed per Exhibit 1. a. For informational purposes, existing valves are a (DeZurik i#9240536). This model has been replaced by the manufacturer. See Exhibit 7 for manufacturer drawing. Use this valve, or equal. 5. All plumbing, inlet and outlet, to be replaced, including all insulation wrap. 6 Replace all temperature gauges. All other `erms and conditions remain in full force and effect. Mary V. Norger Procurement Manarzer ACKNOWLEDGMENT I hereby acknowledge that I have received this Addendum No. i and have reviewed and considered it before submitting my proposal. Signed: gate: Hen J Mani President Company Name MMIlt-v's Boiler, InC. Page 2 of'-) EXHIBIT 1 > nl �' rrlJ 1 3� > T �> �3 0 O d C 2 O w �3 C � 0 O d C 2 EXHIBIT 2 • J\ fi F C� t 304, rt 7. 01V 1 k� 1 4 19 1 EXHIBIT 3 EXHIBIT 4 El \ » »� � � � � - ► i 0 !� � EXHIBIT 5 EXHIBIT e rm-i � y: • � :_<� d « « . :. a:� «: � � � � .� � f� ƒ\ ` > �} � � w � �y\ \ \ / rm-i � y: • � :_<� d « « . :. a:� «: � � � � .� � EXHIBIT 7 VALVE SIZEDIMENSIONS HORIZONTAL 1 1 2'32 59, VERTICAL IN MM IN MM A B C D I E j F G 2 50 1.67 6.50 2.36 5.53 .57 1 4 5/8-11 INCU 4'75 [42 1651 [601 [140] [141 11211 1.79 7.28 2.76 6.02 5.50 2-1/2 65 [45] 1651 [701 [1531 .57 [14] 1 4 518-11 UNC 11401 1.79 7.58 3.15 6.20 6.00 3 80 [451 [1931 1801 [1571 .57 [141 4 5/8-11 UNC 11521 2.02 9.00 3.54 6.93 7.50 4 100 [511 [2291 [90] [1761 .57 [141 8 5/8-11 UNC [1911 5 1258 314-10 UNC ' 1551 [254] [1 12] [1911 [141 [2161 2.18 11.22 5.04 7.97 9.50 6 150 [551 [2851 [1281 [202 .57 [14 8 X4-10 UNC [2411 DOTTED LINES INDICATE OPTIONAL LOCKING DEVICE PROVIDED BY CUSTOMER (SEF DF TAII 'A" R NOT 5)- -T � �a 10.24 [2601 E MOUNTING HOLES FORf PIPELINE MOUNTING"F" OTY AND SIZE OFTAPPED HOLES ON A "G" DIA BC (ANSI STANDARD,- �„B„-1/1' � C NOTE: 1. DRAWING SHOWS MOUNTING HOLES FOR ANSI CLASS 125150 FLANGES. 2. FOR FLANGES OTHER THAN ANSI STANDARD SEE D10478 FOR DIMENSIONS. 3. DO NUT USE GASKETS BETWEEN VALVE AND MATING FLANGES. 4. FLOW MAY BE IN EITHER DIRECTION 5. LEVER WILL USE A.2817I DIA X 2,00[511 VERTICAL X.81(211 HORIZONTAL ADJUSTABLE SHACK �E PADLOCK, DIVENSIONS ARE IN THE LOCKED POSITION. NOTICE HIS DRAWING DOES NCT SHOW' ACTUATOR ACCESSORIES. IF ACCESSORIES ARE REQUIRED. REFER TOTHE APPROPRIATE ACCESSORY INSTALLATION DRAWING FOR DIMENSIONS AND OTHER RELATEC INFORA^ATION. �u A ACTUATOR MOUNTING POSITIONS f��\\ f \'� LJ D eZ U R I I ` BOS-CL BUTTERFLY VALVES SIZE 2 - 6 LUGGED \ \ \/ L710 POSITION LEVER ACTUATOR STANDARD POSITION 180' POSITION SHOWN ON THIS DRAWING _ Sortell, [VIN USIA 66377 WC�_ - rrrcrr SN o CEG A60403 u m a vVrvv BZUiIk.c 0171 Cl sn `' Iz 1e,l� HORIZONTAL 1 1 2'32 59, VERTICAL DETAIL "A" LOCKING DEVICE (PROVIDED BY CUSTOMER SEE NOTE 5) �u A ACTUATOR MOUNTING POSITIONS f��\\ f \'� LJ D eZ U R I I ` BOS-CL BUTTERFLY VALVES SIZE 2 - 6 LUGGED \ \ \/ L710 POSITION LEVER ACTUATOR STANDARD POSITION 180' POSITION SHOWN ON THIS DRAWING _ Sortell, [VIN USIA 66377 WC�_ - rrrcrr SN o CEG A60403 u m a vVrvv BZUiIk.c 0171 Cl sn `' Iz 1e,l� ATTACHMENT A �l` f, b o i l e r- s INSTRUCTION MANUAL FOR INDOOR & OUTDOOR RITE POWER BURNER FIRED* BOILERS 70 Horsepower 125 Psi Hot Water Boiler Rite Engineering & Mfg Corp. 5832 Garfield Ave. Commerce, CA 90040 Tel: (562) 862-2135 Fax: (562) 861-9821 www.riteboiler.com Read instructions carefully before proceeding with installation and operation. Post and maintain instructions in legible condition. "Excludes Durafin Boilers. Please check website for updates and addendas to the manual. 111) 2012 TABLE OF CONTENTS SAFETY WARNING NOTICES: Your physical safety and the safety of others is very important. Throughout this manual we have provided safety warning notices to alert you to potential safety hazards. A safety notice will be preceded by: DAN G� IT MEANS: You CAN be KILLED or SERIOUSLY HURT if you don't follow instructions. EQUIPMENT WARRANTY NOTICES: When properly installed, operated and maintained, Rite Boilers can easily offer forty or more years of service. Throughout this manual we have provided equipment warranty notices to alert you to potential practices that could lead to premature repairs. An equipment warranty notice will be preceded by: CAUTIONI IT MEANS: Failure to follow these instructions will void warranty and may lead to premature repairs. Page Number 1. SAFETY WARNING NOTICES ..................... See Below 2. EQUIPMENT WARRANTY NOTICES ................. See Below 3. RECEIVING...............................1 4. STORAGE................................1 5. PLACEMENT ..............................2 6. INSTALLATION ............................. 2-8 7. WATER TREATMENT AND DERATIONS ............... 9-10 8. START-UP ................................ 10-15 9. SEQUENCE OF OPERATION ..................... 16 10. OPERATION, MAINTENANCE AND SERVICE ............ 16-21 11. WEATHERPROOF - OUTDOOR BOILERS .............. 22 12. TROUBLESHOOTING ......................... 23-39 13. REMOVAL FROM SERVICE (LAYUP) ................. 40 14. GLOSSARY ............................... 41-42 15. HOT WATER SYSTEM PIPING .................... 43-46 16. STEAM SYSTEM PIPING ....................... 47-51 17. WARRANTY ............................... Back Cover SAFETY WARNING NOTICES: Your physical safety and the safety of others is very important. Throughout this manual we have provided safety warning notices to alert you to potential safety hazards. A safety notice will be preceded by: DAN G� IT MEANS: You CAN be KILLED or SERIOUSLY HURT if you don't follow instructions. EQUIPMENT WARRANTY NOTICES: When properly installed, operated and maintained, Rite Boilers can easily offer forty or more years of service. Throughout this manual we have provided equipment warranty notices to alert you to potential practices that could lead to premature repairs. An equipment warranty notice will be preceded by: CAUTIONI IT MEANS: Failure to follow these instructions will void warranty and may lead to premature repairs. RECEIVING 1. Before signing Bill of Lading, check for any signs of external damage. Be sure you have received all the pieces noted on the bill. Barometric Dampers are shipped loose. 2. DANGER Offload the boiler as shown in Figure 1. Follow safe rigging procedures and use load rated equipment. IIIIIi1G BURNER Figure 1 POINTS SPREADER BAR TING LUG SKID ICAUTION1 Forklift underneath base only if forks are long enough to extend rail -to -rail (Dimension B in catalogs). 3. ICAUTION Place the boiler gently onto a firm, level surface. Hard drops, or rigging the boiler on its side unless pre -approved, can cause damage. CTnl4ArZF: 1. If the boiler is temporarily stored outdoors it must be completely protected from the elements by a tarp or other means. 2. Keep the Barometric Damper and any other equipment shipped loose with the boiler, otherwise they have a way of becoming lost. 3. Leave plastic cap plugs in place and keep debris from entering boiler stack(s) and plumbing connections. PLACEMENT 1. Boiler may be placed directly onto pad as shown in Figure I or moved on rollers as shown below in Fi,urc 2: Figure 2 =EL BASE 2. The boiler must be installed on a level. concrete house- keeping pad or other approved non-combustible surface that has been engineered to support the operating weight of the boiler. 3. If the boiler was shipped on a wooden skid, remove the skid prior to final placement on the pad. 4. When anchoring the boiler to the pad observe th following: 4.1 See job specification for any special seismic anchorage requirements. 4.2 If in doubt, contact your local Building & Safety Dept. or a qualified mechanical engineer for assistance. 4.3 Refer to appropriate Rite brochure for boiler weights, water content and dimensions. 4.4 Boilers not shipped on wooden skids will require anchor plates (by others) 5. When installing on a concrete pad be sine the pad is big enough in length and width. The minimum requirement is that the pad must extend beyond the anchor plate holes by at least six (6) times the anchor bolt diameter. (See Figure 3 on the next page). PG 1 RECEIVING / STORAGE / PLACEMENT Boilers Shipped Boiler Foot On Wooden Skids Detail & Section ,A„ Dimension (See Catalog) Top 0 View Boiler Foot (see detail) Boilers Shipped On "C" Channel Concrete Pad Or I -Beam Detail & Section Concrete— Pad (see detail) O %6" Hole Boiler Stack INSTALLATION General 1. In most cases the installation will be carried out by a licensed contractor who must pull the required permits before starting the job. Before the boiler is started up, all the work permits should be signed off. 2. The installing contractor must carry out the work according to state and local codes which may exceed nationally recognized codes such as the Uniform Mechanical Code, Uniform Plumbing Code, National Fire Protection Agency, ASME CSD -1, National Electric Code, etc. Additional insurance requirements or job specifications may also be required. For example, it is mandatory that Section 1 Boilers are piped up in part by an ASME stamp holder in accordance with B31.1 of the ASME Power Piping Code. 3. Always lay out and install the largest components first. Start with the stack system and combustion air ducts, followed by the water or steam mains next and do the smallest diameter runs like water make-up and drain lines last. Plan carefully. The best installations are those where the largest components are run as straight and direct as possible. Combustion / Ventilation Air I . Provide at least L'_ square feet of free air opening from outside for every 1 million btuh of maximum rated input for combustion. Check local codes for exceptions. Figure 3 INSI AI.I.ATION / COMBUSTIONNENTILATION AIR PG 2 y 6xd �— 6xd Top o 4iichorPlatcs t'xd / And Field Weld By Others 2. Provide the same size opening at a high point in the room for ventilation. 3. If additional ventilation is required it is better to force air into the room. Avoid exhaust fans whenever possible. 4. Louvers can significantly reduce free air openings. If the free area is not known, it shall be assumed that: 4.1 Fixed wood louvers will have 20-25`%, free air opening. 4.2 Fixed Metal louvers will have 60-70`%, free air opening. 4.3 Metal mesh screen (minimum 1/4") will have 98% free air opening. 4.4 Blade type motorized Combustion Air Dampers (CAD) will have 95°/, free air opening. 5. Doors and windows that can be closed are not considered to be a source for combustion or ventilation air. 6. When combustion air dampers are used, make sure an electrical interlock (end switch) proves the dampers are fully open before the boiler is allowed to tire. 7. DANGER Exercise caution anytime a fan is used to exhaust air from a boiler room. Negatively pressurized boiler rooms can cause poor combustion and products of combustion to spill out of the barometric damper into the boiler room. Be sure the air pressure in the boiler room is the same as it is outdoors under all operating conditions. 8. CAUTION Determine if the boiler room is next to another equipment room and the two share a common door. If the other equipment room contains air handling equipment, boiler room's air pressure can go negative if the connecting door is left open. In such cases, a door interlock switch must be used to prevent the boiler from firing unless the connecting door is closed. Draft Control Rite Power Burner Fired Boilers require a slightly nega- tive firebox pressure (-.01" w.c.) at all firing rates. The burner blower motor is therefore required for combustion purposes only and not to force the products of combustion through the boiler and out the stack. Natural draft makes use of the leftover heat going up the stack to create all the draw necessary for proper operation. The barometric damper balances the draft at the vent connector as the stack heats and cools and firing rates change. A slightly greater negative pressure at the vent connector minus the pressure drop through the tube bundle yields the -.01" to -.03" w.c. negative firebox pressure. 2. ICAUTIONIThe Barometric Damper must be properly installed and adjusted at the jobsite. It should be located as close to the vent connector as practical with the proper offset (See Figure 4). 3. Barometric Dampers must have the right number of washer weights to produce a draft at the vent connector of between —.03" to —.09" w.c. when firing. Increasing the number of weights makes it harder for the damper gate to open. This results in less dilution air entering the stack, thus increasing the boiler's draft. Too much draft is better than no draft (which can cause sooting and overheating) but keep in mind that too much draft reduces heat transfer efficiency and can pull the flame off the burner head or diffuser to a point where the air/fuel mixture becomes so poor that the flame pulsates and becomes unstable. 4. Factory mounted draft gauges are standard on all boilers. They should be used for adjusting the barometric during start-up and then periodically checked during routine maintenance to make sure the draft stays within range. The fluid will slowly evaporate and must be replenished from time to time. Use only Dwyer .826 Specific Gravity Red gage oil and add with an eyedropper to prevent overfilling. Stack Requirements Natural gas or propane fired boilers are U L. listed for use with Type B gas vent provided a barometric damper is installed as shown in Figure 4. Check local codes for exceptions. Type B is double wall stack, widely available from a number of different manufactures. It is relatively inexpensive, easy to install and available in 3" through 30" diameters. Type B vent is suitable for Category I appliances only - combustion equipment defined as having net stack temperatures less than 400° F., operating with negative draft to the stack termination and producing non -condensing flue gasses. Oil fired boilers. combination gas/oil fired boilers and digester gas boilers cannot use Type B vent. They must use a stack that has Type 316 Stainless Steel inner liner or better to prevent sulfuric acid corrosion. The barometric damper installation requirement is the same, however the red stop hardware on the barometrics for oil tiring should not be removed. 2. Refer to gas vent manufacturers catalogs for detailed installation instructions. Most vent manufacturers offer free engineering support for specific job requirements as one of their selling tools. This can take the guesswork out of unconventional stack designs. 3. It is good practice to incorporate a vent support plate for independent stack support and an adjustable length (telescoping) section for future boiler/stack separation. This will facilitate fireside tube cleaning should it ever be required. Terminate Type B vent stack with a B vent rain cap except in those locations where frequent high winds may necessitate a Breidert type cap available from Rite. 4. CAUTION A horizontal stack run must not exceed 75% of the vertical stack height (NFPA 54 7.6.1d) without the addition of an engineered mechanical draft system (induced draft fan). PG 3 1NSTALI ANON Stack Requirements continued CAUTION Boiler installations \pith unavoidable nc,ati\c air conditions - such as factories with exhaust fans - will generally require engineered mechanical draft systems. 6. CAUTION_ Never reduce the boiler vent connector 8 diameter without written factory approval. Stack size can often be safely reduced at substantial cost savings but only after a review and written approval by either the vent manufactUrer or Rite. 7. FC--AU--TI-O--N-1 If the stack diameter is reduced from the vent connector diameter, the draft gauge "Good" range (green) becomes meaningless because the smaller diameter stack requires a higher CFM and therefore a higher negative static pressure at the vent connector. In order to find the correct draft, remove the 1/8" pipe plus at the rear firebox view port and measure the firebox Opt—al [ Spill Svnr B"mei Figure 4 draft at high tire. It should be between -.01" to -.03 w.c. Adjust the washer weights on the barometric damper until this is achieved and then mark the draft gauge at the vent connector with the new correct setting. Firebox pressure must always remain slightly negative when the boiler is firing. After setting up the burner and draft, always verify firebox pressure with a simple smoke test: Open the front viewport after the boiler has been at high fire for at least ten minutes and provide a smoke source (or something similar) and inch or so from the opening. If the smoke is gently pulled in, the draft is good. If the smoke is rapidly pulled in, the draft is too high. [CA--U--T-1-0-N-1 If the smoke is unaffected then the firebox is at neutral pressure and needs a little more draft. Smoke blowing away from the opening means the firebox is under positive pressure and corrective action must be taken immediately. `r Bullhead Vent Tee Reduced Diameter Stack Section (If Required) 7� Flue Gas 1 of Boder Casng LMIiW, Control Table for Barometric Dampers D—per Sve (A) 18 12 14 16 18 28 24 28 72 (:OW Length (B) 4-3/8" 53/4" 1-118" 8-3/8" 8-1/4" 9-5/8" 12.3/8" 13-1/8" 15-314" NOTE: BE SURE TO USE CORRECT COLLAR LENGTH. TOO SHORT OR TOO LONG MEANS A LESS EFFECTIVE CONTROL. Barometric Damper Location For Indoor Boilers (Barometric dampers cannot be installed on outdoor boilers) INSTALL/V110N PG 4 Clearances 1. U.L. 795 requires the following minimum clearances to combustible construction from the boiler: CLEARANCE TO COMBUSTIBLE MATERIALS MODELS FROM ABOVE FROM FRONT SIDES R REAR VENT CONNECTOR 48W - 1250W (Water) 200 18 210 21 48S -1250S (15# Steam) 18" 48" 18" 18" P9.5 - P250 (150# Steam) PW9.5-PW250 (Water) 48" 96' 36" 36" 2. For tube cleaning or replacement, leave an area in front of the boiler that is approximately the length of the boiler jacket and 24" or more at the rear. Codes typically require a minimum 24" clearance from the non -controls side of the boiler and 36" or more around the controls side. The National Board I-2330 clearances for Section I boilers(Rite "P" & "PW" Series) require minimum 36" clearance to any obstruction around the sides and back. Pennsylvania requires 30" clearance around all boilers. Always check state and local code clearances before laying out the boiler room. 3. Avoid blocking headplates with pipes or other obst-uc- tions. For boilers ordered with optional hinged headplates, leave room for the headplates to swing completely open 180°. See headplate swing dimension "T" in boiler catalog. Piping - Water Boilers 1. See recommended piping diagrams at the back of this manual, pages 43 to 46. 2. CAUTION All Rite Boiler waterside surfaces are thoroughly cleaned prior to shipping so a boil -out procedure is not required. Taking a few extra minutes to remove thread cutting oil and other contaminants from the field piping as it is being assembled can reduce or eliminate the need for chemically flushing the system. 3. Always install the system pump so that the suction side is nearest the boiler hot water outlet. This lowers the risk of air entering the system and does not impose the system head on the boiler. Always pump away - not toward - the expansion tank system connection. 4. Rite Hot Water Boilers can be fired safely with the system pump off as long as there is water in the boiler and the low water cut-offs detect water. There is no required minimum or maximum flow rate through a Rite PG 5 boiler and a flow switch is not a safety requirement. 5. CAUTION Alxvays arse dielectric unions or dielectric flange kits when connecting copper l ipe to the boiler to avoid galvanic electrolysis. 6. An expansion tank must be installed in every hot water heating system. The tank can be bladder or compression type. Do not use open -to -atmosphere type. To order the correct size tank you must know: Total system volume in gallons; minimum anticipated system water temperature at start-up; maximum anticipated system operating temperature and minimum system operating pressure. Minimum system operating pressure can be calculated by dividing the overall height of the system piping above the boiler (in feet) by 2.31. For exceptions, see next paragraph. 7. Minimum system water pressure requirements for sea level to 3000 feet elevation are as follows: Maximum Boiler Operating Temp. (°F) Minimum System Pressure (PSIG) 180 12 190 15 200 18 210 21 220 24 230 27 240 30 For elevations 4000' and higher, maintain a mininunn 30 psi system pressure. For Section I High Temperature Hot Water boilers, refer to the steam tables to find the corresponding pressure to the maximum operating temperature and then add an additional 15 psi to that pressure to find the minimum system pressure. 8. It is a good idea to install a relatively inexpensive water meter in the water make-up line. On closed loop heating systems it is the best way to detect system water loss early on before harmful amounts of entrained solids and oxygen are introduced into the boiler system via water make-up. 9, CAUTION Never let chilled water from a cooling sys- tem circulate through the boiler under any circumstances. 10. CAUTION Reheat systems must not allow the chilled water loop to inadvertently cool down the heating loop inside the air handler(s). 11. DANGER Never use compressed air to test water system piping for leaks. Use water only. INSTALLATION Piping - Stearn Boilers 1. Scc recommended piping diagrams at the back of this manual, pages 47 to 51. 2. Do not reduce the steam boiler outlet nozzle size. Reducing the diameter of the pipe of the boiler's outlet nozzle to the steam main may raise steam exit velocities to the point at which water is "lifted" or carried over from the boiler into the main. 3. Use black pipe - never galvanized pipe - for steam mains and blow -down lines. Condensate return lines should be constructed of Schedule 80 pipe or Type K copper. If copper is used, be sure the fittings are silver soldered rather than soft soldered as condensate return tempera- tures are often at or near the soft solder melting point. Use dielectric unions or flange kits when connecting copper to steel. 4. It is a good idea to install a relatively inexpensive water meter in the make-up line to record the amount of make-up water you are using and help keep the water treatment program on track. 5. For Rite steam boilers (low and high pressure) the boiler feed pump should be sized to deliver the following GPM per boiler horsepower (BHP) at operating pressure as shown at the bottom of this page. • I RHP = 34,000 BTU output. • .069 x BHP z The actual GPM rate of evaporation. Recommended feed rate is 2.5 to 3 times this rate. 6. Section I Boilers with heating surface greater than 500 tt' (Rite P125 and larger) must have 2 feed water pumps each capable of supplying the required GPM at a head pressure 3'%, higher than the safety valve setting per PG 61.1 of the A.S.M.E. Code. 7. 1 DANGERI Never use compressed air to test steam sys- tem piping for leaks. Gas Piping 1. The use of teflon tape is not recommended. Thoroughly clean all thread cutting oil and other debris such as metal chips, welding slag and pipe dope from inside the gas piping during assembly. BOILER HORSEPOWER INPUT MBH 9.5 398 STEAM LB/HR 328 RECOMMENDED GPM 1 RATE 2 10 419 345 2 12 502 414 2.5 15 628 518 3 20 838 690 4 30 1255 1035 6 40 1674 1380 8 50 2093 1725 10 60 2511 2070 12 70 2931 2415 14 80 3348 2760 17 100 4185 3450 21 125 5230 4313 26 150 6276 5175 31 200 8369 6900 41 225 9425 7762 47 250 10456 8625 52 275 11500 9487 57 300 12500 10350 62 1Ns,rnt.LXF10n PG 6 Gas Piping continued 2. CAUTION A drip leg is recommended at or near the connection to the gas train. If an optional wye strainer is used it should have a 40 mesh screen. 3. Be sure the natural gas supply pipe is large enough to deliver the required CFH at the inlet pressure required. If in doubt, refer to the Uniform Mechanical Code or NFPA 54 gas line sizing tables. 4. CAUTION When pressure testing a new gas line with air, be sure the boiler's main and pilot cocks are in the closed position and disconnect the union or flange con- nection between the main gas cock and the drip leg. This will prevent over -pressurization damage to the gas train valves and controls. 5. If the gas train is supplied with a normally open vent valve, it is a good idea to install a full size sight -flow indicator on the discharge side of the valve for visual confirmation that the valve is closed when the boiler is firing. Regular checks can prevent the loss of natural gas out the vent valve should the valve fail to close when energized. 6. Per current U.L. 795 standards, the boiler's gas train will require that one or more separate vent lines be piped outdoors to a safe point of discharge. 6.1 The following two types of valves mast be Burner & Electrical I. CAUTION Most burners require support under the housing to reduce the cantilever effect. Screw a support pipe into the coupling underneath the burner and into the floor plate flange. Adjust or shim until burner is sup- ported. See Figures 4 and 5. 2. The correct voltage must be supplied to the boiler/burner as per the nameplates and connected to the proper point of connection per the wiring diagram. If the burner door is hinged, run the supply power in flexible conduit from the side of the boiler so the door can be swung open without disconnecting the power or conduit. If three phase power is required and no stepdown transformer is provided, run a separate 120/60/1 control circuit or add a stepdown transformer sized per the burner manufacturer's recommendation. CAUTION Do not add additional loads to a stepdown transformer without burner nnanufac- turer's approval. Power supply must be clean and all stepdown transformers must be grounded to neutral. Voltages over 132 VAC or under 102 VAC are out of range and can cause safety controls to fail or malfunction. 3. When connecting power to the boiler make sure the polarity is correct and that there is less than .5 VAC between the neutral supply wire and the "'round conductor. Check that fan wheel rotation is correct and that separate oil pump motor rotation is also correct if' supplied. rented individually: 4. CAUTION A good electrical ground to the boiler 1. Gas pressure regulators (except those approved service connection is essential for two reasons: Poor for use with vent limiter). grounding may cause the flame safeguard control to 2. Normally open vent valves. malfunction and stray voltages may cause electrolysis within the pressure vessel. 6.2 Diaphragm operated gas valves and diaphragm operated gas pressure switches that require 5. CAUTION Electrolysis due to poor electrical ground - venting (look for threaded vent pipe connection ing and/or stray voltages passing through the boiler to on valve or switch body) may be manifolded ground has been known to cause severe pressure vessel together into a single common line provided it damage. The problem usually goes unnoticed until a tube has a cross sectional area not less than the area leak occurs and the cause turns out to be a small crater of the largest vent line plus 50% of the area of on the inside of the tube - often underneath a small and all additional vent lines. otherwise insignificant looking mud deposit. While this problem is relatively rare, it should be checked for by a 6.3 DANGER DO NOT pipe any gas vents into the skilled electrician before the boiler is put into service in combustion chamber or stack. the following manner: Using a digital multimeter with sharp probes, check for the presence of millivoltage 6.4 FNOTICEI Always terminate vents away (AC) between any bare metal spot on the pressure vessel from air intakes or sources of ignition. Be sure and the building ground. A reading of 2 millivolts or less that moisture and insects cannot enter the vent is good and no corrective action is required. If over pipes. Always utilize a drip leg to keep moisture 2 millivolts, either find the cause and correct it or install from traveling back down vent tubing and a separate ground rod dedicated to the boiler. Annual damaging the diaphragms. See Figure 5, testing will show if the ground rod needs to be turned in order to break off deposits that can insulate and inhibit its grounding effectiveness. PG 7 INSTALLATION Building Automation Systems (BAS) CAUTION Rite Hot Water Boilers must not be oper- ated with return water temperatures continually less than 135° to 140° F (see pages 44 - 46 for low temperature supply systems). Outdoor reset controls must be carefully programmed not to reset boiler supply water tempera- tLIres so that return water temperatures could fall below 135". 2. CAUTION For HVAC reheat systems, the heating system pump should be programmed to turn off no more than 10 minutes atter an unscheduled boiler shutdown (such as a limit or flame failure) in order to prevent the heating water from getting chilled in the air handler and circulated back to the boiler where it will condense. 3. CAUTION Care must be taken when integrating Building Automation Systems (BAS) and associated Energy Management Systems (EMS) with the boiler control circuit. BAS and EMS systems - while well intentioned - have been known to override boiler control systems and inadvertently create poor or unsafe operating conditions. EMS and BAS systems may receive informa- tion from the boiler control system but signals sent by the BAS or EMS to the boiler control system should be limited to establishing load demand and Initiating start/ stop sequence. BAS and EMS systems must be pro- grammed not to allow• return water temperatitre to the boiler below 135° to 140"F 4. CAUTION Do not use solid state Triac type relays to enable/disable boiler. Use only electro -mechanical or ice cube type relays. The following operating recommen- dations for Rite Boilers should be part of any EMS Strategy: (PREFERRED) 4.1. Leave the boiler and primary loop pump on during the heating season while turning off all secondary loop pumps, air handlers, etc when heat is not required. Fuel consumption during `off hours" will be limited to boiler and primary loop piping radiant losses which are generally small. A night temperature setback control may also be used to reduce system water temperature to 135" to 140" F. - the minimum recommended return water temperature. Roof Bug Screen Supp Common Vent Line (If Required) INSTALLATION PG 8 Flashing Union(s) Copper, Block Or Galvanized Pipe Gas Pressure Regulator Vent Line (If Required) Vent _1 Drip Legs Tubing Figure 5 (ACCEPTABLE) 4.2 Leave the boiler on and turn the primary loop pump OFF. Due to natural internal circulation, pumped water flow tlu•ough a Rite Boiler is not required when firing. Important: When system heat is again required, the cool system water should be blended slowly back into the boiler so the boiler's water temperature doesn't fall below 135' E This can be accomplished manually or with automatic controls. 5. While initial or infrequent cold start-ups are considered routine and will not harm the boiler - failure to follow the above strategies will cause repeated Thermal Stress Cycling. Although Rite Boilers are designed with floating heads to minimize the stresses of tube expansion and contraction, tube loosening (the "slippage" of the rolled portion of the tube in the tube sheet) may occur if the boiler is subjected to repeated cold start-ups or excessive on - off cycling. 6. Boilers owners and specifications engineers should take the following quote from the ABMA's "Guideline for the Integration of Boilers and Automated Control Systems in Heating Applications " into account: "Automatic programmed de -energizing of boilers should be very closely examined. It is (also) questionable as to the real energy savings to be realized in cooling a boiler or a system on a regular basis only to reheat it in a short time later". WATER TREATMENT System Flush/Boilout Procedure: Boiler tubes are typi- cally coated on the outside with rust inhibitors. On fire - tube boilers. these and other contaminants are in contact with the water and should be removed or priming and foaming may result. This is generally done by the install- ing contractor following a boil -out procedure given by the boiler manufacturer. There are no such coatings inside a Rite watertube boiler. After the tubes are rolled, all traces of tube rolling grease are removed along with any other contaminants. A Rite boiler may therefore be put directly into service without a time consuming boil - out procedure. If the system piping recommendations in paragraph 2 on page 5 are followed by the installer, the need for a system flush can also be eliminated. For more information on what a boilout procedure and system flush entails, contact the factory. 2. WATER TREATMENT FOR CLOSED HOT WATER SYSTEMS: Closed hot water systems require some chemical treatment as no system is completely tight 100%, of the time. "I'hcse chemicals are introduced into the system via 2-5 gallon chemical pot feeders. The chemical treatment can vary depending on the systems operating temperature and pressure. Consult with a qualified water treatment specialist for further information. Regularly monitor that the expansion tank is working proper and the relief valve is not discharging water. Keep the system tight and free of leaks. Soft water make-up is not required. A pH level of no less than 9 Should be maintained. CAUTION A pH level below 7 will cause an acidic attack of the pressure vessel and void the warranty. 3. ICAUTIONI For metal finishing systems that use heat exchangers or coils, check the boiler water regularly for low pH which would indicate a breach between the boiler water and the acid baths. 4. GLYCOL: Glycols reduce heat transfer efficiency and can cause corrosion if the water quality is poor. If glycols are used, consider these tips and guidelines: 4.1 Consult your glycol distributor. Rite is a steel watertube boiler. 4.2 Use only enough glycol for "burst" protection, not "freeze" protection. 4.3 Use only with good quality water defined as having less than 25 ppm of chloride and sulfate; less than 50 ppm of calcium and magnesium and less than 100 ppm (5 grains) of total hardness. 4.4 Higher flow rates will reduce film coefficient of glycol and thus proportionally improve heat transfer. 4.5 Higher operating temperatures will also improve heat transfer efficiency of glycols but not as much as higher flow rates. 4.6 Never exceed more than 50% glycol in solution. 4.7 Ethylene glycol is better at transferring heat than propylene glycol. Ethylene glycol is highly toxic if ingested. 4. NATER TREATMENT FOR STEAM BOILERS: CAUTION Failure to maintain an effective water treatment program as outlined below will void warranties and lead to premature pressure vessel failure. There are three basic components for effective scale and corrosion prevention in steam boilers. 4.1 SOFT WATER MAKE-UP: All fresh water make- up must come through a softener 100% of the time CAUTION Avoid deionized or reverse osmosis systems that lower pH levels. 4.2 BLOW -DOWN: It is recommended that a boiler be blown down a minimum of twice per R hour shift. The goal is to keep the TDS (Total Dissolved Solids) level between 2200 and 2600ppm. A uniform 15 second to 30 second blow -down is typical for most boilers when they are in proper control ranges. Subsequent boiler water analysis is required to properly determine exact length and frequency. To properly blow -down a boiler a washing action is recommended. This is achieved by slowly opening the blow -down valve for approximately 5 to 10 seconds, then slowly closing the valve and repeat again, until the recommended time has been achieved. This allows the solids to remain suspended for more uniform removal during the blow -down procedure. The water column also must be blown down at least once per shift; this helps to keep the column clear of debris and allows the operator to determine if the low water cut-offs and pump start controls are working. The blow -down tank should also be drained and flushed at least once every six months to help remove sludge and scale build up which can cause back pressure on the boiler leading to insufficient blow -downs. 4.3 CHEMICAL TREATMENT: Use an automatic chemical metering pump to inject boiler chemicals into the boiler feed line. The metering purnp should PG 9 WATER TREN111ENT WATER TREATMENT continued be wired in series with the boiler feed pump and the point of connection should be a stainless steel tee down steam of the check valves and just before the shutoff valve at the feedwater inlet connection (see Page 48). Feeding chemicals directly into the feedwater tank is preferred by some water treat merit specialists. If so, be aware that these chemicals can be highly corrosive to feedwater tanks at the point of entry and the dispersal in the tank dilutes their effectiveness inside the boiler where they are intended. In addition, pump seals exposed to high concentrations of chemicals often fail prematurely. 5. CAUTION Annual or more frequent waterside inspections will confirm the effectiveness of your water treatment program. A successful program is one that keeps both scale and corrosion in check. 6. Some low pressure steam boilers are installed in gravity return heating systems that do not have a return tank or feed pump (seepages 50 & 51). In most of these systems there is no water treatment taking place. For these instal- lations. use soft water make-up and install a water meter in the make-up line. Check the low water cut-offs once a month by performing a slow steam evaporation test as described on page 18. Blow -down these boilers only when the TDS exceeds 2600 ppm. 7. The plI of a steaming boiler should be between 10.5 to 11.5. P/Alkalinity: 200-400 ppm. M/Alkalinity: 400- 800 ppm. Sulfite: 20-60 ppm. Hardness (soft water): 0 -Trace. Chlorines: 5 to 7 times the supply soft water level. Altitude Derations Above 2000' CAUTION In most cases, power burners can be pro- vided with larger fan wheels and motors to compensate for lower air densities at higher elevations. The required input/output at elevation should be agreed upon by all parties bdbi-e an order is placed so there is no confusion as to the actual input/output that the boiler will do. WATER TREATMENUSI'ART UP/DERATIONS PG 10 START - UP 1. CAUTION / DANGER Only highly qualified trained and licensed individuals should be asked to do boiler/ burner start-ups. 2. It is the contractor or owner's responsibility to complete steps 3-11 below before requesting start-up in order to avoid the cost of more than one site visit. 3. Verify that the installation instructions have been followed and that all permits have been signed off. 4. Make sure the system pumps are running and most importantly that there is a waY to drop the loud. 5. CAUTION I Make sure air has been bled from the natural gas supply line and that the supply pressure is within the range shown on the boiler shop sheet. A pipe tee with plug has been provided in the boiler's pilot gas line near the main gas cock for this purpose. If the supply gas pressure is over 28" w.c., make sure the boiler has been supplied with suitable high pressure regulators (main and pilot). If in doubt, consult factory bcfiore turning on the gas to the boiler. 6. For oil, make sure there is oil in the tank. Prime the oil pump and circulate the oil without the burner firing. Check the suction line to the oil pump and make sure it doesn't exceed 10 inches mercury of vacuum or more than 3 PSIG positive pressure. Bleed air from lines through bleed valve on integral pumps. Make sure teflon tape was not used on any oil line piping and check unions, packing glands strainer caps etc. for tight seal to prevent oil leaking out or air being sucked in. Make sure the oil storage tank foot valve (check) is holding when the pump is off. 7. iCAUTIONI Make sine there is water in the boiler. For hot water boilers, make sure the system has been filled and air has been bled from all manual bleed valves. 8. For hot water boilers, verify that an expansion tank has been installed and that if a valve is installed between the tank and system it must be open. An elevated, compres- sion type tank should have water in the lower third of the gauge glass when filled. The air pressure in bladder/dia- phragm tanks should be slightly higher than the regulated make-up water pressure and the tank should be pressur- ized before the boiler and system is filled with water. If expansion tank is sized and operating properly, the boiler pressure gauge should show a negligible increase in pres- sure while going from a cold start-up to operating tem- perature. See page 13, paragraph 31 for exception. START - BJP continued 9. For steam boilers, make sure the feedwater system is operating properly and that all make up water is coming through a water softener. Make sure that a blow -down tank or separator has been installed per code. Coordinate the chemical treatment start-up to overlap the boiler start-up. 10. Make sure any intake or exhaust fans or other equipment that can change air pressure conditions in the boiler room are operational and make sure the start-up person is aware of them. 11. Provide the start-up technician the "As Built" wiring diagram and the burner installation and instruction packet hclbre site visit. In addition, burner O & M manuals that contain additional information can be found on-line at http://www.riteboiler.corn/om-nianuals.htin1. 12. [CAUTION/ DANGER Boiler/Burner start-up Should be performed only by qualified technicians. If pos- sible, the boiler operator(s) should witness the start-up. 13. Prior to going to the job site, the start-up technician Should verify with the installing contractor that steps 3-10 have been completed. If on arrival you find any aspects of the installation incomplete, wrong or question- able - do not leave the site before making a complete survey of everything that needs to be reviewed or cor- rected. Go over this list with the installing contractor. Failure to provide a complete list of corrections can lead to back charges by the contractor. 14. For hot water boilers, set aquastats as labeled in the following manner: OPERATOR or LOW FIRE: Between 155" F. and 230° F. HIGH FIRE (if used): 5 to 10 degrees less than low fire. MODULATION (if used): Set so that the burner reaches minimum firing rate prior to the operator aquastat turning off the burner. HIGH LIMIT: 20 degrees or more above operator or low fire control. 15. For low pressure steam boilers (15 PSI) set pressure controls as follows: OPERATOR or LOW FIRE: Between 3 and 12 PSI. HIGH FIRE (if used): 1 - 3 PSI less than low fire . MODULATION (if used): Set so that the burner reaches minimum firing rate prior to the operator pressuretroll turning off the burner. NIGHT SETBACK (if used): Usually 1 -2 PSI. HIGH LIMIT: 13 - 14 PSI. 16. For High Pressure Steam Boilers (M.A.W.P. 100-150 PSI) set pressure controls using similar ratios to low pressure steam boilers. The high limit pressure control Should be set at least 10 PSI less than the boiler's relief valve setting. 17. Rite power burner fired boilers manufactured after January 1, 2011 will be supplied with ceramic fiber side and rear panels instead of cast refractory. The burner door will still be cast refractory. If no refractory curing instructions are taped inside the burner panel cover then no cure time is required during start-up. CAUTION If curing instructions are provided then the instructions must be followed or refractory spalling could result. 18. Refer to the burner manufacturers O & M Manual and "As Built" specification sheet. Verify that the electrical and fuel supply requirements are met. Follow the burner manufacturer's start-up recommendations. If these cannot be obtained, steps 19-37 in this section provides a general outline of common power burner start-up procedures except for some low NOx and surface combustion type burners. For water boilers, record the boiler pressure when the system pump is both on and off prior to tiring the boiler for future reference. 19. Bump the burner motor starter or contactor and check fan rotation. If backwards, change any 1 leg of 3 phase power supply. If there is excessive vibration the fan wheel may need to be balanced or replaced. 20. If the burner is straight gas or combination gas/#2 oil. set selector switch to gas. Tum the pilot gas cock off. Turn the downstream leak test cock off. Install a gas pressure gauge where it can sense the supply gas pressure to the inlet of the gas train. Open the upstream main gas cock slowlti•. Manually reset the high and low gas pressure switches if supplied, making sure the setpoints are properly set. PG 11 STARTUP START - U P continued 21. Twin the burner power switch on. Manually reset the low water cut-off and flame safeguard controls if required. The burner should sequence to a prepurge (fan on only) stage for 10 to 60 seconds depending on the size of the burner. The burner should then sequence to a pilot trial for ignition. On many straight oil fired burners, there is no PTFI and the spark ignition will directly light off the atom- ized oil. Some straight oil and combination gas/oil burg- ers will use a natural or L.P. gas pilot to light off the oil. All gas pilot burners should lock out on flame failure due to the pilot cock being closed. DANGER It is important to check that the spark ignition alone does not cause any flame signal whatsoever. If this occurs, it must be corrected before proceeding to the next step. 22. Open the pilot gas cock and carefully bleed off any air in the pilot tubing. When you smell gas immediately tighten the tubing fitting back up. If the gas is L.P. (propane) make sure all piping is leak tested and tight. Propane is heavier than air and will accumulate on the ground if it leaks. Manually reset the flame safeguard control and allow the burner to sequence to a pilot trial for ignition. On burners with inputs 2.5 million BTU's and less, the Pilot is usually intermittent which means the pilot valve (but not the spark) remains on all during the main flame cycle. On burners larger than 2.5 million BTU's, the pilot is interrupted, meaning both the ignition transformer spark and the pilot valve turn off approximately 10 seconds after the main flame lights. 23. For burners with intermittent pilots, the main fuel valves will open only after a pilot with sufficient flame signal strength is established. The flame scanner will not differ- entiate between seeing the pilot flame and the main flame. To bring on the main flame, slowly open the downstream leak test cock. 24. For burners with interrupted pilots, open the downstream leak test cock first. If the pilot establishes itself within 10 seconds, the main fuel valves will begin to open. If the main burner is not successfully lit before the pilot is extin- guished, the flame scanner will see this and immediately shut off all the fuel valves and lock the burner control out. 25, CAUTION / DANGER A pilot turndown test must be performed. This involves reducing the size of the pilot flame to a point that is at the minimum detectable flame safeguard level but can still light off the main flame reli- able. Do not proceed until this is done. 26. Sequence the boiler to main flame. For modulating or high -low firing burners, hold the burner at low fire and then adjust the air/fuel ratio to the burner manufacturers recommended settings. Leave the burner on for 30 START UP PG 12 minutes then turn the burner off for at least twenty-five minutes. Use this time to check the following: gas leaks on the gas train; water leaks around the headplates and boiler piping; control voltage supply in range (not less than 102 and not more than 132 VAC.); loose electrical and conduit connections. 27. For hot water boilers, check the low water cut-oft(s) to verify that they will shut the burner off in the event of low water. If two low water cut-offs are used, tem1mrurilrr jumper the primary LWCO after it has turned the burner off in order to test the auxilary. ICAUTIONI Do not use "Test" buttons on probe low water cut-offs for this test but do an actual slow drain test by closing off the water supply and return valves on the boiler, lifting the relief valve handle to relieve pressure and break the vacuum and cracking open the drain valve at the back of the boiler. The burner should cut off when the water level drops 4-5 inches below the top of the headplate. When finished, close the drain valve, crack open the return water valve and raise the relief valve handle until all the air is purged out. Make sine the relief valve resects tightly then open the supply and return water valves to their original posi- tion. 28, 1 CAUTION I For steam boilers, let the feed pump or feed - water valve fill the boiler to normal operating level and then perform a slow steam evaporation test as described on page 18. 29. As the boiler heats up, re -tighten the headplate bolts uni- formly. Work from the centers to the corners as you go: center left bolt, center right bolt, center top bolt, center bottom bolt, etc. Make sure all bolts are moderated- tight when finished. If hand holes are supplied make sure the crab mut is snug as well. If insulated headplate covers are provided, leave them off until the very end of start-up. CAUTION Tightening headplate bolts beyond what is required to prevent leaks will reduce gasket service life. 30. After the 25 minute standby (burner off) as described in step 26, remove the low fire hold if applicable and allow the burner to sequence to high fire. Check fuel input rate and make sure it is below• the hoiler name- plate (not the burner) maximum input rating. Adjust the burner air damper to meet the burner manufactur- ers recommendation for excess air (or 02) at high fire. Make sure the boiler draft stays in the green range at high fire: If not, adjust the number of washer weights on the barometric damper or recalibrate auto draft fan system (if supplied) until it is. If flue gas recircula- tion is installed, make sure the FGR butterfly damper is open just enough to achieve the NOx requirement, but not so open that the flame becomes unstable and START - UP continued the burner rumbles. Excess rumbling indicates too much flue gas is being introduced into the air/fuel mix. It is important to check this when the firebox is both hot and cold to find a setting that satisfies both conditions. It is also important to remember that excess air (O,) will change with the density of air. At cooler air tempera- tures, there will be more air (and Oz) per cubic foot than at warmer temperatures. O,) trim sensors automatically adjust for this but are generally to costly for boilers below 300 horsepower. It is therefore advisable that when tuning a burner on a warm day, adjust the excess air (O,) on the low side and on a cold day adjust to the high side of the manufacturers recommended range. For modulating burners, make air/fuel ratio adjustments throughout the curve to maintain good combustion read- ings between previous established minimum and maxi- mum firing rates. 31. For hot water boilers, check the boiler pressure at the P&T gauge with the system pwnp on and when the boiler is at or near the system maximum operating temperature. Compare the pressure with the pressure noted on Page 11, step 18. If the expansion tank was correctly sized (and pressurized if bladder type) and working properly, then the pressure should have risen only slightly from when the system was cold. In some cases the tank will be sized to allow larger pressure differentials. If so, the differential Should be documented and made known to the start-up person and in all cases must be well below the boiler relief valve setting. The pump when operating at full RPM Should also have little or no effect on the pressure in the boiler. CAUTION Any deviation from this must be corrected at once. 32, 1 CAUTION For hot water boilers, check the return water temperature to the boiler and make sure that the return water temperature is at least 135" to 140" F. for natural gas and propane fired boilers. For #2 oil (diesel) and digester gas fired boilers, the return water temperatures should be sig- nificantly higher to avoid condensation in both the boiler and especially the stack. Check with the factory for recorn- mendations if in doubt. Failure to do so can lead to con- densing which is not covered by warranty. If indoor - out- Notes: door reset is used, make sure that it is programmed to avoid condensing return water temperatures to the boiler under all outside air reset conditions. 33. For water boilers in systems with fixed speed system pumps and P.I.D. temperature controls, auto tune the P.I.D. loop atter the system is up and operating normally. On systems with variable speed pumps, do not auto tune P.I.D. controls. For boilers without P.I.D. controls, adjust aquastat set points and differentials to minimize excessive burner cycling while still satisfying the system design temperature demands. 34. For steam boilers, make sure the feedwater system is working properly. If a chemical feed pwnp is used, be sure it is wired in series with the feedwater pump. CAUTION Chemicals fed directly into condensate return/ feedwater tanks have been known to damage feedwater pump seals. Chemical Treatment and blow -down proce- dure should be established and monitored by a water treatment specialist. Steam boilers operated �%ithout chemical treatment will not be covered by warranty against failure from scale or corrosion of the tubes or heat exchanger. 35. Check steps 6-8 on page 4. Make sure burner linkage assemblies or servo motor actuators run smoothly and don't bind throughout the tiring range. Make sure all linkages and servo motor fasteners are tight. Consider marking final ball joint locations and other air -fuel -FGR settings with tamper proof paint. 36. Secure all guards, covers etc. and reinstall insulated head - plate covers if supplied. 37. Be sure the owner/operator receives a copy of this O & M manual, the burner manual, cut sheets of all safety and oper- ating devices furnished with this boiler along with a copy of your start-up report. See next page for suggested start-up form. PG 13 STARTUP BOILER / BURNER START UP INFORMATION & TEST DATA (page , of 2) The following inforniation shall be recorded for each boiler/burner start up: Job Name .lob Location— Rite Model & Serial # Burner Mfg Make/Model & Job or Serial # Burner MFG. Job or S.O.# Start Up Date Start Up Contractors Name Phone Name of Technician Performing Start Up Type of Gas Natural J LP .J Other Fuel Oil Grade No Gas Firing Gas Pressure at Train Inlet Flame Signal Readings Vent Connector Draft Gauge Burner in Off Position " W.C. Pilot Low Fire Low Fire High Fire Gas Pressure at Train Inlet High Fire Low Fire Net Stack Temperature High Fire O, & CO, (at vent connector, less ambient) Low Fire Low Fire Gas Pressure at Firing Head High Fire High Fire Low Fire High Fire CO Combustion Efficiency Low Fire Low Fire Gas PreS5Ure at Pilot Test Tee High Fire High Fire 0 Input Rate BTU/HR NOx Measured (Corrected to 30/, O,_) Power Supply Low Fire Low Fire Volts—Ph—Hz High Fire High Fire Control Circuit Volts Blower Motor amps at high fire Over Fire Draft (Combustion Chamber) Low Gas Pressure Switch Low Fire Setpoint " W.C. High Fire High Gas Pressure Switch Setpoint " l'<'.C. Oil Firing I ligh Fire Vacuum Reading at Oil Pump Inlet " H.G Gas Pressure at Pilot -Crain Inlet (if applicable) Gas Pressure at Pilot Test Tee (if applicable) Oil Nozzle Supply Pressure Low Fire High Fire Oil Nozzle Bypass Pressure Low Fire High Fire Power Supply Volts—Ph—Hz— Control olts Ph Hz— Control Circuit Volts Blower Motor amps at high fire Remote Oil Pump Motor Amps at High Fire Flame Signal Reading Pilot (if applicable) Low Fire High Fire GPH Firing Rate Low Fire High Fire O, & COz Low Fire High Fire Bachrach Scale Smoke Number Low Fire High Fire Low oil pressure switch (PSI) Settings: cut in cut out Over Fire Draft (Combustion Chamber) Low Fire High Fire Vent Connector Draft Gauge Low Fire High Fire Net Stack Temperature (at vent connector, less ambient) Low Fire I ligh Fire Combustion Efficiency Low Fire 0 High Fire 0 NOx Measured (Corrected to 3% O,) Low Fire High Fire High oil pressure switch (PSI) Settings: cut in cut out Control Settings General Operating control cut out setting Operating control cut in setting Limit control setpoint STAR"1' UP FORM PG 14 BOILER / BURNER START UP INFORMATION & TEST DATA (page2of2) Operation Checklist Checked for Proper Operation of: l No N/A (N/A Not Applicable) Yes No N/A Low water cut off ( ) ( ) Barometric damper ( ) ( ) ( ) High Limit ( ) ( ) Boiler room combustion air and ventilation ( ) ( ) ( ) Operator control ( ) ( ) provisions correct Modulation or high -low control ( ) ( ) Oil tank vent system checked ( ) ( ) ( ) Flame safeguard control ignition failure ( ) ( ) All oil lines checked for leaks ( ) ( ) ( ) Flame safeguard control main flame failure ( ) ( ) All gas lines checked for leaks ( ) ( ) ( ) Burner air flow switch ( ) ( ) Gas lines and controls properly vented ( ) ( ) ( ) Induced draft fan controls ( ) ( ) ( ) Expansion tank ( ) ( ) ( ) Over fire draft controls ( ) ( ) ( ) Relief valve ( ) ( ) Fresh air damper end switch ( ) ( ) ( ) BAS, EMS or DDC system integration ( ) ( ) ( ) Feed water system ( ) ( ) Other system components (specify) ( ) ( ) Notes: Starting (cold) water boiler pressure Water boiler pressure at operating temperature Notified of the following system deficienc PG 15 sTARTAT FORM SEQUENCE OF OPERATION: The following is intended to provide a general overview as to how most power burners work. Given the variety of manufacturers and changing technologies, always refer to the burner O & M manual specific to the job for more complete and accurate sequence of operation than the following generic outline below: When there is a call for heat, the burner fan motor will come on and initiate approximately 4 combustion chamber air changes during what is called prepurge. The purpose of this is to force any unburned fuel in the combustion chamber out of the stack prior to pilot ignition if fuel valves are not tightly closing off when the boiler is in standby. Except for on-off fired boilers, following prepurge the burner will modulate to a low fire position prior to light -off. A pilot trial for ignition will then occur during which a pilot flame of sufficient strength must be established before main fuel valves are energized. On some #2 oil fired burners, direct spark ignition of the main fuel may occur in lieu of a gas pilot. If the pilot signal is too weak, the burner control will lock out on pilot flame failure. Otherwise the main fuel valves will be energized within 10 seconds of an established pilot. On boilers 2.5 million BTU's and less, the pilot valve may remain on (intermittent pilot) during the main fuel on period. On boilers over 2.5 million BTUH, the pilot valve will be de -energized (interrupted) after the main flame establishing period (usually 10 seconds) in order that the scanner or flame rod "prove" main flame. Once main flame is established, the burner (except for on-off fired models) will respond to load demand and modu- late accordingly. When the low fire or operator setpoint is reached, the fuel valves will close and following a short post purge, the blower motor will turn off. This constitutes one full burner cycle. The boiler/burner is now in standby mode waitine for the next call for heat. OPERATION, MAINTENANCE AND SERVICE General Maintaining a boiler log and following the recommenda- tions in this section will help your boiler operate at peak efficiency and reduce service calls. It is impossible to cover all potential problems or questions when it comes to operation, maintenance and service. Detailed cut sheets of various components provided with your boiler and burner O & M Manuals should be referred to when necessary. Retubing and refractory replacement instruc- tional videos are available on line at invu'.riteboileys. com. Unless you are a skilled technician, we highly rec- ommend you call one when you spot a problem rather than attempt to repair it yourself. Above all else, use common sense. The combustion chamber and insulation should last many years provided the boiler has: a) Operated with return water temperatures above 135'F SEQUENCE OF OPERATION/ PG 16 OPERAI'ION, MAINTENANCE AND SERVICE b) not been overfircd C) operated with ample draft (minitmttn -.01" W.C. in combustion chamber) d) Not beers sttbjectecl to negative room conditions. 3. Small cracks in the burner door refractory are considered normal. Check the condition of the ceramic fiber com- bustion chamber panels once a year. Pack 2600° F. rated fiber into any voids or areas where the fiber has shrunk or is no longer tight. If exterior boiler jacket shows signs of heat discoloration, check firebox pressure at high fire for positive pressure and check input and draft. Turn the burner off and after cool down period, access the inside of the combustion chamber. Check for soot in the tube bundle and/or gaps in the ceramic fiber panels that cor- respond to hot spots on the jacket. Gas train components are maintenance-fi-ee. Two or three times a year check all ball joint linkages on the burner for tightness. Check fan wheel for excessive vibration or blade loading, especially in dirty air environ- ments. The flame scanner glass should be wiped clean from time to time. Oil filters will need to be cleaned or changed if supply pressure to the pump begins to decline. Most unscheduled shutdowns can be traced by referring to the burner wiring diagram. On most burners a keyboard display module can be plugged into the flame safeguard control to provide a fault history. If the boiler is off due to an open limit switch, remove the cover from each limit beginning with the first limit shown on the diagram and check with a voltmeter until you Find the one that is locked out (open). After correcting the problem, manually reset the switch or control. DANGER Electrical work should be carried out by qualified technicians only. 6. If you notice flue gas temperatures going up over time, it is usually an indication that the tubes need cleaning. It is neither difficult nor expensive to waterside clean a Rite Boiler and doesn't require chemicals. You will need a couple of headplate gaskets and one or two heavy duty tube brushes which can be purchased from your Rite Representative. You will need to remove the front and rear headplates, or simply swing them open if they are hinged from the factory to attain complete waterside access. Most boilers can be cleaned and put back into operation in half a day. See steps 1-4 on the nest page. 7. The following efficiency loss due to scale in tubes applies to all boilers: SCALE, THICKNESS (IN INCHES) EFFICIENCY LOSS 1 '64" 4'Y, 1732" 8% l; 16" 12% 118" 18% 3! 16" 27% It pays to have a clean boiler. It pays to have a boiler that's easily cleaned! Waterside Tube Cleaning Procedure For Rite Boilers with Standard Pilley Brush* STEP 1 Remove (or swing open if hinged) both headplates. Install temporary splash/mud shields as shown. STEP 2 Use a standard hose with a gun type nozzle that will deliver a sharp stream of water. Begin by rinsing out all the tubes starting from the top and working down. FRONT � Figure 7 STEP 3 Brush out the top row of tubes, making two full passes per tube. Because mud or scale will load up the brush, dip the brush into a bucket of water after each pass. Tube brush has 1/4" female pipe thread connection. Mount onto a 1/4" pipe or 1/2" pipe using a bell reducer and 1/4" NPT nipple. The pipe handle should be approximately as long as the boiler. Where space between the boiler and an obstruction does not permit the use of a single length of pipe, use shorter threaded and coupled lengths that you can join together and take apart. STEP 4 Thoroughly rinse the top row of tubes out after brushing. Repeat this process one row at a time, top to bottom, until all tubes are clean. To Elevated Expansion Tank (Valve Off) Temporar Supply (Valve Off) Splash Shield *For more aggressive tube cleaning solutions, see our video showing our electrically operated tube cleaning machine that is available for rent. Optional Bottom Water Return Location (Water boilers Only) Figure 6 Water _� FRoryr Figure 8 U Figure 9 PG 17 OPERATION, MAINTENANCE AND SERVICE Steam Boilers Slow Steam Evaporation Test Procedure pipe cross on top of the rear header drum) senses a low Auto LWCO water condition. This should cause the burner to shut off. '�- probe housing Temporarily jamper the automatic low water cat-nff common and normally open terminals to bring the burner back on. Auto LWCO probe level - Manual reset LWCO probe 8. CAUTION On steam boilers it is necessary to check the feedwater and low water cut off devices once a month by performing a slow steam evaporation test: With the boiler under load and the water level between the top and middle probes on the water column, shut off the electrical disconnect(s) to the boiler fcccl pumP(s). Open the electrical panel marked "Boiler Feed Pump Controls and Low Water Cut -Offs" and look for a red L.E.D. light (illumi- nated) on the top P.C. Board and two red L.E.D. lights (right hand illuninated, left hand not illumi- nated) on the lower P.C. Board. Top P C. Board Automatic low water cut-off Lower PC Board Pump start and manual reset low water cut-off Pump contactor d L E D light L.E.D. lights 8.1 The following should happen as the water slowly drops in the gauge glass: Approximately 5 seconds after the water drops below the level of the middle probe, the left hand light on the lower P.C. Board should illuminate and the bottom relay (labeled "pump contactor") should Pull in. To verify, momentarily restore pump disconnect to the "on" position and make sine the pump starts, then turn the pump disconnect off again. High water level probe fitting (if used) 1/2" Overflow fitting (to steam trap. if used) __--Pump off probe —Pump on probe Tubular gauge glass 8.2 When the water drops to a level approximately I" to 1 1/2" above the bottom of the gauge glass, the top P.C. board's light should go out. This indicates the primary low water cut-off (probe is located in OPERA'T'ION, MAINTENANCE AND SERVICE PG 18 8.3 The water level should continue to drop slowly as the burner continues to fire. Atter the water level reaches the bottom of the glass and falls below the bottom probe on the water column, the lower P.C. Board's right hand light should go out and the burner should shut off. Note that there are time delays of a few seconds built into both P.C. Boards so the switching action occurs shortly after the water crosses a probe in either direction. I CAUTIONJ Do not allow the boiler to keep.firhtg if the water disappears from the gaage glass far longer that 15 seconds. Ttu'n the power switch nff. 8.4 If everything works correctly as described, above, reprove the temporar1, jamper on the automatic low mater cert qff and turn boiler feed pump disconnect(s) back on. When the water level rises above the bottom probe on the water column, reset the low water cut-off push button switch. The middle P.C. Board's right hand light should come on. As the water level approaches the middle probe, the top P.C. Board's light should automatically come on. At this point both low water cut-offs have "remade" and the boiler should attempt a PTFI and light - off with the feed pump continuing to run. When the water level reaches the top probe, the middle P.C. Board's left hand light and the feed PUMP should both turn off. This completes the slow steam evaporation test for probe style low water cut-off and pump start controls. 8.5 Failure of any of the relays or controls to operate as described above requires immediate attention: Turn burner switch off and let boiler pressure drop to zero. DANGER Only when you are certain there is no pressure in the boiler, remove the three column probes (and the vertical probe in the rear header drum by remov- ing the entire probe housing from the pipe cross if the test proved it defective). Clean probes thoroughly using a shop cloth, wire brush or wire wheel. If there is a build- up of scale or mud on the probes, contact your water treatment company to review the water treatment pro- gram. The solution may be as simple as blowing down the steam column more often. For process steam boilers, blow -down the column once every eight hours. For low pressure steam heating boilers, blow -down the column once a day. Reinstall probes and corresponding "top", "middle" and "bottom" probe wires labeled accordingly. Check ground wires and all other wiring to the P.C. Boards for loose connections, shorts or other defects. Repeat the test. If problems persist, contact the factory. Steam Boilers continued 0 10. On steam boilers, the gauge glass, trycock(s) and water column must be clean and in good working order at all times. Steam or water seepage around the gauge glass packing nuts will cause the glass to erode and weaken. Extra gauge glass, brass friction washers and packing gaskets should be kept on hand. Your Rite Representative can supply these items to ensure proper gauge glass length and pressure rating. If tubular gauge glass break- age or erosion becomes an issue, consider replacing with a Rite reflex type water gage. 11. When replacing gauge glass, it is imperative that the water gauge valves be in near perfect alignment to prevent stress on the glass. DANGER Never attempt to replace the gauge glass on a boiler that is operating under pressure unless qualified to do so. Always wear safety glasses when working around gauge glass. 12. The trycock is a back up valve for verifying water level in the boiler and should be used only when the gauge glass is temporarily inoperable or if the boiler operator suspects that the water level in the gauge glass might not be reading true. Constant leakage out the trycock can eventually cause it to plug up with scale and become inoperable. 13. CAUTION The equalizing piping that connects the steam column to the boiler must be kept free of mud and Sludge. To access and clean, remove pipe plugs in the crosses that connect the column to the boiler and rod out with a stiff wire bottle brush. The bottom equalizing pipe is generally the most susceptible to mud accumulation. The steam column itself should be checked at least once a year. Mud or sludge in the steam column is an indica- tion that the column is not being blown down often enough and/or the water softener is not working properly. 14. On steam boilers, sometimes the feed pump is on but the water level won't rise in the sight glass until the s t e a m pressure drops. If this happens, chances are the check valve(s) between the boiler and the pump have failed. For this reason Rite recommends two spring loaded check valves piped in series in the boiler feed line (See page 48). 15. A steam boiler that is shut off and cooling down will eventually draw a vacuum. Usually this vacuum is broken by air seeping in through the gauge glass gasket. If not, the vacuum can be strong enough to pull water out of the condensate return tank and flood the boiler. A full gauge glass in the morning is an indication of this. If this causes more water carry-over than the steam main's trap can handle on restart, here are a few suggestions: 1. Install a larger capacity float & thermostatic trap at the end of the steam main. 2. Leave boiler "on" during off hours with the steam supply valve closed and operating pressuretroll in night set -back mode. 3. A vacuum breaker of the proper rating can be installed by adding a tee in the boiler's control piping, but be aware that this will intro- duce the same unwanted oxygen into the boiler as the seepage through the gauge glass gasket and may require a modification to the chemical treatment program. 16. Check steam traps regularly. Steam loss through traps that are stuck open can waste vast amounts of steam to atmosphere without notice. If the end of the vent pipe from the condensate return tank to outdoors is blowing a continuous plume of steam, chances are one or more traps have failed open. Water Boilers For closed hot water heating systems the most important thing to avoid is losing system water. At least once a month check the discharge piping from the boiler relief valve(s) and the drain valve for any sign of leaks as well as around the boiler head gaskets, pump seal(s), valve packing(s), piping, etc. A water meter installed in the fresh water make-up line is a very cheap and simple way to tell whether or not the heating loop is losing (and therefore making -up) water. 2. On hot water heating boilers, verify the following when the system is at or near operating temperature: The boiler pres- sure gauge should read well below the boiler's relief valve set pressure. The boiler supply temperature gauge should not read below 155° F for systems operating with delta T's of 20° F or less. Return water temperature should be 135" to 140° F or above to avoid the possibility of condensing. 3. On hot water heating boilers check the low water cut-off operation once a month. If you have a float type low water cut-off installed with Test 'N' Check valves, open the drain valve beneath it while the burner is firing. The burner should turn off. Close the drain valve and rnanu- ally reset the low water cut-off if required. The burner should attempt to relight. If you have a probe type low water cut-off, hold in the "test" button for about six seconds while the boiler is firing. The burner should go off during this time and not attempt to relight until you push the reset button. PG 19 OPERATION, MAINTENANCE AND SERVICE DAILY MAINTENANCE SCHEDULE: 1. Check the water level in the boiler gauge glass. Steam RESPONSE Operator Immediate if the water level is unusually low or not visible. On 2. Blow -down boiler and steam column per water treatment Steam Operator Immediate if any of the water On program recommendations. Confirm that both low water level controls fail to respond during cut-offs and the pump control function properly. properly or if the blow -down low 9. valves or piping seem demand. Operator restricted or blocked. On 3. Check condensate return/feedwater tank for: (1) water Steam Operator Immediate if no water in tank 6. Confirm that boiler is drafting properly by checking for a level (2) overflow (3) water make-up valve operation from or float valve rod linkage hangs Immediate if there is any high level (make-up off tight) to low level (make-up keeping up when water level in tank Water up with pump demand) (4) feedwater temperature (5) drops. Otherwise A.S.A.P. High constant steam plume coming out of the vent oioe. Check boiler draft gauge. Steam 4. Check chemical feed and softener systems. Steam Operator A.S.A.P, if not working. On 5. Visually check main flame through the firebox view Steam Operator Notify qualified service company On port at the rear of the boiler. Water 9. if flame is too rich (all yellow), too Steam Operator Immediate or A.S.A.P. if pressure On lean or unstable (pulsating) Immediate or A.S.A.P. if actual 6. Confirm that boiler is drafting properly by checking for a Steam Operator Immediate if there is any On slight negative draft entering the front firebox view port Water indication of back pressure High cover (A small amount of smoke is one way to do this). Check boiler draft gauge. Steam in the firebox. Fire 7. Check for residual flame in the firebox after the burner Steam Operator Immediate if gas valves At the end has cycled off. Water 11. fail to close. of a burner Operator A.S.A.P. if baseline stack temp- On "on" cvcle 8. Check for simmering or discharging relief valves. Steam Operator Immediate if boiler pressure is On or bellows to force the float ball down (simulating low off or if the float fails to bounce Water water) and then releasing in order to confirm that the float within 10% of relief valve setting. 9. Check boiler pressure gauge. Steam Operator Immediate or A.S.A.P. if pressure On 22. Check one complete sequence of operation Steam Operator Immediate or A.S.A.P. if actual Water (see page 16). Water is above normal or closer than there is a written description. call for 10-15% of relief valve set pressure heat. 10. Check boiler draft gauge. Steam Operator A.S.A.P. if the draft reading On Water is in the red zone. 11. Check boiler stack thermometer. Steam Operator A.S.A.P. if baseline stack temp- On Water erature goes up by 40' or more. 12. Check for water leakage: (1) under boiler (2) around Steam Operator Immediate or A.S.A.P. On boiler headplate gaskets (3) low water cut-off gaskets Water (4) pump seals (5) system piping. 13. Continue to eliminate entrained air from a new or Water Operator Manually vent air from high On or freshly filled system. points in the system. Off 14. Check boiler return water temperature. Water Operator Immediate if return is less On than 135° F. WEEKLY MAINTENANCE SCHEDULE: 15. Check make-up water meter and record the number Steam Operator Make sure your water treat- On or of gallons in water treatment log or boiler log. ment company receives a Off copy. Highlight any significant changes in water usage and investigate the cause. 16. Ditto Water Operator Immediate if you are making On or up water. Off 17. Check water level in elevated compression type Water Operator Immediate if gauge glass is On expansion tank. full of water. MONTHLY: TYPE OF BOILER BY WHOMBOILER SERVICE REOUIRED TYPE RESPONSE 18. Slow steam evaporation test (see pages 18 and 19) Steam -Operator Immediate if level controls (See •Boiler Tech fail to respond properly. page 18) 19. Probe low water cut-off test and reset check. Water Operator Immediate if control does On not respond to test and reset Low buttons Fire 20. Blow -down float low water cut-offs that are equipped Water Operator Immediate if low water cut-offs On with McDonnell Miller Test 'N' Check valves. do not shut the burner off. Low Fire 21. Check float low water cut-off that are not equipped with Water Operator Immediate if the low water cut On Test 'N' Check valves by externally manipulating linkages off does not shut the burner Low or bellows to force the float ball down (simulating low off or if the float fails to bounce Fire water) and then releasing in order to confirm that the float back up quickly (indicating and linkages respond freely. This can be accomplished that it is sticking to mud at on most McDonnell Miller low water cut-offs except for #64. the bottom of the float chamber). 22. Check one complete sequence of operation Steam Operator Immediate or A.S.A.P. if actual Start when (see page 16). Water sequence does not follow there is a written description. call for heat. OPERATION, MAINTENANCE AND SERVICE PG 20 AFTER THE FIRST THREE MONTHS OF OPERATION: 23. Internal waterside inspection to check for scale, Steam -Operator Immediate or A.S.A.P. Off corrosion, and electrolysis, the latter sometimes -Boiler Tech depending on condition of indicated by reddish rust primer looking steel. -Water Treatment tubes and header boxes. Company Water" Reoresentative 24. Open the burner door if it is hinged, or the combustion Steam -Operator Immediate or A.S.A.P. if: Off chamber access panel on side of boiler if it's not. Water -Boiler Tech (1) Rust or water marks Locked Inspect bottom row of tubes (fireside) and slide indicate chronic condensing Out/ yardstick back and forth diagonally up between the problems (2) Ceramic fiber or Tagged tubes to check for soot. Inspect entire combustion refractory deterioration indicates Out chamber, including floor brick. for gaps, voids or overheating due to draft or If soot is found. deterioration of the ceramic fiber panels or cast overfiring problems (3) You contacts for wear and replace refractory. discover any soot in the tube as necessary. open the valve. Leave open about 5 seconds and then bundle (4) Any of the bottom Steam Operator tubes are leaking, sagging. or Off return tanks. Twice a year is recommended. have "blisters" or bulges. Boiler Tech 25. Open drip/dirt legs to all vent lines. Disconnect vent Steam -Operator Immediate if water or moisture Off lines at all diaphragm valves and switches as well as the Water -Boiler Tech is discovered. These lines main gas pressure regulator and NOVV if supplied. -Boiler Tech must be completely dry and 38. Lubricate (if necessary) and do amperage test on all Steam -Operator, open to ntmosohere. 26. Inspect stack internally for soot near the draft Steam -Operator Immediate or A.S.A.P. Off control and at the stack cap. Water -Boiler Tech If soot is found. ANNUAL: Immediate if valve fails to open or On contacts for wear and replace 27. Follow step 23-26 above. See above See above See above Off Locked Out/ Tagged Out 28. Inspect feedwater, blow -down and equalizing valves and Steam -Operator Clean or replace piping Off piping for sludge restrictions or obstructions. -Boiler Tech and valves as necessary. 29. Check all wye strainer screens. Steam Operator Clean or replace as necessary. Off Water 30. Check boiler water pH with sample pulled from boiler Steam -Operator Adjust with chemical Off bbefor draining for internal inspection. Water -Boiler Tech treatment as required to bring 38. Lubricate (if necessary) and do amperage test on all Steam -Operator, A.S.A.P. If full load amperage Off -Water Treatment into proper pH range. draw is higher than motor name- en off. Recheck draft when finished. Off -Electrician Company Boiler Tech Immediate if valve fails to open or On contacts for wear and replace Water Representative as necessary. open the valve. Leave open about 5 seconds and then 31. Flush out and clean blow -down tanks and condensate Steam Operator As required. Off return tanks. Twice a year is recommended. reseat tightly, open a few more times Boiler Tech 32. Open all float type low water cut-offs used on steam Steam -Operator Immediate if float bowls Off boilers and McDonnell Miller #64 or 150 s (m) low Water -Boiler Tech or float arm guides have water cut-off on water boilers. any mud or scale buildup. 33. Check for electrolysis due to stray electrical currents or Steam -Electrician See pages 7 and 34 On improper boiler -to -copper pipe connections. Water •Operator 34. Check high limit control operation. Steam Operator Immediate if lowering high On Water limit setting to pressure or low temperature reading in boiler fire does not cause burner to shutdown and high limit to lockout. 35. Check high limit control, operator control and Steam -Operator Immediate if the controls and On pressure/temperature gauge for nominal accuracy. Water -Boiler Tech pressure/temperature gauge are not within reasonable accuracy of each other. 36. Replace gauge glass and glass packing gaskets Steam -Operator Off on steam column. -Boiler Tech 37. Replace gauge glass and glass packing gaskets Water Operator Do only if expansion tank has Off on elevated compression type expansion tanks. gas train for proper operation. become waterlogged during -Boiler Tech open when boiler is firing. the year. 38. Lubricate (if necessary) and do amperage test on all Steam -Operator, A.S.A.P. If full load amperage Off pump and fan motors associated with boiler system. Water -Boiler Tech draw is higher than motor name- en off. Recheck draft when finished. Off -Electrician plate rating, check motor starter Boiler Tech Immediate if valve fails to open or On contacts for wear and replace Water as necessary. 39. If supplied, check normally open vent valve on boiler Steam -Operator Immediate if NOW stays Firing gas train for proper operation. Water -Boiler Tech open when boiler is firing. 40. Check that washer weights have remained in place on Steam Operator Replace weights if they have fall- On or the barometric damper. Water en off. Recheck draft when finished. Off 41. Relief valve test: With boiler pressure at 75% of relief Steam Boiler Tech Immediate if valve fails to open or On valve set pressure- use relief valve lever to manually Water if water or steam is not discharged open the valve. Leave open about 5 seconds and then under pressure. If valve fails to close again. Relief valve discharge piping reseat tightly, open a few more times must be piped to a safe point of discharge. Ear and to dislodge any foreign material on the eye protection is recommended for this test. valve seat. Replace valve if it does not reseat. 42. Check draft gauge calibration Steam Operator Temporarily remove the plastic On tubing to the draft gauage. If red * The 3 month internal inspection may be waived Water gauge oil does not return to "0", try for water boilers provided they are opened up after one year. Subsequent inspections are adjusting it with the zero set knob. discretionary but should not be more than 5 years apart. Add oil as needed. See page 3 Para 4 PG 21 OPERATION, NIAINTENANCE AND SERVICE Outdoor Boilers 1. Weatherproof boilers for outdoor installation come with sheet metal covers over the burner and gas train. Controls are covered or installed in Nema 3R or 4 panels and sealt- ite conduit is used. 2. A storm collar is provided around the vent connector. Sheet metal seams are caulked to prevent rain fi•om entering the jacket. The RTV caulking (Dow #732) Should be inspected once a year and repaired or replaced as necessary. 3. Barometric damper draft controls are not supplied with outdoor boilers because they do not work properly in windy conditions. 4. To maintain proper draft, gas fired boilers should use R to 10 feet of stack straight up from the top of the boiler the same diameter as the vent connector. For #2 oil fired boilers, the height should be increased to 13 to 15 feet and the use of an in-line condensate drain trap is recom- mended in the first stack section. 5. The stack must be guy wired to the boiler or adjacent construction and terminated with a rain cap. hn areas with moderate to strong winds, a breidert type cap - available from Rite - should be used. 6. If stack height must be increased beyond the heights in paragraph 4, it might be necessary to add a baffle across the vent connector to slow the draft down. When tiring, the overfire (firebox) pressure should be -.01" to -.03" water column. The measurement can be taken through the tapping located in the rear viewport pipe on boilers manufactured after June 2007. Draft measurement can also be taken at the vent connector. (below the stack baffle if installed) and the range should be -.03" to -.09" maximum w.c. when firing. OUTDOOR BOILERS PG 22 TROUBLESHOOTING DANGER TROUBLESHOOTING SHOULD BE CARRIED OUT BY QUALIFIED PERSONNEL ONLY HONEYWELL RM7800 SERIES SEEAPPROPRIATE FSG BULLETINFOR OTHER FLAVE SECTION I. FLAME SAFEGUARD CONTROLS S.AFEGt ARD CONTROLSANDMORE COMPLETE OPERATION'& TROUBLESHOOTI:N"GI.NFOR.IIITIO.\. 1. On FSG, the top light does not come on: 1. Circuit breaker or fuse to the boiler is off. 2. Boiler power switch is off. 2. FSG does not sequence to PTFI (Pilot Trial for Ignition). The second light down does not come on Honeywell FSG Run/Test switch (On hailers over 2500 MBH) 3. The top two lights come on but there is no ignition spark as seen through the boiler rear viewport. 1. One or more of the limit switches are not "made" (closed). Correct problem and then manually reset the switch(es). 2. The operator or low fire control is not calling for heat. 3. Burner control circuit fuse is blown. 4. Building Automation System is not calling for heat. 5. Burner fan proving switch not made. Check blower motor rotation, check fan wheel, check fan proving switch adjustment. 6. "End" or proving switches attached to the following devices may not be made: combustion air damper, induced draft fan, supply air fan, automatic stack damper. 1. Make sure primary side of ignition transformer is getting 120 VAC during PTFI. If not, check wiring to the primary side. If wiring is good, the Flame Safeguard is probably bad. 2. To test the ignition transformer, temporarily remove the high voltage wire from the output post. Install a piece of insulated 16 awg wire long enough to reach grounded bare metal. Strip a 1/4" off the end of the wire and holding the wire with insulated pliers, maintain a 1/4" gap between the end of the wire and the bare metal as shown on the next page. If a spark jumps when 120 VAC is applied to the primary side, the ignition transform- er is good. Continued PG 23 TROUBLESHOOTING 3. Honeywell "Pilot" light is on but there is no ignition spark for the pilot (continued from previous page): High voltage ignition wire connected to ignition electrode inside burner housing. 14' Crap Higf Voltagt Jl park ,/ , 4. During PTFI there is ignition spark but no pilot flame: TROUBLESHOOTING 3. High voltage ignition wire could be defective. To test temporarily replace with a piece of 12 or 14 gauge insulated wire, TFFN solid or stranded. The wire may have to be manually held onto the igni- tion electrodes point of connection. If spark occurs when 120 VAC is supplied to the primary side, replace defective ignition wire. 4. Locate ignition electrode. Check high voltage wire connection for tightness and continuity. Check ceramic insulator for defects. Replace insulator if cracked or broken. 5. Check ignition electrode spark gap distance per burner manufacturer's recommendations. The elec- trode will not spark if it is in direct contact with metal or too far away. 1. Make sure air has been bled from the gas line and pilot tubing for all new installations. 2. Make sure the manual pilot gas cock (1) is open. 3. Check the gas pressure to the pilot line at the 1/4" tee test port (2) and make sure it is within the range specified by the burner manufacturer. 4. During PTFI, check for gas pressure downstrearn of the pilot valve at a plugged tee port or by disconnecting the pilot tubing (3). If there is no gas flow: a) Check to see if the pilot valve (4) is receiving 120 VAC (if not, the FSG may be bad or the wiring from the FSG's pilot terminal sub base to the pilot valve may be faulty). b) The pilot valve may be defective c) The pilot regulator (5) vent port may be plugged which may prevent the regulator from opening. 5. Check the pilot tubing for kinks, breaks or internal obstruction. 6. Check the pilot burner orifice opening for debris blockage or reduced diameter due to corrosion. Do not enlarge the orifice opening beyond original size. PG 24 5. During PTFI there is a pilot flame but the third light down does not come on: 6. There is a pilot flame and the third light down is on but the fourth light is not on. The fourth light down comes on but the main flame does not come on. 1. Put the F.S.G. run -test switch in test position. 2. Using a multimeter (or the FSG's optional key- board display module) make sure the pilot flame signal strength is in the proper range. 3. If there is no signal, UV scanner (or flame rod) may not be sighting the flame. Scanner may be mis-wired. The amplifier, scanner or flame rod might be defective. 4. If the flame signal is too low, pilot gas pressure might be too low, the boiler draft might be too high or too much combustion air is affecting the pilot flame. 1. F.S.G. run -test position is in the test position. Move to run position. 2. F.S.G. chassis might be defective. 3. Install keyboard display module on F.S.G. to help troubleshoot. 1. Upstream or downstream manual gas train shut-ofT valves might be off. 2. Check that the electrically operated safety shut-ofY valves are opening, either visually in the case of' motorized valves or by listening for the click of the solenoid or diaphragm gas valves when they open. Gas pressure taps are also available on the upstream and downstream side of most gas valve bodies. 3. The main gas pressure regulator vent or vent line may be plugged, blocked or corroded shut, causing the regulator not to open. 4. The bleed vent port or vent line to diaphragm gas valve might be plugged, blocked or corroded shut and not allowing the valve to open PG 25 TROUBLESHOOTING 6. Intermittent flame reset of FSG: H O N' E W E L L S U B B A S E Poor electrical ground. Verify that a solid earth ground wire has been brought to the F.S.G.'s sub base earth grounding screw. 2. Wrong electrical polarity: Check that the 120 VAC supply hot leg goes to the burner switch and that the neutral leg (L2) has less than .5 VAC potential to earth ground. 3. Transient voltage problems with the main power supply. To verify, run a temporary ground wire from the pilot burner to the F.S.G. sub base earth grounding screw. 4. Power supply less than 102 VAC or greater than 132 VAC. 5. Ambient temperature at the F.S.G. is over 140 degrees F or less than -40 degrees F. 6. Pilot valve is sticking open after a burner firing cycle and creating a false flame signal during standby. Honeywell's "MAIN" and "ALARM" LED lights will be on. 7. Energy Management System's enable -disable relay is "Triac" type (i.e., voltage leaks through before relay contacts fully make). Replace with "ice cube" or similar definite purpose relay. 8. VFD (variable frequency drive) motors are operat- ing nearby. Install a power line "noise" filter (such as Corcom IOVSI or Schaffner FN 660-16-03) at the supply side of the boiler's power -on switch. TROUBLESHOOTING PG 26 Intermittent flame failure requiring manual reset of FSG (continued from previous page) Honeywell Chassis and Modules i6rienri: a �, Purge Amplifier Timing Card )RITE y 404 9. Fluttering draft proving switch. If an induced draft fan is used, be sure the draft proving switch is properly installed and calibrated so that the switch does not "flutter" on and off. / 10. Gas pressure "droop". Make sure the gas supply piping to the boiler is properly sized to prevent the gas pressure from decreasing below minimum supply requirements when the boiler and any other gas burning equipment connected to the same meter are on line. This can be checked by install- ing a gas pressure gauge of the proper range at the gas train's supply gas pressure test port and seeing if the pressure drops appreciably between static (burner not firing) and flow conditions. 11. Intermittent F.S.G. control component failure. The best way to check this is if there is a second boiler operating nearby with the exact same F.S.G. control. Swap the controls and see if the problem stays with the boiler or follows the control. If the problem follows the control, you may then want to swap the F.S.G.'s control modules to further pinpoint the defective component. If you do not have another F.S.G. to swap, check with a local authorized distributor to see if they can bench test the unit. 12. A poor main or pilot flame can lead to deteriora- tion of flame ionization and thus a weak flame signal. Typical causes of this are temporary negative boiler room pressure conditions or stack downdrafts. 13. Too high a draft can pull the flame away from the UV scanner or flame rod. Check draft gauge and draft control to assure that draft is not over —.1" w.c., especially on boilers with vertical stacks over 40 feet tall or operating with an induced draft fan. PG 27 TROUBLESHOOTING 6. Intermittent flame failure requiring manual reset of FSG (continued from previous page) SECTION II. MAIN FLAME 1. Main flame "pulsates": Washer Weights Barometric Damper 14. F.S.G. control sub base is defective. In some rare cases, there have been hidden defects in the F.S.G. sub base. If all else fails, the F.S.G. sub base should be changed out (see page 26). 15. The following F.S.G. plug-in diagnostic display module will provide flame signal read-out as well as other useful burner monitoring and troubleshooting information: Honeywell: S7800A1001 or S7800A1142. 16. Some Honeywell flame safeguards have a "run -test" switch that holds the sequence in the test position. This can be useful for checking flame signals and troubleshooting the burner at various stages of operation. 1. Too much draft. Check draft gauge on side of boiler. 2. Barometric damper- not installed. 3. Barometric damper is installed too far away from the boiler. Install damper in stack tee as close to the boiler as possible (see page 4, figure 4). 4. Barometric damper is installed in a Tee or collar that doesn't provide enough offset, causing the bottom of the damper gate to get caught in the stack's exhaust flow while operating. 5. Barometric damper gate is not opening up enough. Remove some washer weights. TROUBLESHOOTING PG 28 SECTION III. GAS VALVE AND BURNER OPERATION 1. Boiler cycles on/off too frequently: 1. On steam boilers, adjust the differential setpoint higher. 2. Diaphragm gas valve does not open when energized: 3. Solenoid gas valve does not open when energized: 2. On water boilers, replace aquastats with fixed differentials to adjustable type. 3. Check energy management system's remote start/stop relay. 4. Check sequence of operation (see pages 16) to make sure the burner has returned to low lire long before a call for heat has been satisfied. 1. Coil defective. Replace with new coil (part #116931) for all Honeywell V48A valves. 2. Bleed port is plugged, blocked or corroded shut. 3. Valve defective. Replace. 1. Coil defective. For Honeywell V4295A valves, replace with new coil (see chart below). Vahc Size (inch) TNpe Coil Part Number 120 Vac, 50/60 Hz 2 psi 5 psi 3/8, 1/2 N.C. BBA51302 BBA51302 3/4 N.C. BBA51302 BBA51314 N.C. BBA51302 BBA51309 1-1/4 N.C. BBA51303 BBA51310 1-1/2 N.C. BBA51301 BBA51310 2 N.C. BBA51304 BBA51311 2-1/2 N.C. BBA51305 N/A 3 N.C. BBA51306 N/A 3/4, 1 N.C. BBA51307 N/A 1-1/4 N.C. 1313A51308 N/A \2. Valve defective. Replace. PG 29 TROUBLESHOOTING 4. Motorized gas valve does not open when energized: Valve Body Only 5. Safety shut-off gas valves fail to close completely when de -energized: Valve Body Stem Valve Leal( Test (see Figure 10 on next page) This is a test for checking the closure tighmc„ of a gas safety shutoff valve. It should be performed by qualified personnel during the initial startup of a burner system, or whenever the valve or valve bonnet is replaced. It is recommended that this test also be included in the scheduled inspection and maintenance procedures. For a periodic inspection test, fellow steps 1-12 below and refer to figure 10 on page 31. 1. Shut the burner power switch off. 2. Close the downstream leak test cock "E" 3. Open manual gas shutoff cock "A" 4. Remove the plug from the petcock "F" and connect the test apparatus. 5. Submerse the 1/4" tubing vertically 1/2" into ajar of water. 6. Slowly open test petcock "F". 7. When the rate of bubbles coming through the water stabilizes, count the number of bubbles appearing during a ten second period. Each bubble appearing during a ten second period represents a flow rate of approximately .001 CFH (23.32 cc/hr). 8. If the leakage rate for the SSOV "B" does not exceed the allowable rate, close the test petcock "F" and rein- stall plug. 9. Temporary hot-wire SSOV "B" to the open position. 10. Use test petcock "G" to test SSOV "C" in the same manner. 11. If the leakage rate for SSOV "C" does not exceed the allowable rate, close the test petcock "G" and reinstall plug. 12. Rewire all valves and wiring to pre-test conditions and check the burner gas train operation for at least two complete firing sequence. TROUBLESHOOTING PG 30 1. Check actuator for leaking hydraulic oil fluid. 2. Remove actuator and snake sure valve body stem is not jammed and can be forced down against closing spring pressure. 3. Replace actuator or valve body as required. To Meet U.S. requirements, leakage tnatst not exceed the following values: V48A Pipe Size (in) Allowable Leakage (celllr NatGas) Number of Bubbles per 10sec (Nat Gas) 3/4" 332.5 8 1 " 377.5 9 1-1/4" & 1-1/2" 552.5 13 2" & 2-1/2" 812.5 20 V5055 Pipe Size (in) Allowable Leakage (cc/hl) Number of Bubbles per I11See (N it/ Gtm) 3/4, 1, 1-1/4, 1-1/2 573 14 2,2-1/2,3 940 24 4 1 1254 33 V4295 A Allowable Number of Bubbles Pipe Size Leakage per 10sec (111) (CC/hr) (Vat Gas) 3/8" & 1/2" 235 6 3/4" & 1" 241 6 1-1/4 & 1-1/2" 444 11 2" 532 1 14 2-1/2" 629 16 3 768 20 NOTE: For international leak test requirements, contact the office of the appropriate approval agency. Manifold Pressure Pilot Pilot Gas Gau_e Port Solenoid PresSnrC Valve Regulator To Burner To Pilot rSecondlary�OV hMain SSOV Main Gas Pressure Reun lator C, n Doxcnstream Lek Test � oek „ E I c,t Test I'ctcuck * Petcock a" Flexible Tubin %" Aluminum Or Copper fubin, NOTE x Test Tappings 11cry Be Y2" Min Located In Body OJ'SSOV Or Ia The Piping. Figure 10 .lar Of Water Cut At 45' Angle Manual Pilot Val%c Gas Supply Manual Gas Shutoff Vale A, SECTION IV. DRAFT OR HIGH STACK TEMPERATURE PG 31 TROUBLI S1100I IN(. 2. Too much draft: Gate Washer Weights 1. Excess washer weights on Barometric Damper keeps the gate from opening and lowering the draft through the boiler. 2 F `3 3. High stack temperature. Over 400" F net or 500" F gross - except high pressure steam or high temperature hot water boilers which will have higher stack temperatures due to higher fluid saturation temperatures. Stack is over 25' tall and with Barometric Damper wide open, the draft is still too high. Increase the damper size or add a second Barometric Damper in the stack. Induced draft fan (if used) R.P.M. too high. Reduce fan speed. 1. Excessive draft. 2. Boiler tubes require internal waterside cleaning. 3. Boiler tubes sooted (external). 4. Boiler overfiring. 5. Glycol in system (water boilers only) will result in higher operating stack temperatures than systems without glycol (see page 9). TROUBLESHOOTING PG 32 SECTION V. WATER LEAKS 1. Headplate gasket leak Typical headplate cap screw markings, ASME SA grade, and maximuin bolt torque values. Typical bolt torque for Rite Boilers will be less than the following values: 1. Make sure the boiler flange and headplate gasket mating surfaces are clean and not pitted or wire -drawn. 2. Use new authorized factory gaskets as supplied without additional sealant. 3/4"-10 N.C. Thread SA325-1 Maximum 160 foot pounds. 3/4"-10 N.C. Thread SA354BD-1 Section IV Boilers: Maximum 180 foot-pounds. Section I Boilers: Maxintuni 200 foot-pounds. PG 33 TROUBLESIIOOTINC 3. Use new or like new cap screw bolts with 5/8"-11 N.C. Thread undamaged threads, lubricated with anti -seize SA 307B rated for 1800° F. Maximum 50 foot pounds. 4. Make sure threaded thru-holes in header box flanges are not galled or damaged. To "chase" a- 5/8"-I1 N.C. Thread SA 325-1 threads, use 5/8"-11 or 3/4"-10 hand tap with H5 thread limits. Bolts in flnger } ground should go s. ound Maxinnun 100 foottig tight ht until the bolt heads engage the headplates. 5. After finger tightening all the bolts, tighten the 5/8"-11 N.C. Thread cap screws SNUGLY in an alternating pattern SA 354BD-1 starting at the centers (top, bottom, left and right) Maximum 100 foot pounds. and work toward the corners. Repeat this pattern a second time. The third time just start at one center bolt and go around the headplate in one 3/4"-10 N.C. Thread direction without alternating. All bolts should be o SA 307B uniformly snug when finished. Maximum 85 foot pounds. (JP 6. After bringing boiler up to operating pressure/ temperature, snug all bolts one more time. 3/4"-10 N.C. Thread SA325-1 Maximum 160 foot pounds. 3/4"-10 N.C. Thread SA354BD-1 Section IV Boilers: Maximum 180 foot-pounds. Section I Boilers: Maxintuni 200 foot-pounds. PG 33 TROUBLESIIOOTINC 2. One or more boiler tubes leak at the tubesheet(s): 3. One or more boiler tubes leak above the burner bed, usually from the bottom or second row. (External wastage from long term leakage is usually visible): 4. Water Boiler: one or more tubes leak from above the second row: Sectioned boiler tube showing underdeposit corrosion. (Enlarged for clarity). Boiler may have been dry -fired. Tubes that are sagging or warped must be replaced. If tubesheets are warped and cannot be re -straightened, the entire heat exchanger may have to be replaced. Identify and correct the cause of the dry -fire before putting the boiler back into service. Problem is usually a long term overheated area of the tube caused by a buildup of mud or lime deposits. Replacement of leaking tube(s) is required. Find cause of the water makeup before putting boiler back into service and make appro- priate repairs. 2. For steam boilers operating with water make-up, find out why the water treatment program - espe- cially the bottom blow -down, water softener and chemical treatment - has not been more successful at reducing scale. 3. Consider installing an automatic timed surface blow -down system to reduce scale. 1. The leak might be due to longterm overheating from internal scale but the higher- up in the tube bundle the less likely a tube burnout becomes. Check the boiler water pH before you drain the boiler. It should be at or near 8.5. If below 7, the water is acidic and is eating the steel. 2. Test for electrolysis due to stray voltage and correct as necessary (see page 7 paragraph 5). TRO uIII, r?srrooTrNG PG 34 4. Water Boiler: one or more tubes leak from above the second row (continued from previ- ous page): 5. Steam Boiler: One or more tubes leak from above the second row: 6. One or more tubes have "split" or ruptured during cold weather shutdown: 3. If copper piping was used on unv of the lines to the boiler, make sure dielectric flange kits (or unions) are installed and working to keep the copper (cathode) isolated fro►n the steel (anode). Note that a copper ground rod used to fix stray voltage electrolysis will not solve a galvanic electrolysis (dissimilar metals) problem even though galvanic electrolysis will also show up as AC rnillivoltage. The problem might be due to longterm overheating from scale (easily confirmed by visual evidence) but the higher up in the tube bundle the less likely a tube burnout becomes. Check the boiler water pH before draining the boiler. It should be between 10.5 and 11.5. If below 7, the water is acidic and corroding the steel. 2. Remove the leaking tube(s) and section the tube near the failure. If the tube that failed came from below the normal water line, it could be due to oxygen corrosion or carbonic acid. Oxygen corrosion will appear as pitting in the steel, while carbonic acid attack will appear as channeling or grooving. 3. If the tube failed above the water line, it is usually the result of oxygen corrosion. Reasons include: a) Not enough oxygen scavenger in the chemical treatment. b) Boiler is frequently shut down at night or over weekend - causing a vacuum as it cools and sucking in oxygen laden air through the gauge glass packing gaskets. c) Out -of service oxygen corrosion due to improper boiler lay-up (see page 40). PG 35 Indicates that water in boiler reached freezing temperature. To help prevent this from occurring again: a) Install an automatic stack vent damper in the stack. b) Maintain enough glycol in the system (hot water boilers only) to stay above the freeze point. c) Leave the boiler- and the system pump(s) on. TROUBLESHOOTING SECTION VI - Miscellaneous Water Boiler Problems 1. Water boiler "Knocks or Bangs" when firing: Automatic .— air vent Test cock Isolation valve Automatic Air Vent Air Scparalor = To S) stem Pump (s) E CORRECT HOOK UP ° Typical elevated compression expansion tank Tank drain Airetroll ~' Svstem connection from boiler--+gj` fitting (Pitch piping up to prevent air traps) 1. The cause is almost always air in the system. When filling the system, or re -filling the boiler after an internal inspection, always manually vent air from high points and other natural air trap locations before turning the system pump on. 3. Make sure automatic air vents are installed at highpoints in the system and that they meet or exceed the M.A.W.P. of the boiler. 4. Where compression type expansion tanks are used and the boiler is turned off regularly during heat- ing season, the air in the tank can migrate down to the boiler when the water cools. To fix this, either leave the boiler on or replace the tank with a larg- er one (either compression or bladder) that has more acceptance volume. Sizing a new tank will require an engineering review. Never mix compression tanks and bladder/ diaphragm tanks in the same system. 6. System pressure may be to low. If the operating temperature is above the boiling point, make sure the boiler pressure safely exceeds the equivalent steam pressure at that temperature to avoid flashing to steam. 2. Boiler pressure goes up higher than normal. 1. If the system pressure rises when the boiler is not firing there might be dirt under the seat of the -" pressure reducing make-up valve, allowing city '` water pressure to continue entering the boiler SECTION VII - Miscellaneous Steam Boiler Problems 1. Flooded gauge glass: Gauge G Packing 1. If this occurs only after the boiler has been turned off and cooled down, it's due to the boiler drawing a vacuum and pulling water out of the condensate return/feedwater tank. Adding a vacuum breaker on to the boiler external piping can solve this problem, but also creates another problem as well: by introducing air into the boiler, you are introducing oxygen into the boiler which will require more chemical treatment (especially oxygen scavengers) to compensate. As an alterna- tive, consider leaving the boiler "on" in a night or weekend "set back" mode (1-2 psi) with the boiler \\ Pump "OFF" Probe stop valve closed. Pump "ON" Probe 2. If flooded glass occurs when the boiler is Manual Reset Low operating, see if the boiler feed pump is running. Water Cut -Off Probe 3. If the feed pump system is designed to run continuously and multiple boilers are fed by individual electrically operated valves, see if the valves are energized open. In either case, if there is a call for water when there shouldn't gh Water Alarm be, you will have to troubleshoot the feed pump obe Tapping circuit until you find the problem. If solenoid feed Overflow Trap valves are used, there might be foreign material Connection under the seat preventing a tight shut-off. 4. If two or more boilers are piped in battery, make sure that the swing check valve (low pressure steam only) is closing tightly to prevent steam in the main header from condensing back into the boilers that are off line. On high pressure steam boilers piped in battery, the same thing can occur through the spring loaded check valves or the stop/check valves from each boiler's steam supply. On low pressure steam boilers piped in battery, it might be just as effective to install a steam trap just above the level in the boiler where the feed pump normally cuts off in lieu of install- ing a large swing check valve. See page 48 for recommended steam boiler battery piping. PG 37 TROUBLESHOOTING 2. Steam boiler off on low water: 1. Follow steps in slow steam evaporation test (see page 18). 2. If water level in boiler rapidly drops when feed water pump comes on, the gpm rate might be too high, the feedwater temperature too low or a both. See page 6 for recommended feed rates. Ideal feedwater temperature is 180° to 190" F. 3. "Slow" feedwater pump. Water level in gauge l . Check valve(s) in feed water line have failed and glass starts to rise only after pressure in boiler boiler water has reached pump volute where it's drops: flashing to steam. Replace or repair check valves (see page 48 for recommended check valve type and location). 4. Feedwater pump sluggish under most operating conditions: Overflow ' Port 2. Check feed pump discharge pressure with a gauge and make sure it is above boiler operating pressure. If not, on Burks pumps only, try adjusting impeller clearance. 3. Feedwater tank temperatures over 200° F may be causing steam vapor lock in pump volute. Lower feedwater temperature to 180° - 190° F. Make -Up water level ® adjustment valve 4 Wye strainer Triplex Feedwater System shown TROUBLESHOOTING PG 38 1. Feed pump wye strainer screen is clogged. 2. Feedwater inlet port at the boiler is partially blocked by scale or sludge. 3. Feedwater pumps "vortexing" due to low Net Suction Positive Head (NSPH). Raise make-up water level in tank before it reaches the 1" overflow port. 5. Water carryover ("wet steam"): 5. Not enough steam: Reducing the steam stop valve size and associated piping from the steam outlet nozzle can raise steam exit velocities out of the boiler and cause water lift. The exception to this is on larger high pressure steam boilers where stop/check valves are almost always sized smaller than the boiler outlet nozzle. 2. Instantaneous high steam demand. Correct by using slower opening valves such as motorized ball type in lieu of solenoid snap -acting type valves to feed steam equipment. 3. Boiler water T.D.S. levels above 2600 ppm will promote water carry-over. Lower T.D.S. level. 4. Make sure the steam main is properly pitched and trapped at the end. Make sure the risers li-om the steam main come off at or near the top of the pipe. 1. Boiler not sequencing to high fire (see page 16). 2. One or more steam traps have failed open, causing steam to continually blow by the traps. A steady plume of steam coming out of the condensate return tank vent line is a telltale sign of this, normal trap operation will be indicated by wisps of steam corning out the vent as various traps open intermittently. 3. Boiler is undersized for the load. Fix this problem by purchasing another Rite Boiler. PG 39 TROUBLESHOOTING Removing Boilers From Service (Lay. -up) I here are two types of lay-ups: short term and long term. A short term lay-up could be considered anywhere from a few weeks up to the 3 to 6 month warm season that comfort heating boilers are off-line. A long term lay-up could be considered any time period longer that 6 months. The two maingoals of short and long term lay-ups is to prevent corrosion (oxygen or acidic) from attacking the boilers waterside steel surfaces and to prevent freeze -ups if the boiler is layed-up wet (full of water). 2. A water boiler wet lay-up is generally recommended for short term removal from service for two reasons: the boiler can be brought back on-line relatively quickly and it is also less labor intensive than a "dry" (no water in the boiler) lay-up. If the boiler to be layed-up wet in potentially fi-eez- ing weather, add glycol to the boiler and system in concentrations recommended on page 9, or consider lay- ing the boiler up dry instead. To combat corrosion in a wet lay-up, it is common to add a blend of oxygen scavenging and corrosion inhibiting chemicals to the boiler and system, but it is highly recommended that you do so under the guidance of your water treatment specialist. 3. While wet lay-ups of water boilers are fairly straight forward because the boiler and system are full of water and all the air has been vented out of the system, steam boilers are another matter. Steam boilers normally operate with a water line approximately 2/3 full. Steam boilers must not be layed-up in this manner because the air in the upper portion of the boiler will attack the exposed steel above the water line. Steam boilers must therefore be completely flooded up to the steam outlet's stop valve. The water used to flood the boiler should be softened and chemically treated. Returned condensate from the system is ideal for this purpose. The boiler Should also be kept under slight pressure (3 to 5 p.s.i.) to REMOVAL. FROM SERVICE (LAYUP) PG 40 prevent air (oxygen) from entering the boiler. Again, it is Prudent to follow recommendations from your water treatment specialist when laying up a steam boiler wet. Their recommendations may include weekly testing of the water for maintaining pH levels above 8 and sulfite (oxygen scavenging) residual. Test results should be a minimum of 20 ppm sodium sulfite (as S03) and 400 ppm phenolphthalein alkalinity (as CaCO3). In some cases they may recommend nitrogen blankets for your particular installation. 4. In a dry lay-up, you must be sure that the water is not only drained from the boiler, but from all external boiler piping as well. This includes low water cut-off float bowls and the anti -siphon line to the steam boiler pressuretrolls. After draining all the water out of the boiler with the water temperature between 120-135°F, remove the headplates. Next, the boiler tubes should be thoroughly brushed clean to remove any mud or sludge that could promote underdeposit corrosion (see page 17 and the bottom of page 34). Thoroughly dry all waterside surfaces using a warm air fan, towels, etc. Place quick lime (not hydrated) or commercial grade silica gel on elevated non-metallic trays inside each header box. If you are in an area subject to warm humid air, reinstall the headplates. Consult your desiccant supplier or water treatment company regarding the best type and amount of desiccant to use for your area. Generally, 5 lbs. of quick time or 8 lbs. of silica gel should be used for every 30 BHP. Open the headplates up every 1-2 weeks to check results. In some cases, nitrogen blankets are used in dry lay-ups but always exercise caution when working nitrogen in confined spaces as pure nitrogen does not support life. PG 41 GLOSSARY ABMA American Boiler Manufacturers Association Air Handler A system consisting of heating and cooling coils with large fans blowing air across the coils for HGPS heating and cooling buildings. Aquastat A water temperature controller. ASME American Society of High Pressure Steam Mechanical Engineers BAS Building Automation System (same as EMS) BIIP Boiler Horsepower (I BHP = 33,500 BTUH Output) BT'UII British Thermal Unit per hour (input or output) CAD Combustion Air Damper Category 1 Vent stack not pressurized and Appliance non -condensing. Category 2 Vent stack not pressurized and Appliance condensing. Category 3 Vent stack pressurized and Appliance non -condensing. Category 4 Vent stack pressurized and condensing. Appliance CSD -1 Controls and safety devices rules for boilers per AMSE code. DDC Direct Digital Control Delta T Temperature difference between inlet or AT and outlet of a hot water boiler Differential The difference between a boiler operators cut-out pressure or temperature and restart pressure or temperature. Efficiency AFUE Annual Fuel Use Efficiency is the average fuel efficiency of a boiler over one year. Efficiency Combustion 100% of fuel burned less °/0 of heat loss out stack. Also called stack efficiency as determined by a stack analyzer. Efficiency Thermal 100°/o of fuel binned less %, of heat loss out stack plus 'Yo of heat radiation loss from boilerjacket. Also called true efficiency or fuel -to -water (or steam) efficiency. EMS Energy Management System (same as BAS) FGR Flue Gas Recirculation (as in piping or duct used to return flue gasses to the burner to lower NOx) FSG Flame Safeguard Control. Also called burner management system. FM Factory Mutual Insurance that recommends and approves various boiler controls and gas valves. HGPS High Gas Pressure Switch HTHW High Temperature Hot Water boilers built to Section I of ASME Code. High Pressure Steam A boiler designed for making steam Boiler over 15 psi. A Section I Steam Boiler Indirect Heating Heating surfaces in a boiler that do Surface not directly see visible flame. Also called convective heating surface. IRI Industrial Risk Insurers (formerly FIA). Now called GE GAP. Accepts CSD -1 requirements. LGPS Low gas pressure switch. Low Pressure Steam LWCO MANVP MBH or MBTU11 Motorized Gas Valve MR NB NBBI NOVV NOx PFEP P11 Steam pressure at or less than 15 psi. A Section IV Steam Boiler. Low Water Cut -Off: probe (conductance) or mechanical float type. Maximum Allowable Working Pressure (of boiler, stamped on ASME nameplate). 1000 BTU per hour input or output. A fluid powered or hydromotor SSOV consisting of an actuator and separate valve body. Manual Reset National Board: agency responsible for boilers and other pressure vessels in service. National Board of Boiler and Pressure Vessel Inspectors Normally Open Vent Valve - required on IRI gas trains between 2 motorized SSOV. Oxides of nitrogen in exhaust gasses usually expressed in ppm. Caused by fusion of oxygen and nitrogen molecules dining combustion process. A component of smog and acid rain. Pilot Flame Establishing Period The measure of the alkalinity or acidity of a liquid. PG 41 CLOSSARY GLOSSARY PID Proportion Integral Derivative - A SSOV Safety shut-off gas or oil valve that temperature or pressure control with is electically operated. the ability to anticipate load swings and modulate the burner so it cycles TDS Total Dissolved Solids in water on and off less frequently. Thermal Shock Metallurgical stresses inside a PPNI Parts Per Million boiler created by heating (expansion) and cooling Pressuretroll A steam pressure controller. (contraction). Also known as thermal stress cycling. PSI (G) Pounds Per Square Inch (Gauge pressure) Throttling Range The number of degrees (or pounds of pressure) below a modulation PTFI Pilot Trial For Ignition control setpoint that the control will Radiant Heating Boiler heating surfaces that are begin to modulate at. Surface exposed to visible flame. UL 726 Underwriters Laboratories code for Reheat System using hot water to raise the oil fired burners. temperature of dehumidified chilled UL 795 Underwriters Laboratories code for air up to human comfort level. boilers. Section I Boiler An ASME Code Boiler stamped for VAN' Variable Air Volume boxes for over 15 psi steam, or over 160 psi disseminating heat inside a building. or 250° F water. VAC Voltage Alternating Current L- Section 1N' Boiler An ASME Code Boiler stamped for a maximum 15 psi steam, or up to VDC Voltage Direct Current 160 psi and/or 250° F water. QVC Inches of Water Column pressure Short Cycling Burner fires and then turns off after 28" = 1 psi a short run time. WSHP Water Source Heat Pump Static Pressure The pressure inside a boiler caused by the height of the water in the piping above it. Every 2.3 feet = 1 psi. GLOSSARY PG 42 ■ c c To System Pump (s) -a --- Fresh Water Make-up LEGEND: G Water meter [34 Ball Valve lIJ Pressure reducing till Rite Hot Water Boilers Suggested Piping Diagram For Closed Hydronic Heating System Featuring Conventional 135° To 235° F Return Water Temperature r1 Thermometer u Threaded Pipe Cap Or Plug Union or Flange Reduced Principal (R.P.) Backflow Preventer Floor Drain Figure 11 GENERAL NOTE: Natural Gas Supply Automatic Air Vent Gas Rated Shutoff Valve To Floor Drain Drip Leg This system may be used with a ftctory installed boiler indoor/outdoor temperature reset control provided the control is programmed to never return less than 135° F to the boiler. RITE HOT WATER BOILERS SUGGESTED PIPING DIAGRAM FOR CLOSED LOOPED HYDRONIC HEATING SYSTEM FEATURING 3 -WAY VALVE FOR BOILER PROTECTION IMPORTANT THESE ARE CONCEPT DRAWINGS ONLY - NOT ENGINEERED DRAWINGS. SPACE LIMITATIONS PRECLUDE SHOWING VALVES, CONTROL SYSTEM DETAILS AND OTHER APPURTENANCES. PIPING CONFIGURATION FOR REFERENCE ONLY AND PUMPING SYSTEM SHALL BE DESIGNED FOR THE PROPER APPLICATION. AUTOMATIC AIR VENT FRESH WATER MAKE-UP BALL VALVE 7 STRAINER III A A I�I WATER LEVEL O CONTROL i BOILER RETURN ° WATER ISOLATION VALVE PRESSURE RELIEF VALVE BOILER DRAIN RSR AIR SEPARATOR T TRIPLE DUTY VALVE (IF REQUIRED) GENERAL NOTES: 1. THE 3 -WAY VALVE ACTUATOR SHOULD REMAIN IN FULL SYSTEM BYPASS POSITION UNTIL BOILER LOOP TEMPERATURE REACHES 1907. 2. AFTER THE 3 -WAY VALVE IS RELEASED TO PROVIDE THE SYSTEM HOT WATER, THE 3 -WAY VALVE SHALL MAINTAIN A MINIMUM HOT WATER RETURN TEMPERATURE TO THE BOILER OF 1357. 3. "CONDENSING" FLOW THROUGH A STANDBY BOILER CAN BE PREVENTED BY CLOSING EITHER THE SUPPLY OR RETURN VALVE (SEE ISOLATION VALVES SHOWN ON BOILER). OPTIONAL DIVERTING VALVE TO SYSTEM FROM SYSTEM LEGEND: 7 STRAINER III BUTTERFLY VALVE I�I BALL VALVE O WATER METER PRESSURE REDUCING FILL VALVE THERMOMETER PRESSURE GAUGE REDUCED PRINCIPLE (R.P.) BACKFLOW PREVENTER ® FLEXIBLE CONNECTOR FD VARIABLE FREQUENCY DRIVE Figure 12 n n cn 2 -WAY VALVE (TYPICAL) OPTIONAL VARIABLE FREQUENCY DRIVE F\ FD, CLOSELY L J SPACED T TEES MINIMUM 135"F RETURN (TYP.) BOILER #1 BOILER #2 Rite Hot Water Boilers Suggested Piping Examples for Closed Looped Hydronic Heating System Featuring Primary -Secondary Piping with 2 -way and/or 3 -way Control Valves IMPORTANT These Are Concept Drawings Only - Not Engineered Drawings. Space Limitations Preclude Showing Valves, Control System Details and Other Appurtenances. Piping Configuration for Reference Only and Pumping System Shall Be Designed for The Proper Application. \ CIRCULATOR FOR EACH BOILER LOOP SHOULD BE SIZED FOR FLOW THROUGH 3 -WAY BOILER AND PIPING. (WITHIN DASHED BOX) MIXING VALVE BOILER RETURN SENSOR SECONDARYLOOP 3 -WAY MIXING' VALVE ITYPICAL) I I 7 I I I I ---------- -----� -- FAN FAN COIL I TC I COIL END OF MIN 135'F (TYPICAL) LINE I R S I I I BOILER #1 L------------------------- TC MIN 1357 AIR SEPARATOR BOILER #2 MIN 135°F CLOSELY SPACED TEES CLOSELY SPACED TEES TCO) T%/ CLOSELY \> SPACED TEES BOILER #3 _ _r I I MIN 135°F BOILER #4 J LEGEND L ® PUMP ALTERNATE DIVERTING VALVE LOCATION METHOD FOR O BOILER SUPPLY BOILER PROTECTION ® BOILER RETURN (MINIMUM 135'F) TC 3 -WAY MIXING VALVE TO PROTECT BOILER FROM CONDENSING CLOSELY SPACED TEES = MAXIMUM DISTANCE BETWEEN TEE OUTLETS SHOULD NOT EXCEED 4X PIPE DIAMETER Figure 13 / CLOSELY %\? SPACED TEES SECONDARYLOOP SENSOR CONTROLLER OUTDOOR AIR SENSOR FOR RESET (IF USED) CIRCULATOR SIZED FOR ENTIRE SYSTEM EXCLUDING THE BOILER LOOPS AIR SEPARATOR 0 Rite Water Heating Boilers Heat Pump Package Suggested Piping For 60° To 90° F Water Source Heat Pump SystemsOnly To Heat Keep Tees Closely From I Icat Pump Loop Mininnum 4xd Spaced (Max. 4xd) Minimum 8xd Pump Loop Loop Straight To Minimize Straieht Pump pipe Common Pipe AP Pipc i 1 , � v � ---- C�onunon Pj,_ ®--------- j No Valve !-------------- t , Note that reduction in pipe ; diumeterfronr the nozzle 180° to 190° F ' ••V. outlet to p►nnp" E" is standard This arrangement is not intended for �� �� Aquastat (by others) "Q' , I] With 60 90 F use wheugh thful! iter is flow � � � � Midscalc Range through the holler lc required �\ (SPST, Break On Rise) LEGEND: ::U d = Internal Pipe Diameter ------ By Others All other piping shown is factory supply and hydrotestcd as part of Ritz's "Heat Pump Package Option" 4 or 8xd = Minimum straight run length of pipe multiplied by the internal diameter of the pipe (in inches). 0 a 0 0 SET-UP INSTRUCTIONS 0 0 1. Provide aquastat in heat pump loop piping where shown ^° ° o ° o to energize boiler and boiler loop pump "E" when heat is required. 0 2. Set up boiler aquastat to supply 180° to 190° F. d 3. Throttle butterfly valve "A" to approximately 80°/< closed. 4. Make additional fine tune adjustments of butterfly valves "A" and "B" ("B" will be mostly open) until water temperature at thermometer "D" holds between 140° and 150° F. Do not reset F valves even if'heat pump loop tcn,perature is reset. p 5. Mark position of handle on butterfly valve "A". To isolate \ O N a the boiler for summer cooling mode (or to service the boiler) simply close valves "A" and "C". To restore to heat mode. return "A" to marked position and open "C" fully. Figure 14 Rite Steam Boilers Suggested Piping for High Pressure Steam Boilers (150 psi) Featuring Blowdown & Safety Relief Valve Piping DANGER To SAFE Termination LA Schedule 80 Pipe & 300# Malleable Iron Forged Steel Fittings Figure 15 Full Size Vent Outdoor To SAFE Termination A.S.M.E. Blowdown Tank or Separator TO APPROVED FLOOR DRAIN Aftercooler Controls (For Separators or When Discharge to Sewer Is greater Than 135" F) Flashing Steam Sleeve Piping Roof Supply Probe Low Water Cutoff / 9" T. 0. E. I" Nipple Sleeve Piping Support Safety (NO Weight Allowed On Safety Valve) /Valve Drip Pan f Elbow o "High Water Overflow Trap Connection For 0 0 Boilers In Battery 0 0 0 0 \-.,e" u (On Steam Column) 0 Na Gi TO APPROVED a 0 0 200 WSP Rated A FLOOR DRAIN 0 Ball Valve 4 0 0 200 WSP Rated Quick Opening 1" Surface Blowdown Connection 0 Rear Bottom 0 0 0 Blowdown Valve 2" Front Header Drum0 0 Drain & Inspection Opening o 0 0 0 200 WSP Rated Slow u Opening Y-Blowdown Valve /Blowdown Sampling Valve LA Schedule 80 Pipe & 300# Malleable Iron Forged Steel Fittings Figure 15 Full Size Vent Outdoor To SAFE Termination A.S.M.E. Blowdown Tank or Separator TO APPROVED FLOOR DRAIN Aftercooler Controls (For Separators or When Discharge to Sewer Is greater Than 135" F) G) A 00 Rite Steam Boilers Suggested Piping For Low & High Pressure Steam Boilers Featuring Steam Supply, Condensate Return Tank & Feedwater Piping Install A I estcd At 200 VVSP Sluing Loaded Low Pressure hon 110d\ Check Vahe._Or Swing Chcck \ :ih c I [ere Or Install UT Trap OIT Install FST Trap Off Steam —� __-1 Steam Column High \Vater Column I IiLdl Water ovetilo" Overflow Connection Connection Class 25(1 :Angle - c Y -Pattern Slop Check valve � Class 125 Cla," 125 Class 2;(1 OS&Y '0o \\ SI' OS&)' OSSI' (or Rated Ball Valve Ball Or Cate V'ulvc 200 \V'SP �4valve Aaloe „� Or Smaller) Ball A'ulcc 5 PSI Low Pressure 15 PSI Low Pressure 150 PSI High Pressure 150 PSI High Pressure ISO PSI IInd Steam Boiler Steam Boilers Steam Boiler Steam Boilers In Battery For 2" Stearn Boilers In Battery Single Installation In Battery Installation Single Installation II And Smaller Steam Supply Valves For 2 1" And Larger Steam Supple ValceS Option #1 Option #2 Option #3 Option #4 Option #5 Bottom Blowdowr Metering P Wired In S With Feed LEGEND: Mi O Water meter 74 Ball valve QPressure gauge u Threaded pipe cap, plug or blind flange illi Union or flange See ^`I ��P h Steam Mait�L�own " per 10 n n — — Ontinnc tt In Direction Of Steatn Flow. WE&w hm�l Condensate Rettu-n --J' Vent To Outside Air Gap I lore Or R.P. Backflow Preventer Here oft Water — lake -up ( lass'50 OS&Y Valve 200 \1'SP Ball OrOate Vale Flow/Lift Requirements Limits Of Usc Of'I'his Valve To 11150 dirt P250 Ilcat User Equipment F&T Steam Trap g Loaded Checks enc Seats <15 psig) C'ondcn,atc in Seats X15 psig) Relnrn Tank (Surge Tank) Condensate Rettll'll Sampling Port Boiler Feed Pump r. 1 z n Rite Steam Boilers Suggested Piping For Low Pressure Steam Boilers (15 psi ) Featuring Blowdown & High Water Overflow Valve Piping DANCER To jaL Termination Flashim_ Sleeve Piping Sleeve Piping Support (No Weight Allowed On Safety Valves) LEGEND: I)< 150 WSP Rated Ball Valve u Threaded Pipe Cap Or Plug ----- Boiler Normal Water Line Schedule 80 Pipe & 300# Malleable Or Forged Steel Fittings 1111 Union or Flange A. Safety Relief Valve Drip Pan Glbw +" Surface Blowdown Connection Front He Ph. Roof fill � n is xl;_.i_ Figure 17 Overflow Trap Boilers In Battery Lu -nn) Bottom Blowdown � Blowdown Tank Blowdown Sampling Port T 0 cn 0 Reduced principle (R.f backflow preventer Soft Water Make-up LEGEND: Rite Steam Boilers Suggested Piping of 15 PSI Low Pressure Steam Boilers For One Pipe Systems, Wet Gravity Return, Hartford Loop, Operating at 2 PSI or less Heat Heat Heat User(s) User(s) Usens� To Floor Drain To Floor Drain — "A" Dimension should be minimum 28" Combination water feeder/low water cut-off 0 — Water meter — 150 WSP rated ball valve — 125 WSP rated OS&Y stop valve LJ — Threaded pipe cap or plug Union or flange F, 3 — Boiler pressure gauge Figure 18 T1 T Reduced principle (R.I backflow preventer Soft Water Make-up LEGEND: u - Rite Steam Boilers Suggested Piping of 15 PSI Low Pressure Steam Boilers For Two Pipe Systems, Wet Gravity Return, Hartford Loop, Operating at 2 PSI or less HeatHeat Heat Userls) Userts) User(s) From Thermostatic Trine of W—f 11ec To Floor Drain Combination water feeder/low water cut-off Water meter 150 WSP rated ball valve 125 WSP rated OS&Y stop valve Threaded pipe cap or plug Union or flange Boiler pressure gauge To Floor Drain Figure 19 NOTE: "B" Dimension should be 30" for every 1 PSI of Boiler Operating Pressure. NOTES PG 52 25 Year Pro -rated Thermaf Warranty Rite engineering & Manufacturing Corp. warrants its Boilers against pressure vessel cracks and broken welds caused by thermal stress cycling ("thermal shock") for a period of 25 years from the date of manufacture. The Warranty - non pro -rated - is limited to the replacement or repair of the pressure vessel when such damage is determined by Rite Engineering or an authorized Rite Representative to have occurred during normal operation. The Warranty shall not cover damage due to freezing, dry firing, or excessive scale build-up. The Warranty is limited to damage to the boiler itself and expressly excludes all other consequential damage. 25 Year Pro -rated Erosion Warranty Rite Engineering & Manufacturing Corp. warrants its Boilers against waterside tube erosion for a period of 25 years from the date of manufacture. Waterside tube erosion - defined as the result of scrubbing action caused by high velocity water flow through a limited number of boiler tubes such as copper finned - will not occur to Rite Boilers because of our greater number of tubes and low pressure drop heat exchanger construction. The Warranty shall not cover damage due to oxygen, electrolysis or acidic corrosion. The Warranty is limited to damage to the boiler itself and expressly excludes all other consequential damage. Addition.( Warranty Coverage Rite Engineering & Manufacturing Corp. warrants its Boilers against defective parts and poor workmanship for a period of 18 months from date of shipment or 12 months from date of start-up - whichever occurs first. Controls, valves and instruments made by other manufacturers and installed on Rite Boilers are generally covered by the same warranty period. Misuse, neglect or exposure shall not be considered grounds for warranty claims. In no case shall Rite Engineering be held liable for any consequential damage including product loss, freight or replacement labor. "Operating instructions specific to limiting thermal stress cyc ►��emay be found on page 8 of this instructional manual ~, v